Bard PA13481-B Wiring Main Power, Wiring 24V LOW Voltage Control Circuit, Transformer Taps

Page 13

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical Specifications” on pages 5 & 7.) All models are suitable for connection with copper wire only. These instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.

The electrical specifications list fuse and wire sizes (75°F copper) for all models including the most commonly used heater sizes.

The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.

WIRING – 24V LOW VOLTAGE CONTROL CIRCUIT

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 6.

TABLE 6

THERMOSTAT WIRE SIZE

 

 

 

Maximum

 

 

 

Distance

Transformer VA

FLA

Wire Gauge

In Feet

 

 

 

 

 

 

20

45

 

 

18

60

55

2.3

16

100

 

 

14

160

 

 

12

250

 

 

 

 

TRANSFORMER TAPS

230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

THERMOSTATS

See specific wiring information for the different models, heater KWs, and voltages on unit and heating wiring diagrams.

TABLE 7

WALL THERMOSTAT AND SUBBASE COMBINATIONS

Thermostat

Subbase

Predominant Features

 

 

 

8403-049

——

2 stage heat, 2 stage cool,

1F93-380

Electronic Programmable

 

 

 

 

8403-042

 

2 stage heat, 1 stage cool,

——

System: Heat-off-cool-Auto Fan: on-auto

T8511G1070

 

Electronic Non-Programmable

 

 

 

 

 

8403-048

 

1 stage heat, 1 stage cool,

——

System: Heat-off-cool Fan: on-auto

T8400C1313

 

Electronic Non-Programmable

 

 

 

 

 

IMPORTANT NOTE: Only the thermostat and subbase combinations as shown above will work with this equipment. The thermostat and subbase MUST be matched, and correct operation can be assured only by proper selection and application of these parts.

Manual

2100-467

Page

13 of 23

Image 13
Contents Bryan, Ohio Bard Manufacturing CompanyContents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Instructions Field Installed Heater Packages OptionalShipping Damage GeneralHz Circuit a Electrical SpecificationsHeater Package Volts Model Phase Htr. KW & Capacity Circuit B Optional Field Installed Electric Heater TableDimensions of Units Unit Dimension ChartTypical Installations InstallationLocation GeneralSlab Mounting AT Ground Level Airflow and Service Access ClearancesAS Required Elevated Mounting PlatformAIR Filters Condensate Drain TrapFilter Requirements & Sizes Condensate Drain TrapWiring 24V LOW Voltage Control Circuit Wiring Main PowerTransformer Taps ThermostatsUnit Control Panel LOW Voltage WiringStart UP Safety PracticesTopping OFF System Charge Start UP NotesStart UP and Operation Three Phase Scroll Compressor Start UP InformationSequence of Operation Indoor Blower MotorAlarm Output AdjustmentsAdjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer LOW Ambient Control WiringService Hints Service and TroubleshootingPressure Service Ports FAN Blade SettingsSuction and Discharge Tube Brazing Brazing DiagramTroubleshooting GE ECM Motors Troubleshooting GE ECM Motors Cont’d On Page 23 in Table Pressure TableReturn Air Pressure 100 105 115 120 125 ModelReturn Air Pressure 100 105 110 115 120 125 Model

PA13601-B, PA13481-A, PA13601-A, PA13481-B, PA13421-A specifications

Bard is a renowned name in the HVAC (Heating, Ventilation, and Air Conditioning) industry, known for its innovative products that ensure comfort and efficiency in various settings. The models PA13421-B, PA13421-A, PA13481-B, PA13601-A, and PA13481-A are prime examples of Bard's commitment to quality and technology, providing reliable performance and advanced features suitable for both commercial and residential applications.

The PA13421-B and PA13421-A are designed for energy efficiency, boasting high SEER (Seasonal Energy Efficiency Ratio) ratings that significantly reduce energy consumption without sacrificing performance. These units utilize a scroll compressor, which is known for its quiet operation and superior reliability. Additionally, they feature advanced microprocessor control systems that allow for precise temperature regulation and can be easily integrated into building management systems.

The PA13481-B and PA13481-A models are equipped with durable, heavy-gauge cabinets that protect the internal components from environmental factors, ensuring longevity and minimal maintenance. These units also incorporate a high-capacity airflow design, which improves indoor air quality by effectively circulating air throughout the space. The implementation of variable-speed blowers further enhances comfort levels by adjusting airflow based on real-time demand.

The PA13601-A model stands out with its versatility, as it can operate effectively in a wide range of climates. Its design includes a robust refrigerant management system that ensures optimal performance even in extreme temperatures, making it a favorite for users in harsher environments. This model also features a comprehensive diagnostic system that alerts users to potential issues before they escalate, facilitating proactive maintenance.

All these models emphasize sustainability, incorporating environmentally friendly refrigerants that comply with international regulations. Bard's dedication to reducing carbon footprints is evident in these units, which not only perform admirably but also contribute to a greener planet.

In summary, the Bard PA13421-B, PA13421-A, PA13481-B, PA13601-A, and PA13481-A models exemplify cutting-edge technology and superior engineering in the HVAC sector. With their energy-efficient designs, robust construction, and advanced control systems, these HVAC solutions provide reliable comfort for users while being mindful of environmental impact.