WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring muse conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

WIRING – LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8:

TABLE 3

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

Distance

VA

FLA

Wire Gauge

In Feet

 

 

 

 

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 guage

160

 

 

12 guage

250

 

 

 

 

TABLE 4

WALL THERMOSTAT AND SUBBASE COMBINATIONS

Thermostat

Subbase

Predominate Features

 

 

 

8403-002

8404-003

1 stage heat, 1 stage cool

T87F3111

Q539A1220

System: heat-off-cool Fan: auto-on

 

 

 

8403-041

---

1 stage heat, 1 stage cool

T8034C

 

System: heat-off-cool Fan: auto-on

 

 

 

8403-019

8404-012

1 stage cool, 2 stage heat

T874C1760

Q674A1001

System: heat-auto-cool

Fan: auto-on

 

 

 

8403-021

8404-012

2 stage cool, 2 stage heat

T874D1934

Q674A1001

System: heat-auto-cool

Fan: auto-on

 

 

 

8403-035

---

2 stage cool, 2 stage heat

1F95-80

 

Electronic 7 day programming

 

 

 

8403-043

---

1 stage heat, 1 stage cool

CM-200

System: heat-off-cool

Fan: auto-on

 

 

 

 

 

Manual 2100-218 Page 12

Image 14
Contents WA421 WA482 WA602 ModelsContents Getting Other Information and Publications Electric Heat Table Wall Mount General InformationHeat Pump Wall Mount Model Nomenclature Unit Dimensions Front View Side View Back ViewElectrical Specifications Single CircuitDuct Work Shipping DamageGeneral Condensate Drain FiltersFresh AIR Intake Fresh AIR DamperMounting the Unit Installation InstructionsWall Mounting Information Mounting Instructions Electric Heat Clearance Wall Mounting Instructions See Mounting InstructionsCommon Wall Mounting Installations Thermostat Wire Size Wiring Main PowerWiring LOW Voltage Wiring TAP RangeUnit 24V Terminal Board Start UP Compressor Control Module Service HintsSequence of Operation Typical Settings for Dual Unit Installation Phase MonitorPressure Service Ports Removal of FAN Shroud TroubleshootingFAN Blade Setting Dimensions Refrigerant ChargePressure Table Cooling Recommended AirflowMaximum ESP of Operation Electric Heat only Optional Accessories

WA482, WA421 specifications

Bard WA482 and WA421 are high-performance air conditioning units designed for commercial and industrial applications. These models are renowned for their exceptional cooling efficiency, durability, and versatile performance, making them suitable for a variety of settings, including schools, factories, and office buildings.

One prominent feature of the Bard WA482 is its powerful cooling capacity. It has an impressive cooling output that can effectively manage indoor temperatures, even in the hottest conditions. This capability ensures optimal comfort for occupants while maintaining energy efficiency. Similarly, the Bard WA421 offers substantial cooling capacity, catering to smaller commercial spaces without compromising on performance.

Both models utilize advanced technology to enhance their operational efficiency. The units are equipped with a high-efficiency scroll compressor that minimizes energy consumption while delivering consistent cooling. This technology allows businesses to reduce their energy costs significantly, contributing to environmental sustainability.

Another significant characteristic of Bard WA482 and WA421 is their robust construction. Built with heavy-gauge galvanized steel, these units are designed to withstand tough environmental conditions. This durability ensures a long operational life, reducing the need for frequent repairs and replacements. The units are also corrosion-resistant, making them ideal for coastal or humid regions.

Efficiency is further enhanced by the inclusion of a multi-speed fan that allows for better airflow management. This feature enables the units to adjust their functioning based on the current cooling demand, optimizing energy use and minimizing noise levels. Consequently, users experience a comfortable environment without disruptive sound.

Maintenance is made simple with these models thanks to their accessible design. The units feature removable panels that provide easy access to internal components for routine servicing. This design minimizes downtime and helps maintain the overall efficiency of the system.

In terms of versatility, Bard WA482 and WA421 can be customized with various kits and options, including digital thermostats and advanced control systems. This adaptability enables users to tailor the cooling solutions to their specific needs, enhancing overall satisfaction.

In summary, Bard WA482 and WA421 stand out in the commercial air conditioning sector due to their impressive cooling capacity, energy-efficient technologies, robust construction, and ease of maintenance. These characteristics make them a reliable choice for businesses looking to maintain a comfortable and sustainable indoor environment.