Friedrich H)A24K10L, R410A Electrical Troubleshooting Chart Cooling 24K BTU, Circuit Breakers are

Page 34

ELECTRICAL TROUBLESHOOTING CHART - COOLING

24K BTU

NO COOLING OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Before continuing

 

 

 

 

 

 

 

 

check for Error

 

 

Insure that Fuses

 

 

 

 

 

 

 

 

 

Codes, see

 

 

are good and/or that

 

 

 

electronics control

 

 

Circuit Breakers are

 

 

 

diagnostics and

 

on and voltage is 208/230

 

 

 

 

 

 

 

 

 

 

 

test mode, page 15

 

 

O.K.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor and outdoor fan motor run but indoor blower does not run

Yes

Indoor blower runs but outdoor fan motor and compressor do not run

Yes

No

Set thermostat to "Cool," move the Temp. lever below the present Room Temp.

O.K.

Compressor outdoor fan motor and indoor blower should now operate

Yes

See Refrigerant Circuit diagnosis if unit still is not cooling properly

Nothing operates, entire system appears dead

 

 

 

No

Yes

 

 

 

Line voltage present at the Transformer Primary

Yes

24 Volts at

“R” Terminal on board

Yes

24 Volts present at Y terminals on t-stat and board?

Yes

No

No

No

Check Supply Circuit’s jumper at transformer. If okay, replace board

Problems indicated with

Control Transformer replace board

Problems indicated with Room Thermostat or Control Wiring

 

 

 

 

 

 

208/230 Volts present

 

 

24V at t-stat and

 

Defective t-stat

 

 

 

at #1 relay and “OD”

 

 

 

 

 

 

 

 

 

 

 

 

terminal on board?

No

 

 

defective control wiring

 

 

 

 

control wiring?

No

 

 

 

 

 

 

 

or transformer

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230 Volts present

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at compressor’s

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

contactor?

 

 

 

 

 

 

 

 

Yes

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

Is Line Voltage present

 

 

Problems indicated

 

 

 

 

 

 

 

 

 

 

in Blower Relay

 

 

 

 

 

 

 

 

at Motor Leads?

No

 

 

 

 

 

 

 

 

 

 

 

 

of board

 

 

Supply Circuit

 

Is Locked Rotor

 

 

Yes

 

 

 

 

 

problems, loose

 

 

 

 

 

 

 

 

Connections, or bad

 

Voltage a minimum of

 

 

 

 

 

 

No

 

 

 

 

 

 

 

Relays/Board

197 Volts?

 

 

 

 

 

 

 

 

 

 

 

 

Yes

Check Capacitor, is

 

 

Replace Capacitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacitor Good?

No

 

 

Replace Capacitor

 

Are Capacitor and (if

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and/or Start Assist

 

so equipped) Start

 

 

Yes

 

 

 

 

 

Device

No

Assist good?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible motor

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Motor should run

 

 

problem indicated.

 

 

 

 

 

No

 

Check motor

 

 

 

 

 

 

 

 

 

 

thoroughly

 

 

 

 

 

 

 

 

 

 

 

 

Allow ample time

 

Have System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for pressures to

No

Pressures Equalized?

 

 

 

 

 

 

 

 

equalize

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

Possible Compressor

 

 

 

 

 

 

 

 

 

 

 

 

problem indicated.

 

Compressor should

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

See Compressor

 

run

 

 

 

 

 

 

 

 

Checks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace board

Check contactor

If defective replace

Compressor and outdoor fan motor should now operate

Yes

See Refrigerant

Circuit Diagnosis

if unit still is not

cooling properly

32

Image 34
Contents R v i c e M a n u a l R 4 1 0 a M o d e l s Technical Support Contact Information IntroductionTable of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Property Damage Hazards Month Manufactured Serial Number Year ManufacturedProduction RUN Number Product Line Chassis Specifications ModelExtended Cooling Performance Indoor WET Bulb TEMP. Degrees F AT 80 F D.BElectrical Requirements Electric Shock HazardRemote Thermostat and Low Voltage Control Connections RT5 Two speed fan RT4 One speed fanThermostat Connections Electronic Control Board Features Quiet Start/StopElectronic Control Configuration Diagnostics Electronic Control Error Code DiagnosticsTest Mode Vpak electronic control Features Thermostat CompatibilityExternal Static Pressure Explanation of charts Capacitor Check with Capacitor Analyzer Components TestingCapacitors Capacitor ConnectionsHeater Elements and Limit SWITCHES’ Specifications Components TestingDrain PAN Valve Refrigeration Assembly Refrigeration Sequence of OperationService CUT/SEVER HazardEquipment Must be Capable Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockBurn Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Freeze HazardOvercharged Refrigerant Systems Restricted Refrigerant SystemCheck Valve Hermetic Components CheckMetering Device Capillary Tube SystemsReversing Valve DESCRIPTION/OPERATION Testing the CoilChecking the Reversing Valve Touch Test in Heating/Cooling Cycle Procedure For Changing Reversing ValveFire Hazard Compressor Checks Internal Overload Vpak 24 K Btus Single Phase Resistance TestExternal Overload Vpak 9, 12, 18 K Btus Ground TestRecommended procedure for compressor replacement Compressor ReplacementHigh Temperatures Routine Maintenance Electrical Shock HazardElectrical Troubleshooting Chart Cooling 9K BTU, 12K BTU, & 18K BTUElectrical Troubleshooting Chart Cooling 24K BTU Circuit Breakers areElectrical Troubleshooting Chart Heat Pump Heat Pump ModeTroubleshooting Chart Cooling Troubleshooting Chart HeatingVEA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Electric HeatVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Technical Service Data Technical Service DataVPK-ServMan-L Friedrich AIR Conditioning CO
Related manuals
Manual 7 pages 15.54 Kb Manual 61 pages 11.89 Kb Manual 27 pages 24.75 Kb

H)A09K25L, H)A12K50L, H)A09K50L, H)A24K10L, H)A24K25L specifications

Friedrich R410A is a refrigerant blend that has become a cornerstone in the HVAC industry, particularly for air conditioning systems. This hydrofluorocarbon (HFC) is known for its efficiency and environmentally friendly properties, making it a popular alternative to older refrigerants like R22.

One of the main features of R410A is its exceptional thermal efficiency. It has a higher cooling capacity compared to R22, which allows for smaller and more efficient equipment. This efficiency translates to reduced energy consumption and lower operating costs for users. Additionally, the higher pressure capability of R410A enables the design of more compact systems, which is particularly beneficial for residential and commercial applications where space is often limited.

R410A is characterized by its zero ozone depletion potential (ODP), which is a significant advantage over its predecessors. This makes it a more environmentally responsible choice, aligning with global initiatives to phase out substances that harm the ozone layer. However, it is essential to note that while R410A does not deplete the ozone, it does have a global warming potential (GWP) of approximately 2,088, making it less favorable in terms of climate impact compared to natural refrigerants.

In terms of technology, R410A is typically utilized in systems that are designed specifically for this refrigerant. Equipment compatible with R410A often features advanced components that can handle the higher pressures required. Many modern air conditioning systems equipped with R410A also incorporate variable-speed compressors and advanced electronic controls, enhancing overall performance and comfort.

Additionally, R410A systems often come equipped with variable refrigerant flow (VRF) technology, which allows for precise temperature control in multiple zones of a building. This versatility makes R410A an ideal choice for both residential and commercial installations, providing optimal comfort throughout various spaces.

In summary, Friedrich R410A stands out due to its high energy efficiency, zero ozone depletion potential, and suitability for modern HVAC technologies. As the industry moves towards more sustainable practices, R410A serves as a reliable refrigerant that balances performance with environmental responsibility. It’s a significant choice for anyone looking to invest in efficient and eco-friendly heating and cooling solutions.