Correct CFM (if needed):

Chart B – Correction Multipliers

Explanation of charts

Chart A is the nominal dry coil VERT-I-PAK CFMs. Chart B is the correction factors beyond nominal conditions.

1 ½ TON SYSTEM ( 18,000 Btu)

Operating on high speed @ 230 volts with dry coil measured external static pressure .10

Air Flow = 450 CFM

In the same SYSTEM used in the previous example but having a WET coil you must use a correction factor of

.95 (i.e. 450 x .95=428 CFM) to allow for the resistance (internal) of the condensate on the coil.

It is important to use the proper procedure to check external

Ductwork Preparation

If flex duct is used, be sure all the slack is pulled out of the flex duct. Flex duct ESP can increase considerably when not fully extended. DO NOT EXCEED a total of .30 ESP, as this is the MAXIMUM design limit for the VERT-I-PAK A-Series unit.

IMPORTANT: FLEX DUCT CAN COLLAPSE AND CAUSE AIRFLOW RESTRICTIONS. DO NOT USE FLEX DUCT FOR: 90 DEGREE BENDS, OR UNSUPPORTED RUNS OF 5 FT. OR MORE.

Fresh Air Door

The Fresh Air Door is an “intake” system. The fresh air door opened via a slide on the front of the chassis located just above the indoor coil. Move the slide left to open and right to close the fresh air door. The system is capable of up to 60 CFM of fresh air @ ~.3” H20 internal static pressure.

Checking Approximate Airflow

If an inclined manometer or Magnehelic gauge is not available to check the External Static Pressure, or the blower performance data is unavailable for your unit, approximate air flow call be calculated by measuring the temperature rise, then using tile following criteria.

KILOWATTS x 3413

Static Pressure and determine actual airflow. Since in

Temp Rise x 1.08

= CFM

the case of the VERT-I-PAK, the condensate will cause a reduction in measured External Static Pressure for the given airflow.

It is also important to remember that when dealing with VERT-l-PAK units that the measured External Static Pressure increases as the resistance is added externally to the cabinet. Example: duct work, filters, grilles.

Indoor Airflow Data

The Vert-I-Pak A series units must be installed with a free return air configuration. The table below lists the indoor airflow at corresponding static pressures. All units are rarted at low speed.

The Vert-I-Pak units are designed for either single speed or two fan speed operation. For single speed operation refer to the airflow table below and select the most appropriate CFM based on the ESP level. Connect the fan output from the thermostat to the unit on either the GL terminal for low speed or to the GH terminal for high speed operation.

For thermostats with two-speed fan outputs connect the low speed output to the unit GL terminal and the high speed output to the GH terminal.

Electric Heat Strips

The approximate CFM actually being delivered can be calculated by using the following formula:

DO NOT simply use the Kilowatt Rating of the heater (i.e. 2.5, 3.4, 5.0) as this will result in a less-than-correct airflow calculation. Kilowatts may be calculated by multiplying the measured voltage to the unit (heater) times the measured current draw of all heaters (ONLY) in operation to obtain watts. Kilowatts are than obtained by dividing by 1000.

EXAMPLE: Measured voltage to unit (heaters) is 230 volts. Measured Current Draw of strip heaters is 11.0 amps.

230 x 11.0 = 2530 2530/1000 = 2.53 Kilowatts 2.53 x 3413 = 8635

Supply Air

 

95 F

Return Air

 

°

 

75 F

Temperature Rise

 

°

20°

20 x 1.08 = 21.6

 

 

863521.6 = 400 CFM

16

Image 18
Contents R v i c e M a n u a l R 4 1 0 a M o d e l s Technical Support Contact Information IntroductionTable of Contents Important Safety Information Your safety and the safety of others are very importantRefrigeration System Hazards Property Damage Hazards Serial Number Year Manufactured Month ManufacturedProduction RUN Number Product Line Chassis Specifications ModelExtended Cooling Performance Indoor WET Bulb TEMP. Degrees F AT 80 F D.BElectrical Requirements Electric Shock HazardRemote Thermostat and Low Voltage Control Connections RT5 Two speed fan RT4 One speed fanThermostat Connections Electronic Control Board Features Quiet Start/StopElectronic Control Configuration Electronic Control Error Code Diagnostics DiagnosticsTest Mode Vpak electronic control Features Thermostat CompatibilityExternal Static Pressure Explanation of charts Capacitor Check with Capacitor Analyzer Components TestingCapacitors Capacitor ConnectionsComponents Testing Heater Elements and Limit SWITCHES’ SpecificationsDrain PAN Valve Refrigeration Assembly Refrigeration Sequence of OperationService CUT/SEVER HazardEquipment Must be Capable Sealed Refrigeration System RepairsEquipment Required Risk of Electric ShockBurn Hazard Method Of Charging / RepairsUndercharged Refrigerant Systems Freeze HazardOvercharged Refrigerant Systems Restricted Refrigerant SystemCheck Valve Hermetic Components CheckMetering Device Capillary Tube SystemsTesting the Coil Reversing Valve DESCRIPTION/OPERATIONChecking the Reversing Valve Procedure For Changing Reversing Valve Touch Test in Heating/Cooling CycleFire Hazard Compressor Checks Internal Overload Vpak 24 K Btus Single Phase Resistance TestExternal Overload Vpak 9, 12, 18 K Btus Ground TestCompressor Replacement Recommended procedure for compressor replacementHigh Temperatures Routine Maintenance Electrical Shock HazardElectrical Troubleshooting Chart Cooling 9K BTU, 12K BTU, & 18K BTUElectrical Troubleshooting Chart Cooling 24K BTU Circuit Breakers areElectrical Troubleshooting Chart Heat Pump Heat Pump ModeTroubleshooting Chart Cooling Troubleshooting Chart HeatingVEA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Electric HeatVHA 09/12/18 with 2.5 KW, 3.4 KW or 5KW Cool with Electric Heat Heat Pump with Electric Heat Cool with Electric Heat Heat Pump with Electric Heat Technical Service Data Technical Service DataVPK-ServMan-L Friedrich AIR Conditioning CO
Related manuals
Manual 7 pages 15.54 Kb Manual 61 pages 11.89 Kb Manual 27 pages 24.75 Kb

H)A09K25L, H)A12K50L, H)A09K50L, H)A24K10L, H)A24K25L specifications

Friedrich R410A is a refrigerant blend that has become a cornerstone in the HVAC industry, particularly for air conditioning systems. This hydrofluorocarbon (HFC) is known for its efficiency and environmentally friendly properties, making it a popular alternative to older refrigerants like R22.

One of the main features of R410A is its exceptional thermal efficiency. It has a higher cooling capacity compared to R22, which allows for smaller and more efficient equipment. This efficiency translates to reduced energy consumption and lower operating costs for users. Additionally, the higher pressure capability of R410A enables the design of more compact systems, which is particularly beneficial for residential and commercial applications where space is often limited.

R410A is characterized by its zero ozone depletion potential (ODP), which is a significant advantage over its predecessors. This makes it a more environmentally responsible choice, aligning with global initiatives to phase out substances that harm the ozone layer. However, it is essential to note that while R410A does not deplete the ozone, it does have a global warming potential (GWP) of approximately 2,088, making it less favorable in terms of climate impact compared to natural refrigerants.

In terms of technology, R410A is typically utilized in systems that are designed specifically for this refrigerant. Equipment compatible with R410A often features advanced components that can handle the higher pressures required. Many modern air conditioning systems equipped with R410A also incorporate variable-speed compressors and advanced electronic controls, enhancing overall performance and comfort.

Additionally, R410A systems often come equipped with variable refrigerant flow (VRF) technology, which allows for precise temperature control in multiple zones of a building. This versatility makes R410A an ideal choice for both residential and commercial installations, providing optimal comfort throughout various spaces.

In summary, Friedrich R410A stands out due to its high energy efficiency, zero ozone depletion potential, and suitability for modern HVAC technologies. As the industry moves towards more sustainable practices, R410A serves as a reliable refrigerant that balances performance with environmental responsibility. It’s a significant choice for anyone looking to invest in efficient and eco-friendly heating and cooling solutions.