Friedrich 920-087-04 (3-05) manual Dimensions, LintelInstallation

Page 10

920-087-04 (3-05)

Figure6

Dimensions

¼"

A (6.4 cm) min.

13¾"

(35 cm)

B

Wall

 

A

 

B

Dimension*

Allow

Allow for floor finishing

 

for wall

 

 

 

finishing

 

 

 

(Minimum)

Min.

Max

No Accessories

¼"

¼"

 

 

(6.4 mm)*

(6.4 mm)

---

With Subbase

1¾"

3½"

5"

 

(4.5 cm)

(8.9cm)

(12.7cm)

With Lateral Duct

¾"

¼"

 

 

(1.9 cm)

(6.4 mm)

---

*If more than one accessory is to be used, use the maximum dimension. If the wall thickness is more than 13¾" (35cm) - (A + ¼" [6.4 mm]), a sleeve extension must be used.

3.Drill two 3/16" holes through each side of the sleeve approximately 4" from top and 4" from bottom of sleeve. Screw four #10 x 1" screws (included) or appropriate fasteners for your installation, through the holes in the sides of the wall sleeve.

4.Apply sealant around the wall sleeve where it projects through the inside and outside wall surfaces. Apply the sealant to the screw heads or the tops of the fasteners used in Step #3.

NOTE: When sealing the sleeve on the outside of the building, be careful NOT to let the sealant block the two condensate drain holes or the four overfl ow slots at the bottom flange of the sleeve.

5.If the chassis and exterior grille are to be installed later, leave the weatherboard and center support in place, otherwise remove and dispose of them.

6.Provide a support lintel if the wall sleeve is installed in a concrete or masonry wall. (See Figure 7.)

Figure7

LintelInstallation

Main studs

Jack studs

Lintel

Main studs

Jack studs

Mounting screw holes

No holes in bottom of wall sleeve unless drain kit is used

NOTE: Construct wall opening to comply with all applicable building codes.

10

Image 10
Contents Ptac Standard Control Remote Thermostat Seacoast ProtectedTable of Contents Model Number Code Ptac Installation Recommendations Building ElevationFriedrich Digital Control Features DigitalTemperatureHeatPumpMode Drain Kit Location and Installation Installation Instructions PXDR10 Drain KitInternal Drain optional for new construction Cover Plate Installation ExternalDrainfor new construction or unit replacementDrain Tube Installation Drain Kit InstallationWall Sleeve Installation Instructions Pdxws TypicalWallSleeveInstallationDimensions LintelInstallationExtension Installation Section II Deep Wall Installation PxweWall Sleeve Extension Sealant Locations Installation Instructions Model Pxga Standard Grille Standard Grille15/20A Lcdi Device Power Cord Information 230/208V models onlyElectrical Rating Tables 30A Lcdi DeviceInstallation Checklist Section III Chassis InstallationWall sleeve Wall sleeve flange Chassis flange and gasket Factory Dip Switch Configuration Dip Switch SettingDigital Control User Input Configuration Digital Control Operation Control board with optional Pdxrt escutcheon kit installed Remote Thermostat and Low Voltage Control ConnectionsDesk Control Terminals Fresh Air Vent ControlAir Discharge Grille Auxiliary Fan ControlStart-up Checklist Appendix a Electrical Wiring for 265 Volt Models Line Voltage ConnectionsRoutine Maintenance ComponentsEnvironmental Effects Heating Mode Basic Troubleshooting TechniquesEnvironmental Effects Cooling Mode Insufficient Maintenance and InspectionDiagnostics Digital Control Diagnostics and Test ModeTest Mode Friedrich Ptac Accessories Pxdl Friedrich Air Conditioning Company 920-087-04