A. Electrical Rating Tables
All230/208voltunitsareequippedwithpowercords.SeeAppendixBonpage19forwiringinstructionson265Vunits.
NOTE: Use Copper Conductors ONLY. Wire sizes are per NEC, check local codes for overseas applications.
Table 1 | 250 V Receptacles and Fuse Types |
| |||
AMPS |
| 15 | 20* |
| 30 |
RECEPTACLE |
|
|
|
|
|
|
|
|
|
| |
| 15 | 20 |
| 30 | |
(or HACR circuit breaker) |
| ||||
|
|
|
|
HACR – Heating, Air Conditioning, Refrigeration
*May be used for 15 Amp applications if fused for 15 Amp NOTE: 265 volt units are hard wired.
Table 2 | Recommended branch circuit wire sizes* | ||
NAMEPLATE / MAXIMUM | AWG WIRE SIZE** | ||
CIRCUIT BREAKER SIZE | |||
| |||
| 15 | 14 | |
| 20 | 12 | |
| 30 | 10 |
AWG – American Wire Gauge * Single circuit from main box
** Based on copper wire, single insulated conductor at 60°C
ELECTRIC SHOCK HAZARD! Turn off electric power before service or installation. All electrical connections and wiring MUST be installed by a qualified electrician and conform to the National Electrical Code and all local codes which have jurisdiction. Failure to do so can result in property damage, personal injury and/or death.
WIRE SIZE | Use ONLY wiring size recommended for | |
single outlet branch circuit. | ||
| ||
|
| |
| Use ONLY type and size fuse or HACR cir- | |
FUSE/CIRCUIT | cuit breaker indicated on unit’s rating plate. | |
Proper current protection to the unit is the | ||
BREAKER | ||
responsibility of the owner. NOTE: A time | ||
| ||
| delay fuse is provided with 265V units. | |
|
| |
| Unit MUST be grounded from branch circuit | |
| through service cord to unit, or through sep- | |
| arate ground wire provided on permanently | |
| connected units. Be sure that branch circuit | |
GROUNDING | or general purpose outlet is grounded. The | |
field supplied outlet must match plug on | ||
| ||
| service cord and be within reach of service | |
| cord. Refer to Table 1 for proper receptacle | |
| and fuse type. Do NOT alter the service cord | |
| or plug. Do NOT use an extension cord. | |
|
| |
| The field supplied outlet must match plug on | |
RECEPTACLE | service cord and be within reach of service | |
cord. Refer to Table 1 for proper receptacle | ||
| and fuse type. Do NOT alter the service cord | |
| or plug. Do NOT use an extension cord. | |
|
| |
| Use recommended wire size given in Table | |
WIRE SIZING | 2 and install a single branch circuit. All wiring | |
must comply with local and national codes. | ||
| ||
| NOTE: Use copper conductors only. | |
|
|
B. Power Cord Information (230/208V models only)
All Friedrich 230/208V PTAC units are shipped from the factory with a Leakage Current Detection Interrupter (LCDI) equipped power cord. The LCDI device meets the UL and NEC requirements for cord connected air conditioners effective August 2004.
To test your power supply cord:
1.Plug power supply cord into a grounded 3 prong outlet.
2.Press RESET.
3.Press TEST (listen for click; Reset button trips and pops out).
4.Press and release RESET (listen for click; Reset button latches and remains in). The power supply cord is ready for operation.
Figure10a |
| 4.1" |
| ||
|
|
15/20A LCDI Device
2" | RESET | TEST |
|
| Test Button |
|
| Reset Button |
NOTE: The LCDI device is not intended to be used as a switch.
Once plugged in the unit will operate normally without the need to reset the LCDI device. If the LCDI device trips and requires resetting the cause of the trip should be identified prior to further use of the PTAC.
If the device fails to trip when tested or if the power supply cord is damaged it must be replaced with a new supply cord obtained from the product manufacturer, and must not be repaired.
Figure10b |
30A LCDI Device |
7" |
2" |
Test Button |
Reset Button |
13 |