Friedrich 920-087-04 (3-05) manual Digital Control Operation

Page 17

920-087-04 (3-05)

Digital Control Operation

TemperatureDisplay

The Friedrich digital PTAC is shipped from the factory to display the desired room temperature on the LED readout.

The unit can be configured to display the room temperature by simultaneously pressing the ‘Cool’ and ‘High Fan’ buttons for three seconds the display will show an ‘R’ for one seconds to acknowledge the change. The unit will display the setpoint whenever the ‘Temp’ or buttons are pressed and then switch back to room temperature.

To revert back to displaying the setpoint only press the ‘Cool’ and ‘Low Fan’ buttons for three seconds simultaneously, the unit will display an ‘S’ for one seconds to acknowledge the change.

ºF vs. ºC Display

The unit is factory confi gured to display all temperatures in degrees Fahrenheit (ºF). To switch to degrees Celsius press the ‘Fan Only’ and ‘Low Fan’ buttons simultaneously for three seconds. The display will show a ‘C’ as acknowledgement of the change.

To revert back to ºF press the ‘Fan Only’ and Low Fan’ buttons simultaneously for three seconds. The display will show an ‘F’ as acknowledgement of the change.

Cooling Mode

Pressing the ‘Cool’ button while the unit is in any mode, including off, will put the unit into cooling mode. Adjust the temperature readout to the desired room temperature and the unit will cycle the compressor on and off to maintain a comfortable room. The compressor will come on anytime that the room temperature is 1.8°F above the desired temperature. The fan operation is dependent on the fan mode selected, either continuous or cycling. See page 16 for fan cycle control.

Heating Mode

Pressing the ‘Heat’ button while the unit is in any mode, including off, will put the unit into heating mode.

HeatPumpModels(PDH)

When the ‘Heat’ button is pressed initially the unit will energize the electric resistance heat to quickly bring the room to the set temperature. When the desired room temperature falls 1.8°F below the desired set temperature the unit will cycle the compressor on and operate as a heat pump to maintain the room temperature while running more efficiently than resistance heat only models. If the room temperature should fall more than 5°F from the set temperature the unit will run the resistance heater. The fan operation is dependent on the fan mode selected, either continuous or cycling. Dip switch 5 controls the fan mode, see page 16 for setting.

When the outdoor coil temperature falls below 30°F for more than 2 minutes the unit will operate the resistance heaters and not the compressor. When the outdoor coil temperature reaches 45°F the compressor will be allowed to operate again.

Figure12

Digital Control Panel

Heat/CoolModels(PDE)

After pressing the ‘Heat’ button, adjust the temperature readout to the desired room temperature and the unit will cycle the resistance heat on and off to maintain a comfortable room. The heater will come on anytime that the room temperature is 1.8°F below the desired temperature. The fan operation is dependent on the fan mode selected, either continuous or cycling. Dip switch 5 controls the fan mode, see page 16 for setting.

EmergencyHeatOperation

In the event of a compressor failure in heat pump mode the compressor may be locked out to provide heat through the resistance heater. This feature ensures that even in the unlikely event of a compressor failure the room temperature can be maintained until the compressor can be serviced. Dip switch 7 controls the emergency heat setting, see page 16.

Fan Mode

FanOnly

Pressing the ‘Fan Only’ button will run the fan to allow for air circulation in the room without operating the compressor or heater regardless of the room or set temperature. The fan speed selection is made by pressing either the ‘High Fan’ or ‘Low Fan’ button.

Cycle/Continuous

The owner may choose between fan cycling or fan continuous mode based on property preference. (Note: Even heat monitoring and quiet start/stop fan delay only operate in fan cycle mode) Fan continuous mode is used to keep constant airfl ow circulation in the room during all times the unit is ‘ON’. Fan cycle will conserve energy by only operating the fan while the compressor or electric heater is operating. Dip switch 5 controls the fan mode, see page 16 for setting.

17

Image 17
Contents Standard Control Remote Thermostat Seacoast Protected PtacTable of Contents Model Number Code Building Elevation Ptac Installation RecommendationsDigitalTemperature Friedrich Digital Control FeaturesHeatPumpMode Internal Drain optional for new construction Installation Instructions PXDR10 Drain KitDrain Kit Location and Installation Drain Tube Installation ExternalDrainfor new construction or unit replacementCover Plate Installation Drain Kit InstallationTypicalWallSleeveInstallation Wall Sleeve Installation Instructions PdxwsLintelInstallation DimensionsWall Sleeve Extension Sealant Locations Section II Deep Wall Installation PxweExtension Installation Standard Grille Installation Instructions Model Pxga Standard GrilleElectrical Rating Tables Power Cord Information 230/208V models only15/20A Lcdi Device 30A Lcdi DeviceSection III Chassis Installation Installation ChecklistWall sleeve Wall sleeve flange Chassis flange and gasket Digital Control User Input Configuration Dip Switch SettingFactory Dip Switch Configuration Digital Control Operation Remote Thermostat and Low Voltage Control Connections Control board with optional Pdxrt escutcheon kit installedAir Discharge Grille Fresh Air Vent ControlDesk Control Terminals Auxiliary Fan ControlStart-up Checklist Line Voltage Connections Appendix a Electrical Wiring for 265 Volt ModelsComponents Routine MaintenanceEnvironmental Effects Cooling Mode Basic Troubleshooting TechniquesEnvironmental Effects Heating Mode Insufficient Maintenance and InspectionTest Mode Digital Control Diagnostics and Test ModeDiagnostics Friedrich Ptac Accessories Pxdl Friedrich Air Conditioning Company 920-087-04