SPECIFICATIONS
UNIT |
|
| |||||
Operating Weight (Lb) | 214 |
| 202 |
| 237 | ||
|
|
|
|
|
|
|
|
ELECTRICAL |
|
|
|
|
| ||
Unit |
|
|
|
| |||
|
|
|
|
|
|
|
|
Operating Voltage Range* |
|
|
|
| |||
|
|
|
|
|
|
|
|
Compressor— Rated Load Amps | 12.8 |
| 14.7 |
| 15.4/16.7 | ||
|
|
|
|
|
|
|
|
|
| Locked Rotor Amps | 60.0 |
| 72.5 |
| 83.0/79.0 |
|
|
|
|
|
|
|
|
Condenser Fan | 0.80 |
| 0.80 |
| 1.1 | ||
|
|
|
|
|
|
|
|
Min Unit Ampacity for Wire Sizing | 16.8 |
| 19.2 |
| 20.2/22.0 | ||
|
|
|
|
|
|
|
|
Min Wire Size (60°C Copper) AWG† | 14 |
| 14 |
| 12 | ||
|
|
|
|
|
|
|
|
Min Wire Size (75°C Copper) AWG† | 14 |
| 14 |
| 12 | ||
|
|
|
|
|
|
|
|
Max Wire Length (Ft) (60°C Copper)‡ | 46 |
| 41 |
| 62/57 | ||
|
|
|
|
|
|
|
|
Max Wire Length (Ft) (75°C Copper)‡ | 44 |
| 39 |
| 59/54 | ||
|
|
|
|
|
|
|
|
Max Branch Circuit Fuse or |
|
|
|
|
| ||
Circuit Breaker Size (Amps) | 25 |
| 30 |
| 30 | ||
|
|
|
|
|
|
|
|
COMPRESSOR & REFRIGERANT |
|
|
|
|
| ||
Compressor— Type |
|
| Scroll |
|
| ||
|
|
|
|
|
|
|
|
Temperature & Current Protection |
|
| Internal Line Break |
|
| ||
|
|
|
|
|
|
|
|
Refrigerant— Type |
|
| Puron® |
|
| ||
|
|
|
|
|
|
|
|
| Amount (Lb) | 5.50 |
| 6.00 |
| 6.88 | |
|
|
|
|
|
|
|
|
CONDENSER COIL & FAN |
|
|
|
|
| ||
Coil Face Area (Sq Ft) | 12.2 |
| 12.2 |
| 15.2 | ||
|
|
|
|
|
|
|
|
Fins per |
|
| |||||
|
|
|
|
|
|
|
|
Fan | 1/8 & 825 |
| 1/8 & 825 |
| 1/5 & 825 | ||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
Condenser Airflow (CFM) | 2400 |
| 2400 |
| 2800 | ||
|
|
|
|
|
|
|
|
OPTIONAL EQUIPMENT |
|
|
|
|
| ||
Support Feet |
|
| KSASF0101AAA |
|
| ||
|
|
|
|
|
|
|
|
Coastal Filter |
|
| KAACF0801MED |
|
| ||
Time Delay Relay |
|
| KAATD0101TDR |
|
| ||
|
|
|
|
|
|
|
|
Cycle Protector |
|
| KSACY0101AAA |
|
| ||
|
|
|
|
|
|
|
|
Crankcase Heater |
|
| KAACH1201AAA |
|
| ||
|
|
|
|
|
|
|
|
Start |
|
| KSAHS1501AAA |
|
| ||
|
|
|
|
|
|
| |
Start | Standard |
|
| KAACS0201PTC | |||
|
|
|
|
|
|
|
|
TXV (Hard Shutoff) | KSATX0201PUR |
|
| KSATX0301PUR | |||
|
|
|
|
|
|
|
|
Piston Body |
|
| KSAPX0101PIS |
|
| ||
|
|
|
|
|
|
|
|
Filter Drier (Suction Line) |
|
| KH45LG140 (RCD) |
|
| ||
|
|
|
|
|
|
|
|
Evaporator Freeze Thermostat** |
|
| KAAFT0101AAA |
|
| ||
|
|
|
|
|
|
|
|
|
| KAALS0201LLS |
|
| |||
|
|
|
|
|
|
|
|
Winter Start Control** |
|
| KAAWS0101AAA |
|
| ||
|
|
|
|
|
|
|
|
|
| KSALA0301410 |
|
| |||
|
|
|
|
|
|
|
|
MotorMaster® |
|
| KSALA0401AAA |
|
| ||
|
|
|
|
|
|
|
|
Ball Bearing Fan Motor |
|
| HC38GE231 (RCD) |
|
| ||
|
|
|
|
|
|
|
|
Thermidistat™ Control— |
|
|
|
|
| ||
Programmable Thermostat with Humidity Control |
|
|
|
| |||
|
|
|
|
| |||
|
|
|
|
| |||
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| |||
|
|
|
| ||||
|
|
|
|
| |||
|
|
|
|
| |||
|
| TSTATBBSAC01 |
|
| |||
Builder’s |
|
|
|
|
| ||
|
|
|
|
| |||
|
|
|
| ||||
|
|
|
|
|
|
|
|
Outdoor Air Temperature Sensor |
|
|
|
| |||
|
|
|
|
|
|
|
|
Backplate for |
|
| TSTATXXNBP01 |
|
| ||
|
|
|
|
|
|
|
|
Backplate for Programmable Thermostat |
|
| TSTATXXPBP01 |
|
| ||
|
|
|
|
|
|
|
|
Backplate for Builder’s Thermostat |
|
| TSTATXXBBP01 |
|
| ||
|
|
|
|
|
|
|
|
Backplate for Standard Thermostat |
|
| TSTATXXSBP01 |
|
| ||
|
|
|
|
|
|
|
|
Thermostat Conversion Kit (4 to 5 |
|
| TSTATXXCNV10 |
|
| ||
|
|
|
|
|
|
|
|
Evolution Controls |
|
| See chart. |
|
|
See notes on page 5.
.