SYSTEM DESIGN SUMMARY

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).

3.Maximum outdoor operating air temperature is 125°F (51.7°C).

4.For reliable operation, unit should be level in all horizontal planes.

5.Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 50 ft, indoor coil below = 150 ft.

6.For interconnecting refrigerant tube lengths greater than 50 ft and/or 20 ft vertical differential, consult the Residential Split-System Application Guideline and Service Manual for

Air Conditioners and Heat Pumps using Puron® (R-410A) Refrigerant available from equipment distributor.

7.If any refrigerant tubing is buried, provide a 6 in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. may be buried without further consideration. Do not bury refrigerant lines longer than 3 ft.

8.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

9.Mismatches of indoor coil capacity more than one size larger than outdoor unit capacity may result in inadequate indoor comfort.

10.Do not apply capillary tube indoor coils to these units.

11.Factory-supplied filter drier must be installed.

—41—

Image 41
Contents 550A Unit Dimensions Minimum Mounting DimensionsSize UnitPiston Identification noElectrical SpecificationsSpecifications Required for LOW-AMBIENT LONG-LINE SEA Coast Description AccessoryRating Unit Size StandardCombination Ratings Coils + 315A,JAV066155 VARIABLE-SPEED Furnace EER030-F TDR CC5A/CD5AW042 Coils + 355MAV060120 VARIABLE-SPEED Furnace Coils + 355MAV060080 VARIABLE-SPEED FurnaceCoils + 355MAV060100 VARIABLE-SPEED Furnace FV4BNF005 Coils + 355MAV042080 VARIABLE-SPEED Furnace Coils + 355MAV042040 VARIABLE-SPEED FurnaceCoils + 355MAV042060 VARIABLE-SPEED Furnace CC5A/CD5AC048 14.00 11.95 CD5AA048 40,500 CC5A/CD5AW060 CC5A/CD5AA060 CK5PA060 46,500 TDR† TDR + TXV‡ TOT SuppliedUnit Indoor CAP Enhance Tested combination 550A024-G Outdoor Section With CC5A/CD5AA030 Indoor Section Detailed Cooling CapacitiesCoils + 355MAV042040 Variable Speed Furnace Coils + 315A,JAV066155 Variable Speed FurnaceCoils + 355MAV060080 Variable Speed Furnace Coils + 355MAV042060 Variable Speed FurnaceSection Size 550A030-F Outdoor Section With CC5A/CD5AA036 Indoor SectionCoils + 355MAV042040 Variable Speed Furnace 550A030-F,Outdoor Section With CC5A/CD5AA036 Indoor Section28.3 25.9 550A036-F Outdoor Section With CC5A/CD5AA042 Indoor Section22.4 26.5 20.9 036 See notes on 550A036-G Outdoor Section With CC5A/CD5AA042 Indoor Section Coils + 315A,JAV066155 Variable Speed Furnace Coils + 355MAV060080 Variable Speed Furnace 33.5 30.7 550A042-F Outdoor Section With CD5AA048 Indoor Section042 048 Detailed Cooling Capacities 550A048-F Outdoor Section With CC5A/CD5AA060 Indoor Section Coils + 355MAV060100 Variable Speed Furnace FC4CNB 550A060-H Outdoor Section With CD5PX060 Indoor SectionCondenser only Ratings SST Condenser Entering AIR Temperatures F550A024-G 550A030-F550A060-H 550A042-F550A048-F System Design Summary Page Page General Guide Specifications