39/41B Users Manual
| Table 3. Screen Abbreviations (cont) | |
|
|
|
Screen Usage |
| Name and Description |
|
|
|
DPF |
| Displacement Power Factor cosφ fundamental |
|
| The ratio of the active power (W) to the apparent power |
|
| (VA rms) at the fundamental frequency. Equivalent to |
|
| cosφ at that frequency. Traditional power factor for linear |
|
| loads. |
HZ |
| Waveform Screens: Fundamental frequency in hertz |
| ||
|
| Harmonics Screens: Frequency of selected harmonic in |
|
| hertz |
KF |
| |
| ||
|
| A load current waveform rating calculation that rates the |
|
| waveform’s capability to produce |
|
| loss in transformers and other magnetic components. |
|
| Used to select transformer |
|
| current |
PF |
| Power Factor |
| ||
|
| Ratio of active power to apparent power (including all |
|
| harmonics).True power factor for all loads, linear and |
|
| |
|
|
|
%THD-F Total Harmonic Distortion (as % of Fundamental)
Defines amount of harmonic distortion as a percentage of the waveform at the fundamental frequency.
%THD - F = rms of harmonics (less fundamental) rms of fundamental
%
Defines amount of harmonic distortion as a percentage of the rms value of waveforms at all frequencies (fundamental and harmonics).
%THD - R = rms of harmonics (less fundamental) total rms
22