Bryant 619CNF, 619CNQ III. Clean Indoor Unit Bottom Panel, IV. Clean Indoor Coil, Troubleshooting

Page 20

III. CLEAN INDOOR UNIT BOTTOM PANEL

If the bottom panel of the unit becomes dirty or smudged, wipe the outside of the panel with a soft dry cloth. Use a mild liquid detergent and wipe off carefully with a dry cloth.

IV. CLEAN INDOOR COIL

To clean the coil, remove indoor unit bottom panel and vac- uum the coil fins, using care not to bend or damage fins.

V. CLEAN OUTDOOR COIL (OUTDOOR UNIT)

WARNING: Some metal parts and sharp fins of outdoor unit coil can cause personal injury during cleaning. Clean coil carefully.

To clean the outdoor coil:

1.Remove any dirt or obstruction from discharge opening.

2.Use a garden hose to spray water on the coil. Debris that collects between coil fins inhibits heat transfer

— direct the water spray between coil fins to flush out debris.

VI. CLEAN CONDENSATE DRAINS

Clean all drains and drain pans at the start of each cooling season. Check the flow by pouring water into the drain.

A. Clean Or Replace Drain Pan

1.Place a plastic sheet on the floor to catch any water that may spill from drain pan.

2.Remove the intake grille and distribution assembly (attached).

3.Remove the condensate water in the drain pan by letting water drain into a 3-gallon bucket.

CAUTION: Do not use a screwdriver to pry drain pan out of assembly — it could damage the pan.

4.Remove the 4 screws holding the drain pan.

5.Carefully hold the drain pan to remove it from the assembly.

SERVICE

WARNING: When servicing unit, turn off all elec- tric power to unit to avoid shock hazard or injury from rotating parts.

CAUTION: Do not vent refrigerant to atmosphere when servicing unit. Recover refrigerant during sys- tem repair or unit removal.

I. BEFORE CALLING FOR SERVICE

Save the cost of a service call by doing the following:

1. Be sure main power to system is turned on.

a40-636

Fig. 23 — Cleaning Filters

2.Press Mode button until OFF is displayed. Wait 5 minutes.

3.Press Mode button until either COOL or HEAT is displayed (as desired).

4.Adjust thermostat set point to desired room tempera- ture. If system starts within a few minutes, service may not be necessary. If system does not operate properly, check Table 7 for typical solutions.

A.If System Fails To Operate

Be sure:

unit ON/OFF switch is in ON position

fuse or circuit breaker is not tripped

FRESH AIR INSTALLATION OPTION

The units have an installation option, which allows for field installation of fresh air ventilation. Plan the installation carefully. Before beginning, measure carefully and follow acceptable building practices, NEC, and local codes.

I. VENTILATION-AIR ACCESSORY

Refer to ventilation air accessory installation instructions.

TROUBLESHOOTING

If the under-ceiling fan coil unit fails to start or operate prop- erly, sometimes the problem is minor and can be handled without a service call. Refer to Table 7 for some common problems, causes, and typical solutions. See Fig. 20 and 21 for additional system troubleshooting details. If the problem cannot be corrected, contact a local dealer for further assistance.

—20—

Image 20
Contents Installation ContentsSafety Considerations System Matches Application RangeSystem Type Indoor Section Number Outdoor Section Number CoolingComplete PRE-INSTALLATION Checks Before InstallationPhysical Data, Under Ceiling Cooling Only Units Unpack UnitUnit Size Physical Data, Under Ceiling Heat Pump UnitsII. Select Location Weight lb UnitSize Ft-inIII. Mount Unit Installing Hex-Head Mounting Bolts Fan Coil Unit IV. Connect Refrigerant PipingConnect Condensate Drain Line Piston and Charge Combinations Cooling Only SystemsPiston and Charge Combinations Heat Pump Systems Piston and Charge Combinations Heat and Cool SystemsAccuRater Metering Device at Service Valve Mounting Hanging BracketsVI. Make Electrical Connections Electrical DataComponent Location Typical Ceiling-Suspended System VII. Install Thermostat Line Power ConnectionsASM ASRTran FPTThermostats VIII. Make Connections Between Indoor and Outdoor Units Check AccuRater Metering DeviceCooling Only Systems Heat Pump SystemsCooling System Wiring Diagram Heat Pump Wiring Diagram III. Adjusting Airflow IV. Operating Mode MemoryAutomatic Operation AUTO. Mode START-UPII. AIR Filters FIG Cleaning and MaintenanceLubrication III. Clean Indoor Unit Bottom Panel IV. Clean Indoor CoilClean Outdoor Coil Outdoor Unit VI. Clean Condensate DrainsTroubleshooting Problem Cause Typical SolutionService Training Call for Free CatalogIII. Piping START-UP Checklist Preliminary InformationII. PRE-START-UP START-UP Checklist IV. START-UP