Bryant 583B instruction manual Special Procedures For 208-V Operation, HIGH-VOLTAGE Connections

Page 11

SUPPLY

RETURN

DUCT

DUCT

OPENING

OPENING

C99089

Fig. 11—Supply and Return Duct Opening

The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used. See Fig. 6 and 7 for acceptable location.

See unit wiring label and Fig. 14 for reference when making high voltage connections. Proceed as follows to complete the high- voltage connections to the unit.

1.Run the high-voltage (L1, L2, L3) and ground leads into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the lines side of the contactor.

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

5.Connect field wire L2 to yellow wire on connection 13 of the compressor contactor.

6.Connect field wire L3 to Blue wire from compressor.

B. Special Procedures For 208-V Operation

DUCT COVERS REMOVED

C99012

Fig. 12—Vertical Duct Cover Removed

CAUTION: Failure to follow these precautions could result in damage to the unit being installed:

1.Make all electrical connections in accordance with NEC ANSI/NFPA 70 (latest edition) and local electri- cal codes governing such wiring. In Canada, all elec- trical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2.Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.

3.Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate.

4.Do not damage internal components when drilling through any panel to mount electrical hardware, con- duit, etc.

5.On 3-phase units, ensure phases are balanced within 2%. Consult local power company for correction of improper voltage and/or phase imbalance (refer to Table 5).

A.HIGH-VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field- supplied, water-proof, disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate for maximum fuse/ circuit breaker size and minimum circuit amps (ampacity) for wire sizing. See Table 5 for electrical data.

—11—

WARNING: Make sure that the gas supply then the power supply to the unit is switched OFF before making any wiring changes. Electrical shock or explosion could cause serious injury or death.

With disconnect switch open, move yellow wire from transformer (3/16 in.) terminal marked 230 to terminal marked 200. This retaps transformer to primary voltage of 208 vac.

C. CONTROL VOLTAGE CONNECTIONS

NOTE: Do not use any type of power-stealing thermostat. Unit control problems may result.

Use no. 18 American Wire Gage (AWG) color-coded, insulated (35° C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35° C minimum) wires.

STANDARD CONNECTION — Remove knockout hole located in the flue panel adjacent to the control access panel. See Fig. 6 and 7. Remove the rubber grommet from the installer’s packet (included with unit) and install grommet in the knockout opening. Provide a drip loop before running wire through panel.

Run the low-voltage leads from the thermostat, through the inlet hole, and into unit low-voltage splice box.

Locate five 18-gauge wires leaving control box. These low-voltage connection leads can be identified by the colors red, green, yellow, brown, and white. (See Fig. 14.) Ensure the leads are long enough to be routed into the low-voltage splice box (located below right side of control box). Stripped yellow wire is located in connection box. Route leads through hole in bottom of control box and make low-voltage connections as shown in Fig. 14. Secure all cut wires, so that they do not interfere with operation of unit.

HEAT ANTICIPATOR SETTING — The room thermostat heat anticipator must be properly adjusted to ensure proper heating performance. Set the heat anticipator, using an ammeter between the W and R terminals to determine the exact required setting.

NOTE: For thermostat selection purposes, use 0.18 amp for the approximate required setting.

Failure to make a proper heat anticipator adjustment will result in improper operation, discomfort to the occupants of the conditioned space, and inefficient energy utilization; however, the required setting may be changed slightly to provide a greater degree of comfort for a particular installation.

Image 11
Contents Rules for Safe Installation and Operation Safety ConsiderationsIII. Field Fabricate Ductwork Receiving and Installation I. Check EquipmentGeneral II. Provide Unit SupportRoof Curb Dimensions Top View VI. Connect Condensate Drain Roof Curb DimensionsIV. Provide Clearances RIG and Place UnitCharacteristics Electrical Unit Weight Unit Height Center of GravityNEC. Required Clearances Required Clearance for Operation and ServicingRequired Clearance to Combustible Matl Unit 583B Maximum Weight Size VII. Install Flue HoodIX. Install Duct Connections VIII. Install GAS PipingPhysical Data Unit 583B Install Electrical ConnectionsNominal Iron Pipe Size Internal Diameter Length of PIPE, FT† Maximum GAS Flow CapacityControl Voltage Connections Special Procedures For 208-V OperationHIGH-VOLTAGE Connections RLA LRA FLA MCA Mocp Electrical Data 583BCheck for Refrigerant Leaks Start Up Heating Section and Make AdjustmentsPRE-START-UP START-UPBtuh Orifices Heating InputsHeating Number GAS Supply Pressure Manifold Pressure InputLED Indications Heating Temperature Rise F Input BtuhError Code LED Indication Speed Start-Up Cooling Section and Make AdjustmentsIndoor Airflow and Airflow Adjustments 208/230-3-60 Wiring Diagram 460-3-60 Wiring Diagram Evaporator Blower and Motor MaintenanceAir Filter Cooling Charging Chart, 583B030 Units WET Coil AIR DELIVERY* Horizontal and Downflow Discharge Blower Housing and Flue Collector Box Flue Gas PassagewaysMain Burners Limit SwitchCombustion-Air Blower Burner IgnitionEvaporator Airflow Electrical Controls and WiringPressure Switches Refrigerant CircuitLiquid Line Filter Drier Refrigerant SystemCompressor Oil Servicing Systems on Roofs with Synthetic MaterialsAIR Conditioner with Puron R-410A-QUICK Reference Guide Symptom Cause Remedy Troubleshooting CoolingWater in gas line Drain. Install drip leg Troubleshooting HeatingLED OFF LED TROUBLESHOOTING-ERROR CodePreliminary Information START-UP Checklist Remove and Store in JOB File
Related manuals
Manual 28 pages 39.19 Kb Manual 30 pages 37.07 Kb

583B specifications

The Bryant 583B is an advanced, high-efficiency gas furnace designed to provide exceptional heating performance and reliability. With a focus on comfort and energy efficiency, this model stands out in the residential heating market.

One of the main features of the Bryant 583B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 95%. This means that the furnace converts up to 95% of the fuel it consumes into usable heat. As a result, homeowners can expect lower energy bills and reduced environmental impact due to decreased carbon emissions.

The Bryant 583B is equipped with a modulating gas valve that allows for precise control of the heating output. This technology enables the furnace to adjust its running capacity based on the heating demands of your home. Instead of operating at a single, high setting, the furnace runs at the required level to maintain the desired temperature, delivering consistent comfort while maximizing efficiency.

Another noteworthy characteristic of the 583B is its two-stage operation. This feature allows the furnace to operate at a lower stage for mild weather, which reduces energy consumption and minimizes noise levels. During colder conditions, it can switch to a high stage for increased heating capacity. This dual approach not only enhances comfort but also prolongs the lifespan of the unit by reducing wear and tear.

In terms of construction, the Bryant 583B is built with durable materials and a robust cabinet, which ensures longevity and resilience over time. It also comes with a quiet operation feature, minimizing disturbances while maintaining a comfortable indoor environment.

The unit is compatible with Bryant's advanced communication technology, enabling seamless integration with smart thermostats. This addition allows homeowners to monitor and control their furnace remotely, optimizing energy usage even further.

In summary, the Bryant 583B furnishes an outstanding combination of efficiency, reliability, and user-friendly technologies. Its modulating gas valve, two-stage operation, and high AFUE rating collectively ensure that customers enjoy a comfortable home environment while significantly reducing energy costs. As energy-conscious choices become increasingly crucial, the Bryant 583B stands ready to meet the challenges of modern heating needs.