Bryant 583B instruction manual Combustion-Air Blower, Limit Switch, Burner Ignition, Main Burners

Page 22

BLOWER

HOUSING

2 SETSCREWS

(HIDDEN)

C99085

Fig. 26—Removal of Motor and Blower Wheel

C99090

Fig. 27—Unit Access Panel

1.Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section below.

2.Remove the 3 screws holding the blower housing to the flue collector box cover (see Fig. 25).

3.Remove the 12 screws holding the flue collector box cover (Fig. 25) to the heat exchanger assembly. Inspect the heat exchangers.

4.Clean all surfaces as required, using the wire brush.

D. Combustion-Air Blower

Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi- monthly to determine proper cleaning frequency.

To inspect blower wheel, remove draft hood assembly. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel as follows:

1.Remove unit access panel (See Fig. 24).

2.Remove the 7 screws that attach induced-draft motor mounting plate to blower housing (See Fig. 25).

3.Slide the motor and blower wheel assembly out of the blower housing (See Fig. 26). Clean the blower wheel. If additional cleaning is required, continue with Steps 4 and 5.

4.To remove blower, remove 2 setscrews (See Fig. 26).

—22—

5.To remove motor and cooling fan assembly, remove 4 screws that hold blower housing to mounting plate.

6.To reinstall, reverse the procedure outlined above.

E. Limit Switch

Remove unit access panel. Limit switch is located on the blower partition.

F. Burner Ignition

Unit is equipped with a direct spark ignition 100% lockout system. Ignition module is located in the control box. Module contains a self-diagnostic LED. During servicing, refer to label diagram for LED interpretations.

If lockout occurs, unit may be reset by either momentarily interrupting power supply to unit, or turning selector switch to OFF position at the thermostat.

G. Main Burners

At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames and adjust if necessary.

CAUTION: When servicing gas train, do not hit or plug orifice spuds.

REMOVAL OF GAS TRAIN

1.Shut off manual gas valve.

2.Shut off power to unit.

3.Remove unit access panel (See Fig. 27).

4.Disconnect gas piping at unit gas valve.

5.Remove wires connected to gas valve. Mark each wire.

6.Remove ignitor and sensor wires at the ignitor module.

7.Remove the mounting screw that attaches the burner rack to the basepan (See Fig. 25).

8.Slide the burner rack out of the unit (See Figs. 25 and 28).

9.To reinstall, reverse the procedure outlined above.

H. Condenser Coil, Evaporator Coil, and Condensate Drain Pan

Inspect the condenser coil, evaporator coil, and condensate drain pan at least once each year.

The coils are easily cleaned when dry; therefore, inspect and clean the coils either before or after each cooling season. Remove all obstructions, including weeds and shrubs, that interfere with the airflow through the condenser coil.

Straighten bent fins with a fin comb. If coated with dirt or lint, clean the coils with a vacuum cleaner, using the soft brush attachment. Be careful not to bend the fins. If coated with oil or grease, clean the coils with a mild detergent-and-water solution. Rinse coils with clear water, using a garden hose. Be careful not to splash water on motors, insulation, wiring, or air filter(s). For best results, spray condenser coil fins from inside to outside the unit. On units with an outer and inner condenser coil, be sure to clean between the coils. Be sure to flush all dirt and debris from the unit base.

Inspect the drain pan and condensate drain line when inspecting the coils. Clean the drain pan and condensate drain by removing all foreign matter from the pan. Flush the pan and drain tube with clear water. Do not splash water on the insulation, motor, wiring, or air filter(s). If the drain tube is restricted, clear it with a ‘‘plumbers snake’’ or similar probe device. Ensure that the auxiliary drain port above the drain tube is also clear.

Image 22
Contents Safety Considerations Rules for Safe Installation and OperationII. Provide Unit Support Receiving and Installation I. Check EquipmentGeneral III. Field Fabricate DuctworkRoof Curb Dimensions Top View RIG and Place Unit Roof Curb DimensionsIV. Provide Clearances VI. Connect Condensate DrainElectrical Unit Weight Unit Height Center of Gravity CharacteristicsRequired Clearance to Combustible Matl Required Clearance for Operation and ServicingNEC. Required Clearances VII. Install Flue Hood Unit 583B Maximum Weight SizeVIII. Install GAS Piping IX. Install Duct ConnectionsInstall Electrical Connections Physical Data Unit 583BMaximum GAS Flow Capacity Nominal Iron Pipe Size Internal Diameter Length of PIPE, FT†HIGH-VOLTAGE Connections Special Procedures For 208-V OperationControl Voltage Connections Electrical Data 583B RLA LRA FLA MCA MocpSTART-UP Start Up Heating Section and Make AdjustmentsPRE-START-UP Check for Refrigerant LeaksInput Heating InputsHeating Number GAS Supply Pressure Manifold Pressure Btuh OrificesError Code LED Indication Heating Temperature Rise F Input BtuhLED Indications Indoor Airflow and Airflow Adjustments Start-Up Cooling Section and Make AdjustmentsSpeed 208/230-3-60 Wiring Diagram 460-3-60 Wiring Diagram Air Filter MaintenanceEvaporator Blower and Motor Cooling Charging Chart, 583B030 Units Blower Housing and Flue Collector Box Flue Gas Passageways WET Coil AIR DELIVERY* Horizontal and Downflow DischargeBurner Ignition Limit SwitchCombustion-Air Blower Main BurnersRefrigerant Circuit Electrical Controls and WiringPressure Switches Evaporator AirflowServicing Systems on Roofs with Synthetic Materials Refrigerant SystemCompressor Oil Liquid Line Filter DrierAIR Conditioner with Puron R-410A-QUICK Reference Guide Troubleshooting Cooling Symptom Cause RemedyTroubleshooting Heating Water in gas line Drain. Install drip legLED TROUBLESHOOTING-ERROR Code LED OFFSTART-UP Checklist Remove and Store in JOB File Preliminary Information
Related manuals
Manual 28 pages 39.19 Kb Manual 30 pages 37.07 Kb

583B specifications

The Bryant 583B is an advanced, high-efficiency gas furnace designed to provide exceptional heating performance and reliability. With a focus on comfort and energy efficiency, this model stands out in the residential heating market.

One of the main features of the Bryant 583B is its impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 95%. This means that the furnace converts up to 95% of the fuel it consumes into usable heat. As a result, homeowners can expect lower energy bills and reduced environmental impact due to decreased carbon emissions.

The Bryant 583B is equipped with a modulating gas valve that allows for precise control of the heating output. This technology enables the furnace to adjust its running capacity based on the heating demands of your home. Instead of operating at a single, high setting, the furnace runs at the required level to maintain the desired temperature, delivering consistent comfort while maximizing efficiency.

Another noteworthy characteristic of the 583B is its two-stage operation. This feature allows the furnace to operate at a lower stage for mild weather, which reduces energy consumption and minimizes noise levels. During colder conditions, it can switch to a high stage for increased heating capacity. This dual approach not only enhances comfort but also prolongs the lifespan of the unit by reducing wear and tear.

In terms of construction, the Bryant 583B is built with durable materials and a robust cabinet, which ensures longevity and resilience over time. It also comes with a quiet operation feature, minimizing disturbances while maintaining a comfortable indoor environment.

The unit is compatible with Bryant's advanced communication technology, enabling seamless integration with smart thermostats. This addition allows homeowners to monitor and control their furnace remotely, optimizing energy usage even further.

In summary, the Bryant 583B furnishes an outstanding combination of efficiency, reliability, and user-friendly technologies. Its modulating gas valve, two-stage operation, and high AFUE rating collectively ensure that customers enjoy a comfortable home environment while significantly reducing energy costs. As energy-conscious choices become increasingly crucial, the Bryant 583B stands ready to meet the challenges of modern heating needs.