Bryant 577D----A Install Electrical Connections, Fire or Explosion Hazard

Page 12

577D-- -- A

IN

TEE

OUT

NIPPLE

CAP

C99020

Fig. 10 - Sediment Trap

!WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in fire, explosion, personal injury, death and/or property damage.

SConnect gas pipe to unit using a backup wrench to avoid

damaging gas controls.

SNever purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.

SUse proper length of pipe to avoid stress on gas control manifold.

SIf a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be installed at furnace gas valve and extend a minimum of 2 in. (51 mm) outside furnace casing.

SIf codes allow a flexible connector, always use a new connector. Do not use a connector which has previously serviced another gas appliance.

8.Check for gas leaks at the field-installed and factory-installed gas lines after all piping connections have been completed. Use a commercially available soap solution made specifically for the detection of leaks (or method specified by local codes and/or regulations).

Install Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, NFPA 70 National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.

HIGH-VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.

The field-supplied disconnect may be mounted on the unit over the high-voltage inlet hole (See Fig. 5 and 6).

NOTE: Field supplied disconnect switch box should be positioned so that it does not cover up any of the unit gas combustion supply air louvers.

Operation of unit on improper line voltage constitutes abuse and may cause unit damage that could affect warranty.

!CAUTION

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the unit being installed.

1.Make all electrical connections in accordance with NEC NFPA 70 (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2.Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.

3.Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate.

4.Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are in same conduit as high-voltage wires.

5.Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.

ROUTING POWER LEADS INTO UNIT

Use only copper wire between disconnect and unit. The high voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight. Run the high-voltage leads through the power entry knockout on the power entry side panel. See Fig. 5 and 6 for location and size. For single-phase units, connect leads to the black and yellow wires.

CONNECTING GROUND LEAD TO GROUND SCREW

Connect the ground lead to the chassis using the ground screw on the control plate near the inducer switch (See Fig. 12).

12

Image 12
Contents Installation Instructions Table of ContentsSafety Considerations Receiving and InstallationIntroduction Check EquipmentProvide Clearances Rig and Place UnitUNIT/STRUCTURAL Damage Hazard Unit Falling HazardSize CPRFCURB010A00CPRFCURB011A00 CPRFCURB012A00577D--A24-30 Unit Dimensions 577D--A36-60 Unit Dimensions Physical Data Unit 577D--A Physical Data Con’t Unit 577D--A Indoor FANSelect and Install Ductwork Cabinet Model Rigging WeightPersonal Injury Hazard Provide for Condensate Disposal Supply and Return Duct OpeningInstall Flue Hood Install Gas PipingCarbon Monoxide Poisoning Hazard Install Electrical Connections Fire or Explosion HazardUnit Component Damage Hazard Outdoor Air Temperature Sensor OAT Electronic Air CleanerMaximum Gas Flow Capacity Humidifier ConnectionsTypical Installation Control Plate Unit Start-Up and Troubleshooting PRE-START-UPSTART-UP FIRE, EXPLOSION, Electrical Shock and Environmental HazardIndoor Fan Motor Troubleshooting Furnace Control Troubleshooting577D a A10217L A10219C A10219L HP/AC Control Troubleshooting Sequence of Operation Unit Operation HazardAir Delivery and Temperature Rise at Rated Heating Input Heat Pump/Air Conditioner Board Status CodesDehumidification Mode Evolution Controlled LOW Ambient CoolingCheck GAS Input Natural GAS Unit Damage HazardFire and Unit Damage Hazard U.S.AAltitude Derate Multiplier for U.S.A CanadaCheck GAS Input Propane GAS Check Burner FlameStart-Up Adjustments Check for Refrigerant LeaksHeating Inputs ECM Wet Coil Pressure Drop IN. W.CFilter Pressure Drop Table IN. W.C Cooling Charging Table-Subcooling Maintenance Inducer Pressure Switch Electrical Controls and WiringOutdoor Coil, Indoor Coil, and Condensate Drain Pan Outdoor FanPressure Switches Refrigerant Circuit Refrigerant CircuitIndoor Airflow Copeland Scroll Compressor Puron RefrigerantTroubleshooting Final Checks Care and Maintenance Observe all warnings, cautions, and bold text Troubleshooting Chart Cooling Symptom Cause RemedyTroubleshooting Chart Gas Furnace Operation Burners will not igniteSTART-UP Checklist TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor Amps

577D----A specifications

The Bryant 577D----A is a highly regarded model in the HVAC industry, representing a blend of efficiency, performance, and advanced technology. This heating and cooling unit is designed to cater to a variety of residential and light commercial applications, making it a versatile choice for consumers looking to enhance their indoor climate control systems.

One of the standout features of the Bryant 577D----A is its impressive energy efficiency rating. With a Seasonal Energy Efficiency Ratio (SEER) typically exceeding 14, this model is engineered to reduce energy consumption, helping homeowners lower their utility bills while minimizing environmental impact. The unit also employs a two-stage cooling system, which not only improves comfort by maintaining more consistent temperatures but also provides enhanced dehumidification during hotter months.

The technology used in the Bryant 577D----A is noteworthy. The unit incorporates a variable-speed compressor that adapts to the specific cooling or heating needs of the space, ensuring optimal performance at all times. This advanced feature not only contributes to energy savings but also allows for quieter operation compared to single-stage systems. The inclusion of a smart thermostat integration further enhances convenience, enabling users to manage their HVAC system remotely and optimize settings according to their schedules.

Additional characteristics of the Bryant 577D----A include a durable construction designed to withstand various environmental conditions. The cabinet is made from quality materials that protect against corrosion and other factors that could affect the unit's longevity. Furthermore, the unit operates quietly, thanks to sound-dampening technologies, which is a significant advantage for residential areas where noise can be a concern.

Maintenance is also simplified with the Bryant 577D----A, as it is equipped with self-diagnostics for easy troubleshooting. This feature alerts users to potential issues before they escalate, promoting efficient operation and prolonging the lifespan of the system.

In conclusion, the Bryant 577D----A stands out as a superior choice for those seeking reliability and efficiency in their HVAC solutions. With its energy-efficient operation, advanced technologies, and robust construction, it serves as a valuable investment for homeowners committed to comfort and sustainability.