Bryant 577D----A Provide Clearances, Rig and Place Unit, UNIT/STRUCTURAL Damage Hazard

Page 3

A

C

MAXIMUM ALLOWABLE

BDIFFERENCE in. (mm)

 

A-B

B-C

 

A-C

1/4

(6.35)

1/4

(6.35)

1/4

(6.35)

 

 

 

 

 

 

A07925

Fig. 2 - Unit Leveling Tolerances

Installation on older “G” series roof curbs.

Two accessory kits are available to aid in installing a new “G” series unit on an old “G” roof curb.

1.Accessory kit number CPADCURB001A00, (small chassis) and accessory kit number CPADCURB002A00, (large chassis) includes roof curb adapter and gaskets for the perimeter seal and duct openings. No additional modifications to the curb are required when using this kit.

2.An alternative to the adapter curb is to modify the existing curb by removing the outer horizontal flange and use accessory kit number CPGSKTKIT001A00 which includes spacer blocks (for easy alignment to existing curb) and gaskets for the perimeter seal and duct openings. This kit is used when existing curb is modified by removing outer horizontal flange.

!CAUTION

UNIT/STRUCTURAL DAMAGE HAZARD

Failure to follow this caution may result in property damage.

Ensure there is sufficient clearance for saw blade when cutting the outer horizontal flange of the roof curb so there is no damage to the roof or flashing.

OPTIONAL

OPTIONAL

RETURN

SUPPLY

AIR

AIR

OPENING

OPENING

 

(50.8mm)

 

EVAP. COIL

COND. COIL

A07926

Fig. 3 - Slab Mounting Detail

SLAB MOUNT

Place the unit on a solid, level concrete pad that is a minimum of 4 in. (102 mm) thick with 2 in. (51 mm) above grade. The slab should extend approximately 2 in. (51 mm) beyond the casing on all 4 sides of the unit (See Fig. 3). Do not secure the unit to the slab except when required by local codes.

Provide Clearances

The required minimum service clearances are shown in Fig. 5 and

6.Adequate ventilation and outdoor air must be provided. The outdoor fan draws air through the outdoor coil and discharges it through the top fan grille. Be sure that the fan discharge does not recirculate to the outdoor coil. Do not locate the unit in either a corner or under an overhead obstruction. The minimum clearance under a partial overhang (such as a normal house overhang) is 48 in. (1219 mm) above the unit top. The maximum horizontal extension of a partial overhang must not exceed 48 in. (1219 mm). IMPORTANT: Do not restrict outdoor airflow. An air restriction at either the outdoor-air inlet or the fan discharge may be detrimental to compressor life.

Do not place the unit where water, ice, or snow from an overhang or roof will damage or flood the unit. Do not install the unit on carpeting or other combustible materials. Slab-mounted units should be at least 4 in. (102 mm) above the highest expected water and runoff levels. Do not use unit if it has been under water.

Rig and Place Unit

Rigging and handling of this equipment can be hazardous for many reasons due to the installation location (roofs, elevated structures, etc.).

Only trained, qualified crane operators and ground support staff should handle and install this equipment.

When working with this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that might apply.

Training for operators of the lifting equipment should include, but not be limited to, the following:

1.Application of the lifter to the load, and adjustment of the lifts to adapt to various sizes or kinds of loads.

2.Instruction in any special operation or precaution.

3.Condition of the load as it relates to operation of the lifting kit, such as balance, temperature, etc.

Follow all applicable safety codes. Wear safety shoes and work gloves.

Inspection

Prior to initial use, and at monthly intervals, all rigging shackles, clevis pins, and straps should be visually inspected for any damage, evidence of wear, structural deformation, or cracks. Particular attention should be paid to excessive wear at hoist hooking points and load support areas. Materials showing any kind of wear in these areas must not be used and should be discarded.

!WARNING

UNIT FALLING HAZARD

Failure to follow this warning could result in personal injury or death.

Never stand beneath rigged units or lift over people.

!WARNING

PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in personal injury/death or property damage.

When straps are taut, the clevis should be a minimum of 36 in. (914 mm) above the unit top cover.

577D-- -- A

3

Image 3
Contents Table of Contents Installation InstructionsCheck Equipment Safety ConsiderationsReceiving and Installation IntroductionUnit Falling Hazard Provide ClearancesRig and Place Unit UNIT/STRUCTURAL Damage HazardCPRFCURB012A00 SizeCPRFCURB010A00 CPRFCURB011A00577D--A24-30 Unit Dimensions 577D--A36-60 Unit Dimensions Physical Data Unit 577D--A Indoor FAN Physical Data Con’t Unit 577D--ASelect and Install Ductwork Cabinet Model Rigging WeightPersonal Injury Hazard Supply and Return Duct Opening Provide for Condensate DisposalInstall Flue Hood Install Gas PipingCarbon Monoxide Poisoning Hazard Install Electrical Connections Fire or Explosion HazardUnit Component Damage Hazard Humidifier Connections Outdoor Air Temperature Sensor OATElectronic Air Cleaner Maximum Gas Flow CapacityTypical Installation Control Plate FIRE, EXPLOSION, Electrical Shock and Environmental Hazard Unit Start-Up and TroubleshootingPRE-START-UP START-UPFurnace Control Troubleshooting Indoor Fan Motor Troubleshooting577D a A10217L A10219C A10219L HP/AC Control Troubleshooting Unit Operation Hazard Sequence of OperationHeat Pump/Air Conditioner Board Status Codes Air Delivery and Temperature Rise at Rated Heating InputUnit Damage Hazard Dehumidification ModeEvolution Controlled LOW Ambient Cooling Check GAS Input Natural GASCanada Fire and Unit Damage HazardU.S.A Altitude Derate Multiplier for U.S.ACheck Burner Flame Check GAS Input Propane GASCheck for Refrigerant Leaks Start-Up AdjustmentsHeating Inputs ECM Wet Coil Pressure Drop IN. W.CFilter Pressure Drop Table IN. W.C Cooling Charging Table-Subcooling Maintenance Outdoor Fan Inducer Pressure SwitchElectrical Controls and Wiring Outdoor Coil, Indoor Coil, and Condensate Drain PanCopeland Scroll Compressor Puron Refrigerant Pressure Switches Refrigerant CircuitRefrigerant Circuit Indoor AirflowTroubleshooting Final Checks Care and Maintenance Observe all warnings, cautions, and bold text Symptom Cause Remedy Troubleshooting Chart CoolingBurners will not ignite Troubleshooting Chart Gas Furnace OperationIII. START-UP Electrical Supply Voltage Compressor Amps START-UP ChecklistTemperatures Preliminary Information Model no

577D----A specifications

The Bryant 577D----A is a highly regarded model in the HVAC industry, representing a blend of efficiency, performance, and advanced technology. This heating and cooling unit is designed to cater to a variety of residential and light commercial applications, making it a versatile choice for consumers looking to enhance their indoor climate control systems.

One of the standout features of the Bryant 577D----A is its impressive energy efficiency rating. With a Seasonal Energy Efficiency Ratio (SEER) typically exceeding 14, this model is engineered to reduce energy consumption, helping homeowners lower their utility bills while minimizing environmental impact. The unit also employs a two-stage cooling system, which not only improves comfort by maintaining more consistent temperatures but also provides enhanced dehumidification during hotter months.

The technology used in the Bryant 577D----A is noteworthy. The unit incorporates a variable-speed compressor that adapts to the specific cooling or heating needs of the space, ensuring optimal performance at all times. This advanced feature not only contributes to energy savings but also allows for quieter operation compared to single-stage systems. The inclusion of a smart thermostat integration further enhances convenience, enabling users to manage their HVAC system remotely and optimize settings according to their schedules.

Additional characteristics of the Bryant 577D----A include a durable construction designed to withstand various environmental conditions. The cabinet is made from quality materials that protect against corrosion and other factors that could affect the unit's longevity. Furthermore, the unit operates quietly, thanks to sound-dampening technologies, which is a significant advantage for residential areas where noise can be a concern.

Maintenance is also simplified with the Bryant 577D----A, as it is equipped with self-diagnostics for easy troubleshooting. This feature alerts users to potential issues before they escalate, promoting efficient operation and prolonging the lifespan of the system.

In conclusion, the Bryant 577D----A stands out as a superior choice for those seeking reliability and efficiency in their HVAC solutions. With its energy-efficient operation, advanced technologies, and robust construction, it serves as a valuable investment for homeowners committed to comfort and sustainability.