Bryant 577D----A installation instructions Troubleshooting Chart Cooling, Symptom Cause Remedy

Page 38

577D-- -- A

Table 9 – Troubleshooting Chart - Cooling

SYMPTOM

CAUSE

REMEDY

 

 

 

 

Power failure

Call power company

 

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

 

Defective contactor, transformer, control relay, or high--

Replace component

 

pressure, loss--of--charge or low--pressure switch

 

 

 

 

 

 

Insufficient line voltage

Determine cause and correct

Compressor and outdoor fan

 

 

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

will not start

 

 

UI setting too low/too high

Reset UI setting

 

 

 

 

 

 

DO NOT bypass this compressor time

 

Units have a 5--minute time delay

delay–wait for 5 minutes until time--delay

 

 

relay is de--energized

 

 

 

 

Faulty wiring or circuit

Check wiring and repair or replace

 

Loose connections in compressor

 

 

 

 

 

Compressor will not start but condenser fan

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

runs

 

 

Defective run capacitor, overload, or PTC (positive

Determine cause and replace

 

 

temperature coefficient) thermistor

 

 

 

 

 

 

Low input voltage (20 percent low)

Determine cause and correct

 

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

 

charge to capacities shown on rating plate

 

 

 

 

 

 

Defective compressor

Replace and determine cause

Compressor cycles (other than normally sat-

Insufficient line voltage

Determine cause and correct

isfying) cooling/heating calls

Blocked outdoor coil

Determine cause and correct

 

Defective run/start capacitor, overload or start relay

Determine cause and replace

 

Faulty outdoor fan motor or capacitor

Replace

 

Restriction in refrigerant system

Locate restriction and remove

 

Dirty air filter

Replace filter

 

Unit undersized for load

Decrease load or increase unit size

 

UI temperature set too low

Reset UI setting

Compressor operates continuously

Low refrigerant charge

Locate leak, repair, and recharge

 

Air in system

Recover refrigerant, evacuate system, and re-

 

charge

 

 

 

 

 

 

Outdoor coil dirty or restricted

Clean coil or remove restriction

 

Dirty air filter

Replace filter

 

Dirty indoor or outdoor coil

Clean coil

Excessive head pressure

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

 

 

charge

 

 

 

 

 

 

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

 

 

High heat load

Check for source and eliminate

Excessive suction pressure

Reversing valve hung up or leaking internally

Replace valve

 

Refrigerant overcharged

Recover excess refrigerant

 

Dirty air filter

Replace filter

 

Low refrigerant charge

Check for leaks, repair and recharge

 

Metering device or low side restricted

Remove source of restriction

Suction pressure too low

Insufficient coil airflow

Check filter–replace if necessary

 

Temperature too low in conditioned area

Reset UI setting

 

Outdoor ambient below 55°F (13°C)

Verify low--ambient cooling enabled in UI

 

Filter drier restricted

Replace

 

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft

IFM does not run

Insufficient voltage at motor

Determine cause and correct

 

Power connectors not properly sealed

Connectors should snap easily; do not force

 

Water dripping into motor

Verify proper drip loops in connector wires

IFM operation is intermittent

Connectors not firmly sealed

Gently pull wires individually to be sure they are

 

crimped into the housing

 

 

 

 

 

38

Image 38
Contents Installation Instructions Table of ContentsIntroduction Safety ConsiderationsReceiving and Installation Check EquipmentUNIT/STRUCTURAL Damage Hazard Provide ClearancesRig and Place Unit Unit Falling HazardCPRFCURB011A00 SizeCPRFCURB010A00 CPRFCURB012A00577D--A24-30 Unit Dimensions 577D--A36-60 Unit Dimensions Physical Data Unit 577D--A Physical Data Con’t Unit 577D--A Indoor FANPersonal Injury Hazard Select and Install DuctworkCabinet Model Rigging Weight Provide for Condensate Disposal Supply and Return Duct OpeningCarbon Monoxide Poisoning Hazard Install Flue HoodInstall Gas Piping Unit Component Damage Hazard Install Electrical ConnectionsFire or Explosion Hazard Maximum Gas Flow Capacity Outdoor Air Temperature Sensor OATElectronic Air Cleaner Humidifier ConnectionsTypical Installation Control Plate START-UP Unit Start-Up and TroubleshootingPRE-START-UP FIRE, EXPLOSION, Electrical Shock and Environmental HazardIndoor Fan Motor Troubleshooting Furnace Control Troubleshooting577D a A10217L A10219C A10219L HP/AC Control Troubleshooting Sequence of Operation Unit Operation HazardAir Delivery and Temperature Rise at Rated Heating Input Heat Pump/Air Conditioner Board Status CodesCheck GAS Input Natural GAS Dehumidification ModeEvolution Controlled LOW Ambient Cooling Unit Damage HazardAltitude Derate Multiplier for U.S.A Fire and Unit Damage HazardU.S.A CanadaCheck GAS Input Propane GAS Check Burner FlameStart-Up Adjustments Check for Refrigerant LeaksFilter Pressure Drop Table IN. W.C Heating InputsECM Wet Coil Pressure Drop IN. W.C Cooling Charging Table-Subcooling Maintenance Outdoor Coil, Indoor Coil, and Condensate Drain Pan Inducer Pressure SwitchElectrical Controls and Wiring Outdoor FanIndoor Airflow Pressure Switches Refrigerant CircuitRefrigerant Circuit Copeland Scroll Compressor Puron RefrigerantTroubleshooting Final Checks Care and Maintenance Observe all warnings, cautions, and bold text Troubleshooting Chart Cooling Symptom Cause RemedyTroubleshooting Chart Gas Furnace Operation Burners will not ignitePreliminary Information Model no START-UP ChecklistTemperatures III. START-UP Electrical Supply Voltage Compressor Amps

577D----A specifications

The Bryant 577D----A is a highly regarded model in the HVAC industry, representing a blend of efficiency, performance, and advanced technology. This heating and cooling unit is designed to cater to a variety of residential and light commercial applications, making it a versatile choice for consumers looking to enhance their indoor climate control systems.

One of the standout features of the Bryant 577D----A is its impressive energy efficiency rating. With a Seasonal Energy Efficiency Ratio (SEER) typically exceeding 14, this model is engineered to reduce energy consumption, helping homeowners lower their utility bills while minimizing environmental impact. The unit also employs a two-stage cooling system, which not only improves comfort by maintaining more consistent temperatures but also provides enhanced dehumidification during hotter months.

The technology used in the Bryant 577D----A is noteworthy. The unit incorporates a variable-speed compressor that adapts to the specific cooling or heating needs of the space, ensuring optimal performance at all times. This advanced feature not only contributes to energy savings but also allows for quieter operation compared to single-stage systems. The inclusion of a smart thermostat integration further enhances convenience, enabling users to manage their HVAC system remotely and optimize settings according to their schedules.

Additional characteristics of the Bryant 577D----A include a durable construction designed to withstand various environmental conditions. The cabinet is made from quality materials that protect against corrosion and other factors that could affect the unit's longevity. Furthermore, the unit operates quietly, thanks to sound-dampening technologies, which is a significant advantage for residential areas where noise can be a concern.

Maintenance is also simplified with the Bryant 577D----A, as it is equipped with self-diagnostics for easy troubleshooting. This feature alerts users to potential issues before they escalate, promoting efficient operation and prolonging the lifespan of the system.

In conclusion, the Bryant 577D----A stands out as a superior choice for those seeking reliability and efficiency in their HVAC solutions. With its energy-efficient operation, advanced technologies, and robust construction, it serves as a valuable investment for homeowners committed to comfort and sustainability.