Bryant 577D----A installation instructions Sequence of Operation, Unit Operation Hazard

Page 23

open or shorted at any time after initial validation, Status Code 53 will be displayed at amber STATUS LED.

Check for faults in wiring connecting sensor to OAT terminals. Using an Ohm meter, check resistance of thermistor for a short or open condition.

If thermistor is shorted or open, replace it to return the system to normal operation. If fault is in the wiring connections, correcting the fault will clear the code and return the system to normal operation.

NOTE: If fault condition is an open thermistor or a wiring problem that appears to be an open thermistor and the power to the unit is cycled off, the fault code will be cleared on the next power-up but the fault will remain and system operation will not be as expected.

This is because on power-up, the unit control cannot discern the difference between an open sensor or if a sensor is not installed.

Sequence of Operation

The 577D--A packaged unit is designed for installation with a communicating UI. This unit will not respond to commands provided by a common thermostat except under certain emergency situations described in Step 1—Start-Up and Troubleshooting.

The UI uses temperature, humidity and other data supplied from indoor and outdoor system components to control heating or cooling system for optimum comfort. The unit will be commanded by UI to supply airflow. The unit will operate the indoor blower at requested airflow for most modes.

INDOOR AIRFLOW ADJUSTMENTS

The nominal requested airflow for air conditioner operations will be 350 cfm per ton of nominal cooling capacity as defined by unit size. Actual airflow request will be adjusted from nominal using indoor and outdoor temperature and indoor humidity data to optimize the system operation for occupant comfort and system efficiency. Refer to UI literature for further system control details.

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit damage.

For cooling operation, the recommended airflow is 350 to 450 cfm for each 12,000 Btuh of rated cooling capacity. For heating operation, the airflow must produce a temperature rise that falls within the range stamped on the unit rating plate.

For gas heat operations, Table 3 shows the temperature rise in each gas heating mode. Refer to these tables to determine the desired heating airflow for the system being installed.

NOTE: Be sure that all supply-and return-air grilles are open, free from obstructions, and adjusted properly. Airflow can be changed using the UI. See UI installation instructions for more detail.

NOTE: Once the compressor has started and then has stopped, it should not be started again until 4 minutes have elapsed. The cooling cycle remains “on” until the room temperature drops to point that is slightly below the cooling control setting of the UI.

AIR CONDITIONER SEQUENCE OF OPERATION COOLING OPERATION

With a call for first stage cooling, the outdoor fan, and low stage compressor are energized. If low-stage cannot satisfy cooling demand, high-stage cooling is energized by the UI. After second stage is satisfied, the unit returns to low-stage operation until first stage is satisfied or until second stage is required again. When both first stage and second stage cooling are satisfied, the compressor will shut off.

NOTE: When two-stage unit is operating at low-stage, system vapor (suction) pressure will be higher than a standard single-stage system or high-stage operation.

NOTE: Outdoor fan motor will continue to operate for one minute after compressor shuts off, when outdoor ambient is greater than or equal to 100°F (38°C).

UTILITY INTERFACE WITH Evolution CONTROL

The utility curtailment relay should be connected to factory supplied pigtails (PINK, connected to R, VIOLET connected to Y2 on the control board) located in the low voltage splice box (See Fig. 16, 18 and 18). This input allows a power utility device to interrupt compressor operation during peak load periods. When the utility sends a signal to shut the system down, the UI will display “Curtailment Active”.

COMPRESSOR OPERATION

When the compressor is operating in low stage, the modulating ring is deactivated, allowing two internal bypass ports to close off 33% of the scroll compression area so the system operates at part load capacity. The 24-volt solenoid coil is de-energized in low-stage operation.

When the compressor is operating at high stage, the modulating ring is activated, sealing the bypass ports, which allows the compressor to operate at full load capacity. The 24-volt solenoid coil is energized in high stage operation.

CRANKCASE HEATER OPERATION (IF APPLICABLE)

The crankcase heater is energized during off cycle below 65_F (18_C) outdoor air temperature.

OUTDOOR FAN MOTOR OPERATION

The outdoor unit control energizes the outdoor fan any time the compressor is operating. The outdoor fan remains energized if a pressure switch or compressor overload should open. Outdoor fan motor will continue to operate for one minute after the compressor shuts off when the outdoor ambient is greater than or equal to 100_F (38°C).

TIME DELAYS-AIR CONDITIONER OPERATIONS The unit time delays include:

SFive minute time delay to start cooling operation when there is a call from the thermostat or user interface. To bypass this feature, momentarily short and release Forced Defrost pins.

SFive minute compressor recycle delay on return from a brown-out condition.

STwo minute time delay to return to standby operation from last valid communication (with Evolution only).

SOne minute time delay of outdoor fan at termination of cooling

mode when outdoor ambient is greater than or equal to 100_F (38°C).

SThere is no time delay between air conditioner staging from low to high and from high to low capacity; the compressor will change from low to high and from high to low capacity as demand dictates.

577D-- -- A

23

Image 23
Contents Table of Contents Installation InstructionsCheck Equipment Safety ConsiderationsReceiving and Installation IntroductionUnit Falling Hazard Provide ClearancesRig and Place Unit UNIT/STRUCTURAL Damage HazardCPRFCURB012A00 SizeCPRFCURB010A00 CPRFCURB011A00577D--A24-30 Unit Dimensions 577D--A36-60 Unit Dimensions Physical Data Unit 577D--A Indoor FAN Physical Data Con’t Unit 577D--APersonal Injury Hazard Select and Install DuctworkCabinet Model Rigging Weight Supply and Return Duct Opening Provide for Condensate DisposalCarbon Monoxide Poisoning Hazard Install Flue HoodInstall Gas Piping Unit Component Damage Hazard Install Electrical ConnectionsFire or Explosion Hazard Humidifier Connections Outdoor Air Temperature Sensor OATElectronic Air Cleaner Maximum Gas Flow CapacityTypical Installation Control Plate FIRE, EXPLOSION, Electrical Shock and Environmental Hazard Unit Start-Up and TroubleshootingPRE-START-UP START-UPFurnace Control Troubleshooting Indoor Fan Motor Troubleshooting577D a A10217L A10219C A10219L HP/AC Control Troubleshooting Unit Operation Hazard Sequence of OperationHeat Pump/Air Conditioner Board Status Codes Air Delivery and Temperature Rise at Rated Heating InputUnit Damage Hazard Dehumidification ModeEvolution Controlled LOW Ambient Cooling Check GAS Input Natural GASCanada Fire and Unit Damage HazardU.S.A Altitude Derate Multiplier for U.S.ACheck Burner Flame Check GAS Input Propane GASCheck for Refrigerant Leaks Start-Up AdjustmentsFilter Pressure Drop Table IN. W.C Heating InputsECM Wet Coil Pressure Drop IN. W.C Cooling Charging Table-Subcooling Maintenance Outdoor Fan Inducer Pressure SwitchElectrical Controls and Wiring Outdoor Coil, Indoor Coil, and Condensate Drain PanCopeland Scroll Compressor Puron Refrigerant Pressure Switches Refrigerant CircuitRefrigerant Circuit Indoor AirflowTroubleshooting Final Checks Care and Maintenance Observe all warnings, cautions, and bold text Symptom Cause Remedy Troubleshooting Chart CoolingBurners will not ignite Troubleshooting Chart Gas Furnace OperationIII. START-UP Electrical Supply Voltage Compressor Amps START-UP ChecklistTemperatures Preliminary Information Model no

577D----A specifications

The Bryant 577D----A is a highly regarded model in the HVAC industry, representing a blend of efficiency, performance, and advanced technology. This heating and cooling unit is designed to cater to a variety of residential and light commercial applications, making it a versatile choice for consumers looking to enhance their indoor climate control systems.

One of the standout features of the Bryant 577D----A is its impressive energy efficiency rating. With a Seasonal Energy Efficiency Ratio (SEER) typically exceeding 14, this model is engineered to reduce energy consumption, helping homeowners lower their utility bills while minimizing environmental impact. The unit also employs a two-stage cooling system, which not only improves comfort by maintaining more consistent temperatures but also provides enhanced dehumidification during hotter months.

The technology used in the Bryant 577D----A is noteworthy. The unit incorporates a variable-speed compressor that adapts to the specific cooling or heating needs of the space, ensuring optimal performance at all times. This advanced feature not only contributes to energy savings but also allows for quieter operation compared to single-stage systems. The inclusion of a smart thermostat integration further enhances convenience, enabling users to manage their HVAC system remotely and optimize settings according to their schedules.

Additional characteristics of the Bryant 577D----A include a durable construction designed to withstand various environmental conditions. The cabinet is made from quality materials that protect against corrosion and other factors that could affect the unit's longevity. Furthermore, the unit operates quietly, thanks to sound-dampening technologies, which is a significant advantage for residential areas where noise can be a concern.

Maintenance is also simplified with the Bryant 577D----A, as it is equipped with self-diagnostics for easy troubleshooting. This feature alerts users to potential issues before they escalate, promoting efficient operation and prolonging the lifespan of the system.

In conclusion, the Bryant 577D----A stands out as a superior choice for those seeking reliability and efficiency in their HVAC solutions. With its energy-efficient operation, advanced technologies, and robust construction, it serves as a valuable investment for homeowners committed to comfort and sustainability.