Bryant 577D----A Maximum Gas Flow Capacity, Outdoor Air Temperature Sensor OAT

Page 13

Table 2 – Maximum Gas Flow Capacity*

NOMINAL

INTERNAL

 

 

 

 

 

LENGTH OF PIPE ft (m)†

 

 

 

 

 

IRON PIPE

DIAMETER

10

20

30

40

50

60

70

80

90

100

125

150

175

200

SIZE (IN.)

(IN.)

(3.0)

(6.1)

(9.1)

(12.1)

(15.2)

(18.3)

(21.3)

(24.4)

(27.4)

(30.5)

(38.1)

(45.7)

(53.3)

(61.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2

.622

175

120

97

82

73

66

61

57

53

50

44

40

3/4

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

1---1/4

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

1---1/2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5---IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2 and NFPA 54/ANSI Z223.1.

{This length includes an ordinary number of fittings.

ROUTING CONTROL POWER WIRES

For detailed instruction on the low voltage connections to the User Interface (UI), refer to the UI installation guide.

Form a drip-loop with the control leads before routing them into the unit. Route the low voltage control leads through grommeted, low-voltage hole provided into unit (See Fig. 5 and 6). Connect user interface leads to unit control power leads as shown in Fig. 14.

The unit transformer supplies 24-v power for complete system including accessory electrical heater. Transformer is factory wired for 230-v operation. If supply voltage is 208-v, rewire transformer primary as described in Special Procedures for 208-v Operation section.

The furnace board is fused by a board-mounted automotive fuse placed in series with transformer SEC1 and R circuit. The C circuit of transformer circuit is referenced to chassis ground through a printed circuit run at SEC2 and gas valve grounding wire. Check to be sure control board is mounted securely using both factory-installed screws.

ACCESSORY INSTALLATION

A. Outdoor Air Temperature Sensor (OAT)

!CAUTION

EQUIPMENT OPERATION HAZARD

The installation of an outdoor air temperature sensor (OAT) using the Evolution control board OAT terminals is required. Many Evolution features (auto humidity control, comfort rollback, etc.) will be lost if the OAT is not connected.

For detailed mounting instructions for the OAT sensor, please refer installation instructions shipped with the OAT.

The OAT input is used to supply outdoor temperature data for system level functions and for temperature display on User Interface (UI). Using two wires of the field-supplied thermostat wire cable, wire the ends of the two black OAT pigtails. Wire the opposite ends of these two wires to the OAT provided with the UI. There is no polarity to be observed.

NOTE: Mis-wiring OAT inputs will not cause damage to either Evolution control or thermistor. If the thermistor is wired incorrectly, no reading will appear at UI. Re-wire thermistor correctly for normal operation.

B. Humidifier Connections

The furnace control board terminal marked HUM is provided for low voltage (24-vac) control of a humidifier. No humidistat is required as UI monitors indoor humidity.

When commanded to operate humidifier, the unit control will energize the HUM output to turn humidifier on and de-energize HUM output to turn humidifier off. Wire HUM and COM terminals directly to humidifier as shown in Fig. 14.

C. Electronic Air Cleaner

Electronic Air Cleaner terminals are provided on the Evolution Control Board (EAC-1 and EAC-2). While these terminals can be used to power a 230V EAC, it is recommended that any EAC be installed per the EAC installation instructions and connected separately to a standard 115V or 230V outlet with an airflow sensor to control operation of the EAC.

SPECIAL PROCEDURES FOR 208-V OPERATION Be sure unit disconnect switch is open.

Disconnect the black primary lead from the transformer. See unit wiring label (See Fig. 16 and 17).

Connect the black primary lead to the transformer terminal labeled 208-v.

577D-- -- A

13

Image 13
Contents Table of Contents Installation InstructionsReceiving and Installation Safety ConsiderationsIntroduction Check EquipmentRig and Place Unit Provide ClearancesUNIT/STRUCTURAL Damage Hazard Unit Falling HazardCPRFCURB010A00 SizeCPRFCURB011A00 CPRFCURB012A00577D--A24-30 Unit Dimensions 577D--A36-60 Unit Dimensions Physical Data Unit 577D--A Indoor FAN Physical Data Con’t Unit 577D--ACabinet Model Rigging Weight Select and Install DuctworkPersonal Injury Hazard Supply and Return Duct Opening Provide for Condensate DisposalInstall Gas Piping Install Flue HoodCarbon Monoxide Poisoning Hazard Fire or Explosion Hazard Install Electrical ConnectionsUnit Component Damage Hazard Electronic Air Cleaner Outdoor Air Temperature Sensor OATMaximum Gas Flow Capacity Humidifier ConnectionsTypical Installation Control Plate PRE-START-UP Unit Start-Up and TroubleshootingSTART-UP FIRE, EXPLOSION, Electrical Shock and Environmental HazardFurnace Control Troubleshooting Indoor Fan Motor Troubleshooting577D a A10217L A10219C A10219L HP/AC Control Troubleshooting Unit Operation Hazard Sequence of OperationHeat Pump/Air Conditioner Board Status Codes Air Delivery and Temperature Rise at Rated Heating InputEvolution Controlled LOW Ambient Cooling Dehumidification ModeCheck GAS Input Natural GAS Unit Damage HazardU.S.A Fire and Unit Damage HazardAltitude Derate Multiplier for U.S.A CanadaCheck Burner Flame Check GAS Input Propane GASCheck for Refrigerant Leaks Start-Up AdjustmentsECM Wet Coil Pressure Drop IN. W.C Heating InputsFilter Pressure Drop Table IN. W.C Cooling Charging Table-Subcooling Maintenance Electrical Controls and Wiring Inducer Pressure SwitchOutdoor Coil, Indoor Coil, and Condensate Drain Pan Outdoor FanRefrigerant Circuit Pressure Switches Refrigerant CircuitIndoor Airflow Copeland Scroll Compressor Puron RefrigerantTroubleshooting Final Checks Care and Maintenance Observe all warnings, cautions, and bold text Symptom Cause Remedy Troubleshooting Chart CoolingBurners will not ignite Troubleshooting Chart Gas Furnace OperationTemperatures START-UP ChecklistPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor Amps

577D----A specifications

The Bryant 577D----A is a highly regarded model in the HVAC industry, representing a blend of efficiency, performance, and advanced technology. This heating and cooling unit is designed to cater to a variety of residential and light commercial applications, making it a versatile choice for consumers looking to enhance their indoor climate control systems.

One of the standout features of the Bryant 577D----A is its impressive energy efficiency rating. With a Seasonal Energy Efficiency Ratio (SEER) typically exceeding 14, this model is engineered to reduce energy consumption, helping homeowners lower their utility bills while minimizing environmental impact. The unit also employs a two-stage cooling system, which not only improves comfort by maintaining more consistent temperatures but also provides enhanced dehumidification during hotter months.

The technology used in the Bryant 577D----A is noteworthy. The unit incorporates a variable-speed compressor that adapts to the specific cooling or heating needs of the space, ensuring optimal performance at all times. This advanced feature not only contributes to energy savings but also allows for quieter operation compared to single-stage systems. The inclusion of a smart thermostat integration further enhances convenience, enabling users to manage their HVAC system remotely and optimize settings according to their schedules.

Additional characteristics of the Bryant 577D----A include a durable construction designed to withstand various environmental conditions. The cabinet is made from quality materials that protect against corrosion and other factors that could affect the unit's longevity. Furthermore, the unit operates quietly, thanks to sound-dampening technologies, which is a significant advantage for residential areas where noise can be a concern.

Maintenance is also simplified with the Bryant 577D----A, as it is equipped with self-diagnostics for easy troubleshooting. This feature alerts users to potential issues before they escalate, promoting efficient operation and prolonging the lifespan of the system.

In conclusion, the Bryant 577D----A stands out as a superior choice for those seeking reliability and efficiency in their HVAC solutions. With its energy-efficient operation, advanced technologies, and robust construction, it serves as a valuable investment for homeowners committed to comfort and sustainability.