Bryant 559F operation manual XIII. Base Unit Operation, Service Cleaning, II. Lubrication

Page 20

XIII. BASE UNIT OPERATION

A. Cooling, Units Without Economizer

When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC), and compressor contactor no. 1 (C1) are energized and evaporator- fan motor, compressor no. 1 and condenser fans start. The condenser-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by ener- gizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts.

B.Heating, Units Without Economizer (If Accessory or Op- tional Heater is Installed)

Upon a call for heating through terminal W1, IFC and heater contactor no. 1 (HC1) are energized. On units equipped for 2 stages of heat, when additional heat is needed, HC2 is en- ergized through W2.

C. Cooling, Units With Economizer

Upon a call for cooling, when outdoor ambient temperature is above the outdoor-air temperature control setting, the evapo- rator and condenser fans and compressor energize. The econo- mizer damper moves to VENT position.

Upon a ®rst-stage call for cooling, when outdoor ambient temperature is below the temperature control setting, the evapo- rator fan starts and economizer damper modulates to main- tain mixed-air temperature. The compressor(s) remains off.

Upon a second-stage call for cooling, compressor no. 1 is en- ergized and mechanical cooling is integrated with econo- mizer cooling. Compressor no. 2 is locked out. If the outdoor- air temperature is below 50 F, a cooling lockout switch prevents the compressor(s) from running.

When supply-air temperature drops below a ®xed set point, the economizer damper modulates to maintain the tempera- ture at the ®xed set point.

D. Freeze Protection Thermostat

A freeze protection thermostat (FPT) is located on the evapo- rator coil. It detects frost build-up and turns off the compres- sor, allowing the coil to clear. Once frost has melted, the com- pressor can be reenergized by resetting the compressor lockout.

E.Heating, Units With Economizer (If Accessory or Op- tional Heater Is Installed)

The outdoor air damper stays at VENT position while the evapo- rator fan is operating. Upon a call for heating through ter- minal W1, the indoor (evaporator) fan contactor (IFC) and heater contactor no. 1 (HC1) are energized. On units equipped for 2 stages of heat, when additional heat is needed, HC2 is energized through W2.

SERVICE

WARNING: Before performing service or mainte- nance operations on unit, turn off main power switch to unit. Turn off accessory heater power switch if appli- cable. Electrical shock could cause personal injury.

I. CLEANING

Inspect unit interior at beginning of each heating and cool- ing season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior.

A. Evaporator Coil

Clean as required with a commercial coil cleaner.

NOTE: The 559F300 unit has a mist eliminator screen attached to the evaporator coil to prevent condensate runoff at high wet-bulb conditions. Check periodically and clean as necessary.

B. Condenser Coil

Clean condenser coil annually and as required by location and outdoor-air conditions. Inspect coil monthly Ð clean as required.

C. Condensate Drain

Check and clean each year at start of cooling season.

D. Filters

Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to Table 1 for type and size.

NOTE: The 559F300 unit requires industrial grade throw- away ®lters capable of withstanding face velocities up to 625 fpm. Ensure that replacement ®lters for the 559F300 units are rated for 625 fpm.

E. Outdoor-Air Inlet Screens

Clean screens with steam or hot water and a mild detergent. Do not use throwaway ®lters in place of screens.

II. LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at the factory. Conventional white oil (Sontext 200LT) is used. White oil is compatible with 3GS oil, and 3GS oil may be used if the addition of oil is required. See compressor nameplate for original oil charge. A complete recharge should be four ounces less than the original oil charge. When a com- pressor is exchanged in the ®eld it is possible that a major portion of the oil from the replaced compressor may still be in the system. While this will not affect the reliability of the replacement compressor, the extra oil will add rotor drag and increase power usage. To remove this excess oil, an access valve may be added to the lower portion of the suction line at the inlet of the compressor. The compressor should then be run for 10 minutes, shut down, and the access valve opened until no oil ¯ows. This should be repeated twice to make sure the proper oil level has been achieved.

B. Fan Shaft Bearings

For size 180 units, bearings are permanently lubricated. No ®eld lubrication is required. For size 216-300 units, the bear- ings are of the pillow block type and have grease ®ttings. The bearing opposite the motor end has an extended tube line so it can be lubricated from the motor side. Lubricate the bear- ings twice annually.

Typical lubricants are given below:

MANUFACTURER

LUBRICANT

Texaco

Regal AFB-2*

Mobil

Mobilplex EP No. 1

Sunoco

Prestige 42

Texaco

Multifak 2

*Preferred lubricant because it contains rust and oxidation inhibitors.

C. Condenser and Evaporator-Fan Motor Bearings

The condenser and evaporator-fan motors have permanently- sealed bearings, so no ®eld lubrication is necessary.

Ð20Ð

Image 20
Contents Contents Safety ConsiderationsInstallation Provide Unit Support II. Ð RIG and Place UnitUnit DEG 559FUnit Maximum Dimensions Shipping Weight 559F Ft-in 180216 240Base Unit Dimensions, 559F180 Base Unit Dimensions, 559F240 Physical Data CompressorTrap Condensate Drain III. Ð Field Fabricate DuctworkIV. Ð Make Unit Duct Connections Field Power Supply Field Control WiringVI. Ð Make Electrical Connections Unit VoltageElectrical Data FLA LRA MCA MOCP²Ð10Ð VII. Ð Make OUTDOOR-AIR Inlet Adjustments Heat Anticipator SettingsManual Outdoor-Air Damper Optional EconomizerVIII. Ð Install OUTDOOR-AIR Hood Outdoor-Air Hood Component LocationIX. Ð Install ALL Accessories Motormaster I Control Installation 559F180Motormaster III Control Installation 559F240 559F180 559F216II. Service Valves III. Internal WiringVI. Refrigerant Service Ports XII. Accessory Economizer AdjustmentFan Performance Ð 559F180 FiopBhp Brake Horsepower Fan Performance Ð 559F216559F216 and 240 18 and 20 Tons Air¯ow Rpm Bhp Watts 500Fan Performance Ð 559F300 Accessory/FIOP Static Pressure in. wg Ð 559F180 Accessory/FIOP Static Pressure in. wg Ð 559F216-300Fan Rpm at Motor Pulley Settings Component CFMII. Lubrication Service CleaningXIII. Base Unit Operation III. Evaporator FAN Performance Adjustment Fig IV. Evaporator FAN Service and Replacement559F180 Units See Fig 559F216-300 Units See FigBelt Tension Adjustment VI. CONDENSER-FAN AdjustmentVII. Economizer Adjustment 559F180-216 Units FigVIII. Power Failure IX. Refrigerant ChargeFilter Drier XI. Protective DevicesXIII. Control Circuit XIV. Replacement PartsXII. Relief Devices Problem Cause Remedy TroubleshootingCooling Service Analysis Typical Wiring Schematic 559F180, 460-v Shown AHA IFCIfcb IFMTypical Component Arrangement 559F180 Shown Page Service Training Call for Free CatalogPage START-UP Checklist PRE-START-UP

559F specifications

The Bryant 559F is a standout heating and cooling solution, designed with both efficiency and performance in mind. This model is a part of Bryant's legacy of reliability, combining innovative technology with user-friendly features to ensure a comfortable indoor environment throughout the year.

One of the most notable features of the Bryant 559F is its high efficiency rating. With a Seasonal Energy Efficiency Ratio (SEER) that exceeds industry standards, this model is engineered to significantly reduce energy consumption, translating to lower utility bills and a smaller carbon footprint. The system is designed to perform efficiently even in extreme temperatures, making it a reliable choice for households in diverse climates.

Incorporating advanced inverter technology, the Bryant 559F automatically adjusts its output to meet the precise cooling and heating needs of the space, providing consistent comfort while minimizing energy usage. This adaptive capability reduces energy waste, resulting in more efficient operation compared to traditional systems that constantly cycle on and off.

The Bryant 559F also features an integrated Wi-Fi capability, allowing users to control their heating and cooling system remotely via a smartphone app. This modern convenience empowers homeowners to create schedules, adjust settings, and monitor performance from virtually anywhere, enhancing both comfort and energy management.

Another characteristic of the Bryant 559F is its quiet operation. Thanks to sound-dampening features, the system is designed to operate at lower noise levels, providing a peaceful indoor environment. This makes it particularly suitable for residential applications where noise can be a concern, such as bedrooms and home offices.

Additionally, the Bryant 559F is equipped with advanced air filtration and purification systems that help improve indoor air quality. This is particularly beneficial for allergy sufferers or those concerned about pollutants in the air. The system can remove dust, pollen, and other particulates, creating a healthier living space.

Furthermore, the Bryant 559F model is backed by a robust warranty, showcasing Bryant's commitment to quality and customer satisfaction. Overall, the Bryant 559F combines innovative technology, energy efficiency, and user-friendly features to deliver a reliable heating and cooling solution that meets the needs of modern households. Its blend of performance, comfort, and convenience makes it an excellent choice for anyone looking to enhance their indoor climate control solutions.