TYPICAL PIPING AND WIRING

LEGEND

NEC — National Electrical Code

NOTES:

1.Wiring and piping shown are not intended for or to include all details for specific installation.

2.All wiring must comply with applicable local and national codes.

3.All piping must follow standard refrigerant piping techniques.

4.For other installation details refer to Installation Instructions.

5.If unit sections are field split, 8 threaded support rods are required.

6.Ensure condenser air recirculation is minimized.

APPLICATION DATA

OUTDOOR-AIR TEMPERATURE OPERATING LIMITS (F)

UNIT 502A

 

024

036

048

060

Without Head Pressure Control

Minimum

35

35

40

40

 

Maximum

126

126

126

126

With Head Pressure Control

Minimum

0

0

0

0

 

Maximum

126

126

126

126

Field Splitting Instructions — If components are split, maxi- mum length of refrigerant tubing to be used is 50 ft, assuming components are installed in same horizontal plane. Condenser may be mounted up to 12-ft above evaporator. Liquid line tubing is 3/8-in. OD copper tubing, and discharge line is 1/2-in. OD copper tubing. Units should always be within line of sight from each other, or separate NEC (National Electrical Code)

disconnects will be required. Junction boxes should be installed in both the evaporator and condenser sections adjacent to D-shaped grommets, to provide a location to splice the outdoor- fan motor factory wiring (no. 16 AWG [American Wire Gage], 4/64-in. thick insulation). Field wiring should be a minimum of no. 16 AWG, 4/64-in. thick insulation. Check all applicable electri- cal codes to ensure proper compliance.

14

Image 14
Contents FEATURES/BENEFITS Model 502AARI* Capacity Ratings Table of ContentsModel Number Nomenclature Physical Data Operating Weight Distribution Center of GravityDimensions Unit 502ADimensions FIELD-INSTALLED AccessoriesAccessory 88EN Electric Heat ModuleUnit Component Locations Base Unit DimensionsDimensions ft-in Selection Procedure with example Performance DataEvaporator FAN Performance Performance DataGross Cooling Capacities Belt Drive Evaporator FAN Performance Condenser FAN PerformanceOperating Sequence ControlsElectrical Data CoolingElectric Heater Static Pressure Drop in. wg Typical Wiring SchematicsElectrical Data Typical Wiring Schematics 502A024, 230-1-60 Units502A048,060, 230-1-60 Units 502A048,060, 575-3-60 Units BKR W/ATApplication Data Typical Piping and WiringOUTDOOR-AIR Temperature Operating Limits F With Head Pressure Control Minimum MaximumPart 1 General Guide SpecificationsIndoor Packaged Unit Part 2 ProductsGuide Specifications Specifications Subject to Change Without Notice