Bryant 502A manual Selection Procedure with example, Performance Data

Page 6

SELECTION PROCEDURE (with example)

I DETERMINE COOLING REQUIREMENTS AT DESIGN CONDITIONS.

Given:

Gross Cooling Capacity

Required (TC) . . . . . . . . . . . . . . . . . . . . . . . . . 39,000 Btuh Sensible Heat Capacity (SHC) . . . . . . . . . . . . 30,500 Btuh Temperature of Air Entering Condenser . . . . . . . . . . . 95 F Temperature of Air Entering

Evaporator. . . . . . . . . . . . . . . . . . . . . 80 F edb/67 F ewb Evaporator Air Quantity . . . . . . . . . . . . . . . . . . . 1,200 cfm External Static Pressure:

Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . 0.50 in. wg Evaporator (includes static pressure

drop of factory-supplied filter

of 0.06 in. wg) . . . . . . . . . . . . . . . . . . . . . . 0.20 in. wg

IISELECT UNIT BASED UPON REQUIRED COOLING CAPACITY.

67 F ewb will provide a Total Capacity (TC) of 44,200 Btuh and a Sensible Heat Capacity (SHC) of 31,300 Btuh. Since the entering air is 80 F edb, an SHC correction is not required.

IIIDETERMINE EVAPORATOR FAN PERFORMANCE.

Enter Evaporator Fan Performance table at 1200 cfm and 502A036 data. The external static pressure shown (0.23 in. wg) will exceed the 0.20 in. wg required. The fan motor will require 0.52 kW.

IV DETERMINE CONDENSER FAN PERFORMANCE AND MOTOR PULLEY SETTING REQUIREMENTS.

Enter Condenser Fan Performance table at the selected cfm and required static pressure of 0.50 in. wg. The fan motor will require 0.73 kW and the motor pulley should be set at 2 turns open at 1350 cfm of condenser air required.

NOTE: Unit 502A024 contains a direct-drive condenser fan assembly.

Enter cooling capacity table at temperature of air entering condenser of 95 F. The 502A036 unit at 1200 cfm and

PERFORMANCE DATA

GROSS COOLING CAPACITIES

502A024

Temp

 

Evaporator Air Quantity — Cfm/BF

 

Air Ent

600/0.02

800/0.03

1000/0.04

Condenser

 

 

Evaporator Air Ewb Temp (F)

 

 

 

(F)

 

 

 

 

 

 

 

 

 

 

72

67

62

72

67

62

72

67

62

 

 

 

 

 

TC

27.1

25.3

23.0

27.7

26.4

24.6

27.8

26.9

25.8

85

 

SHC

13.5

17.0

20.2

14.7

19.4

23.7

15.6

21.5

25.8

 

 

kW

1.64

1.62

1.61

1.65

1.63

1.62

1.65

1.64

1.63

 

 

TC

26.6

24.5

20.8

27.4

25.8

22.9

28.0

26.5

25.2

95

 

SHC

13.4

16.7

19.1

14.7

19.4

22.8

16.0

21.7

25.2

 

 

kW

1.85

1.84

1.80

1.86

1.85

1.82

1.87

1.85

1.84

 

 

TC

25.8

22.3

18.4

27.1

24.5

21.2

27.7

25.6

23.6

105

 

SHC

13.1

15.8

17.9

14.7

18.9

21.2

16.2

21.5

23.6

 

 

kW

2.09

2.05

1.99

2.11

2.08

2.04

2.12

2.10

2.07

 

 

TC

24.6

19.9

16.5

26.1

22.0

19.8

26.8

23.6

22.3

115

 

SHC

12.7

14.8

16.5

14.4

17.9

19.8

16.0

20.7

22.3

 

 

kW

2.36

2.29

2.22

2.39

2.33

2.29

2.39

2.35

2.33

See Legend on page 7.

502A036

Temp

 

Evaporator Air Quantity — Cfm/BF

 

Air Ent

900/0.01

1050/0.01

1200/0.02

Condenser

 

 

Evaporator Air Ewb Temp (F)

 

 

 

(F)

 

 

 

 

 

 

 

 

 

 

72

67

62

72

67

62

72

67

62

 

 

 

 

 

TC

45.0

41.1

37.3

45.8

42.3

38.6

46.5

43.4

39.8

85

 

SHC

22.5

27.7

32.6

23.6

29.9

35.6

24.6

32.0

38.3

 

 

kW

3.19

3.07

2.96

3.22

3.11

3.00

3.25

3.14

3.04

 

 

TC

43.0

38.8

34.3

44.1

40.1

35.8

45.0

44.2

37.4

95

 

SHC

21.8

26.8

31.1

23.1

29.1

34.1

24.4

31.3

36.8

 

 

kW

3.42

3.28

3.15

3.46

3.33

3.20

3.49

3.37

3.25

 

 

TC

40.4

35.8

29.6

41.6

37.1

31.3

42.6

38.2

33.2

105

 

SHC

20.9

25.6

28.5

22.3

27.9

30.8

23.7

30.2

33.2

 

 

kW

3.63

3.48

3.38

3.68

3.53

3.44

3.73

3.58

3.49

 

 

TC

37.7

30.6

25.8

38.7

31.6

37.8

39.7

32.8

29.7

115

 

SHC

19.9

23.3

25.8

21.3

25.5

27.8

22.7

27.8

29.7

 

 

kW

3.85

3.71

3.59

3.90

3.76

3.67

3.94

3.80

3.73

6

Image 6
Contents FEATURES/BENEFITS Model 502ATable of Contents Model Number NomenclatureARI* Capacity Ratings Physical Data Operating Weight Distribution Center of GravityDimensions Unit 502ADimensions FIELD-INSTALLED AccessoriesAccessory 88EN Electric Heat ModuleBase Unit Dimensions Dimensions ft-inUnit Component Locations Selection Procedure with example Performance DataPerformance Data Gross Cooling CapacitiesEvaporator FAN Performance Belt Drive Evaporator FAN Performance Condenser FAN PerformanceOperating Sequence ControlsElectrical Data CoolingTypical Wiring Schematics Electrical DataElectric Heater Static Pressure Drop in. wg Typical Wiring Schematics 502A024, 230-1-60 Units502A048,060, 230-1-60 Units 502A048,060, 575-3-60 Units BKR W/ATApplication Data Typical Piping and WiringOUTDOOR-AIR Temperature Operating Limits F With Head Pressure Control Minimum MaximumPart 1 General Guide SpecificationsIndoor Packaged Unit Part 2 ProductsGuide Specifications Specifications Subject to Change Without Notice