Bryant 502A manual Controls, Electrical Data, Operating Sequence, Cooling, Electric Heater Data

Page 9

CONTROLS

OPERATING SEQUENCE

Cooling

1.Thermostat calls for cooling.

a.Indoor (evaporator) fan relay is energized and starts evaporator fan.

b.Compressor contactor is energized to start compressor and condenser fan (up to a 5-minute delay on single- phase units).

2.When room thermostat is satisfied, the evaporator fan, com- pressor, and condenser fan shut off.

Continuous Fan Operation — The thermostat can be set for continuous operation by setting the fan switch to ON.

ELECTRICAL DATA

UNIT

V-PH

 

VOLTAGE RANGE

COMPRESSOR

 

FAN MOTORS

 

 

POWER SUPPLY

 

Evaporator

Condenser

 

Min Ckt

MOCP

502A

(60 Hz)

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

Hp

FLA

Hp

FLA

 

Amps

Amps

024

 

230-1

 

207

254

11.5

62.5

.17

1.10

.50

3.40

 

19.1

25

036

 

230-1

 

207

254

17.2

96.0

.50

3.20

.75

6.06

 

29.5

40

 

208/230-3

 

187

254

10.2

77.0

.50

3.20

.75

3.93

 

19.9

25

 

 

460-3

 

414

508

4.3

37.0

.50

1.50

.75

1.97

 

8.8

15

 

 

230-1

 

207

254

23.7

129.0

.75

4.00

1.0

8.35

 

42.0

60

048

 

208/230-3

 

187

254

13.5

99.0

.75

4.00

1.0

3.93

 

24.8

35

 

460-3

 

414

508

7.4

49.5

.75

2.15

1.0

1.97

 

13.4

15

 

 

 

 

 

 

575-3

 

518

632

5.8

40.0

.75

1.40

1.0

1.45

 

10.1

15

048*

 

208/230-3

 

187

254

13.5

99.0

1.5

5.60

1.0

3.93

 

26.4

35

 

460-3

 

414

508

7.4

49.5

1.5

2.80

1.0

1.97

 

14.0

20

 

 

 

 

 

 

230-1

 

207

254

28.8

169.0

.75

4.00

1.5

9.50

 

49.5

70

060

 

208/230-3

 

187

254

17.3

123.0

.75

4.00

1.5

4.82

 

30.4

45

 

460-3

 

414

508

9.0

62.0

.75

2.15

1.5

2.41

 

15.8

25

 

 

 

 

 

 

575-3

 

518

632

7.1

50.0

.75

1.40

1.5

1.90

 

12.2

20

060*

 

208/230-3

 

187

254

17.3

123.0

1.5

5.60

1.5

4.82

 

32.0

40

 

460-3

 

414

508

9.0

62.0

1.5

2.80

1.5

2.41

 

16.5

25

 

 

 

 

 

 

LEGEND

 

 

 

*Optional evaporator-fan motor nameplate data.

 

 

HACR

Heating, Air Conditioning, and Refrigeration

 

 

 

 

 

 

 

 

Hp

Horsepower

 

 

 

 

 

 

 

 

 

 

 

FLA

Full Load Amps

 

 

 

 

 

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

MOCP — Maximum Overcurrent Protection (HACR breaker)

 

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEATER DATA

ELECTRIC HEATER

USED WITH

V-PH

CAP. (kW)

 

BRANCH CIRCUIT

 

UNIT 88EN

UNIT 502A

(60 Hz)

Heater Amps

MCA

 

MOCP (Amps)

 

 

0050CA01

 

240-1

5.0

20.8

26.0

 

30

0075CA01

 

240-1

7.5

31.3

39.1

 

40

0115CA01

024, 036

240-1

11.5

47.9

59.9

 

60

0075EA01

1-Stage Heat

208-3

5.6

15.6

19.5

 

20

 

240-3

7.6

18.0

22.6

 

25

 

 

 

1150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-3

15.0

36.1

45.1

 

50

 

 

 

0100EA01

 

208-3

7.5

20.8

26.0

 

30

 

240-1*

10.0

41.7

52.1

 

60

 

 

240-3

10.0

24.1

30.1

 

35

0150EA01

 

208-3

11.3

31.2

39.0

 

40

 

240-1*

15.0

62.5

78.1

 

80

 

 

240-3

15.0

36.1

45.1

 

50

0200EA01

 

208-3

15.0

41.7

52.1

 

60

048, 060

240-1*

20.0

83.3

104.2

 

110

 

2-Stage Heat

240-3

20.0

46.9

58.6

 

60

0300EA01

 

208-3

22.5

62.5

78.2

 

80

 

240-3

30.0

72.2

90.2

 

100

 

 

 

0300CA01

 

240-1

30.0

124.0

155.0

 

175

0100FA01

 

480-3

10.0

12.0

15.0

 

15

0150FA01

 

480-3

15.0

18.1

22.6

 

25

0200FA01

 

480-3

20.0

24.1

30.1

 

35

0300FA01

 

480-3

30.0

36.1

45.1

 

50

LEGEND

*May be field converted to single-phase units, see electric heat installa-

MCA — Minimum Circuit Ampacity

tion instructions.

MOCP — Maximum Overcurrent Circuit Protection

NOTE: Separate power source is required for all heaters. Control from

(Fuses or Circuit Breaker)

base unit 502A (24 v).

9

Image 9
Contents Model 502A FEATURES/BENEFITSTable of Contents Model Number NomenclatureARI* Capacity Ratings Dimensions Operating Weight Distribution Center of GravityPhysical Data Unit 502AAccessory FIELD-INSTALLED AccessoriesDimensions 88EN Electric Heat ModuleBase Unit Dimensions Dimensions ft-inUnit Component Locations Performance Data Selection Procedure with examplePerformance Data Gross Cooling CapacitiesEvaporator FAN Performance Condenser FAN Performance Belt Drive Evaporator FAN PerformanceElectrical Data ControlsOperating Sequence CoolingTypical Wiring Schematics Electrical DataElectric Heater Static Pressure Drop in. wg 502A024, 230-1-60 Units Typical Wiring Schematics502A048,060, 230-1-60 Units BKR W/AT 502A048,060, 575-3-60 UnitsOUTDOOR-AIR Temperature Operating Limits F Typical Piping and WiringApplication Data With Head Pressure Control Minimum MaximumIndoor Packaged Unit Guide SpecificationsPart 1 General Part 2 ProductsSpecifications Subject to Change Without Notice Guide Specifications