Bryant 502A manual Table of Contents, Model Number Nomenclature, ARI* Capacity Ratings

Page 2

TABLE OF CONTENTS

Page

Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . 2

ARI Capacity Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Field-Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Base Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-8

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9,10

Typical Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . .10-13

Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15,16

MODEL NUMBER NOMENCLATURE

502A P X 048 000 AB

Model Designation

502A Horizontal, Indoor

Single-Package Cooling Unit

Voltage

J — 208/230-1-60

P — 208/230-3-60

E — 460-3-60

T — 575-3-60

Indoor Fan Motor

AAStandard Motor

AB — 1.5 hp Optional Motor*

Electric Heaters

000 — No factory-installed electric heaters

Nominal Tons 024 — 2 036 — 3 048 — 4 060 — 5

XHeat Not Installed

(field-installed electric heaters available)

*Factory-Installed option, contact your local representative for specific information.

ARI* CAPACITY RATINGS

UNIT

 

V-PH-Hz

 

TOTAL

NET TOTAL

NOMINAL

EER

SEER

SEER

SOUND RATING

502A

 

 

kW

COOLING CAP. (Btuh)

CFM

(with TDR)

(dB)

 

 

 

 

 

024

 

208/230-1-60

 

2.6

25,000

800

10.80

11.00

78

036

 

208/230-1-60

 

 

 

 

10.00

10.05

 

 

208/230-3-60

 

4.3

36,000

1200

9.0

82

 

 

460-3-60

 

 

 

 

9.0

 

 

 

208/230-1-60

 

 

 

 

10.20

10.40

 

048

 

208/230-3-60

 

5.5

49,500

1600

9.1

82

 

460-3-60

 

9.1

 

 

 

 

 

 

 

 

 

575-3-60

 

 

 

 

9.1

 

 

 

208/230-1-60

 

 

 

 

9.75

10.05

 

060

 

208/230-3-60

 

6.9

58,500

2000

8.55

82

 

460-3-60

 

8.55

 

 

 

 

 

 

 

 

 

575-3-60

 

 

 

 

8.55

 

dB

LEGEND

 

 

 

 

 

 

 

Decibels

 

 

 

 

 

 

 

EER

Energy Efficiency Ratio

 

 

 

 

 

 

 

SEER — Seasonal Energy Efficiency Ratio

 

 

 

 

 

 

TDR

Time-Delay Relay

 

 

 

 

 

 

 

*Air-conditioning and Refrigeration Institute.

NOTES:

1.Ratings are at zero condenser air static and rated in accordance with ARI Standard 210.

NET CAPACITY (Btuh)

2. EER =

TOTAL WATTS

2

Image 2
Contents FEATURES/BENEFITS Model 502AARI* Capacity Ratings Table of ContentsModel Number Nomenclature Physical Data Operating Weight Distribution Center of GravityDimensions Unit 502ADimensions FIELD-INSTALLED AccessoriesAccessory 88EN Electric Heat ModuleUnit Component Locations Base Unit DimensionsDimensions ft-in Selection Procedure with example Performance DataEvaporator FAN Performance Performance DataGross Cooling Capacities Belt Drive Evaporator FAN Performance Condenser FAN PerformanceOperating Sequence ControlsElectrical Data CoolingElectric Heater Static Pressure Drop in. wg Typical Wiring SchematicsElectrical Data Typical Wiring Schematics 502A024, 230-1-60 Units502A048,060, 230-1-60 Units 502A048,060, 575-3-60 Units BKR W/ATApplication Data Typical Piping and WiringOUTDOOR-AIR Temperature Operating Limits F With Head Pressure Control Minimum MaximumPart 1 General Guide SpecificationsIndoor Packaged Unit Part 2 ProductsGuide Specifications Specifications Subject to Change Without Notice