Bard W24H1, W18H1, W48H1, W36H1, W42H1, W60H1 Wiring Main Power, Wiring LOW Voltage Wiring, TAP Range

Page 14

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

See Table 5 for Electrical Specifications.

WIRING – LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

For wiring size and connections, refer to Wiring Manual 2100-507.

Manual

2100-511

Page

14 of 27

Image 14
Contents W18H1 W24H1 W30H1 W36H1 W42H1 W48H1 W60H1 Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersHeat Pump Wall Mount Model Nomenclature Shipping DamageGeneral Fresh AIR Intake Duct WorkFilters Condensate DrainWall Mounting Information Mounting the UnitRight Unit Supply ReturnW18H1, W24H1 Mountinginstructions W30H1, W36H1 Mountinginstructions W42H1, W48H1, W60H1 Mountinginstructions Electric Heat Clearance W30H1, W36H1, W42H1, W48H1, W60H1Wall Mounting Instructions Common Wall Mounting Installations TAP Range Wiring Main PowerWiring LOW Voltage Wiring Safety Practices Topping OFF System ChargeThree Phase Scroll Compressor Start UP Information Important Installer NoteHigh & LOW Pressure Switch Phase MonitorDefrost Cycle Pressure Service PortsSequence of Operation Defrost Control Board Solid State Heat Pump Control Troubleshootingprocedure TroubleshootingChecking Temperature Sensor Outside Unit Circuit Temperature F VS. Resistance R of Temperature SensorRefrigerant Charge FAN Blade Setting DimensionsRemoval of FAN Shroud Heating Pressures ALL Temperatures F Cooling Pressure TableElectrical Specifications W**H Series Recommendedairflow Indoor Blower PerformanceTables Maximum ESP of Operation Electric Heat only Electric HeatOptional Accessories Heater Kits Circuit Breaker Wmcb & Pull Disconnect WmpdVent & Control Options W18, W24 W30, W36 W42, W48, W60