INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1.Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3.

2.On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

3.Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.

MOUNTING THE UNIT

1.These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.

2.The unit itself is suitable for 0 inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material for model series W30, W36, W42, W48 and W60. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 3 for details on opening sizes.

3.Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.

4.Mount bottom mounting bracket.

5.Hook top rain flashing, attached to front - right of supply flange for shipping, under back bend of top.

WARNING

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death.

6.Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.

7.Secure rain flashing to wall and caulk across entire length of top. See Figure 3.

8.For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.

9.On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.

Clearances Required for Service Access and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

W18H, W24H, W30H, W36H

15"

20"

W42H, W48H, W60H

20"

20"

Minimum Clearances Required to Combustible Materials

MODELS

SUPPLY AIR DUCT

CABINET

FIRST THREE FEET

W18H

/ W24H

0"

0"

W30H

/ W36H

1/4"

0"

W42H

/ W48H / W60H

1/4"

0"

Manual 2100-511 Page 6 of 27

Image 6
Contents W18H1 W24H1 W30H1 W36H1 W42H1 W48H1 W60H1 Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersShipping Damage GeneralHeat Pump Wall Mount Model Nomenclature Fresh AIR Intake Duct WorkFilters Condensate DrainWall Mounting Information Mounting the UnitRight Unit Supply ReturnW18H1, W24H1 Mountinginstructions W30H1, W36H1 Mountinginstructions W42H1, W48H1, W60H1 Mountinginstructions Electric Heat Clearance W30H1, W36H1, W42H1, W48H1, W60H1Wall Mounting Instructions Common Wall Mounting Installations Wiring Main Power Wiring LOW Voltage WiringTAP Range Safety Practices Topping OFF System ChargeThree Phase Scroll Compressor Start UP Information Important Installer NoteHigh & LOW Pressure Switch Phase MonitorPressure Service Ports Sequence of OperationDefrost Cycle Defrost Control Board Solid State Heat Pump Control Troubleshootingprocedure TroubleshootingChecking Temperature Sensor Outside Unit Circuit Temperature F VS. Resistance R of Temperature SensorFAN Blade Setting Dimensions Removal of FAN ShroudRefrigerant Charge Heating Pressures ALL Temperatures F Cooling Pressure TableElectrical Specifications W**H Series Recommendedairflow Indoor Blower PerformanceTables Maximum ESP of Operation Electric Heat only Electric HeatOptional Accessories Heater Kits Circuit Breaker Wmcb & Pull Disconnect WmpdVent & Control Options W18, W24 W30, W36 W42, W48, W60