Bard W36H1, W24H1, W18H1, W48H1, W42H1 Sequence of Operation, Pressure Service Ports, Defrost Cycle

Page 17

SEQUENCE OF OPERATION

COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.

HEATING – A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing “Auto” changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season, and thus eliminating pressure equalization noise except during defrost, are to be used. On “Auto” option a circuit is completed from R-W1 and R-Y on each heating “on” cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second option has no “Auto” changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A Thermostat demand for heat completes R-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number. See Tables 4A & 4B.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time on the solid state heat pump control. See Figure 8.

When the outdoor temperature is in the lower 40°F temperature range or colder, the outdoor coil temperature is 32°F or below. This coil temperature is sensed by the coil temperature sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30°F or below, the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start.

After 60 minutes at 30°F or below, the heat pump control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57°F, the coil temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically.

If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of 30, 60 or 90-minute setting. All models are shipped from the factory on the 60-minute pin. If special circumstances require a change to another time, remove the wire from the 60-minute terminal and reconnect to the desired terminal. The manufacturer’s recommendation is for 60-minute defrost cycles. Refer to Figure 8.

There is a cycle speed up jumper on the control. This can be used to reduce the time between defrost cycle operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or another ¼ inch QC, to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost.

Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.

As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals. Otherwise the timing will remain accelerated and run through the 1-minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence.

There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature.

This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.

By placing a jumper across the SEN JMP terminals (a

¼inch QC terminal works best) the defrost sensor mounted on the outdoor coil is shunted out and will activate the timing circuit. This permits the defrost cycle to be checked out in warmer weather conditions without the outdoor temperature having to fall into the defrost region.

In order to terminate the defrost test the SEN JMP jumper must be removed. If left in place too long, the compressor could stop due to the high pressure control opening because of high pressure condition created by operating in the cooling mode with outdoor fan off. Pressure will rise fairly fast as there is likely no actual frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay function built into the HPC. This is to protect the compressor from short cycling conditions. In some instances, it is helpful to the service technician to override or speed up this timing period, and shorting out the SPEEDUP terminals for a few seconds can do this.

Manual

2100-511

Page

17 of 27

Image 17
Contents W18H1 W24H1 W30H1 W36H1 W42H1 W48H1 W60H1 Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsHeat Pump Wall Mount Model Nomenclature Shipping DamageGeneral Filters Duct WorkFresh AIR Intake Condensate DrainMounting the Unit Wall Mounting InformationSupply Return Right UnitW18H1, W24H1 Mountinginstructions W30H1, W36H1 Mountinginstructions W42H1, W48H1, W60H1 Mountinginstructions W30H1, W36H1, W42H1, W48H1, W60H1 Electric Heat ClearanceWall Mounting Instructions Common Wall Mounting Installations TAP Range Wiring Main PowerWiring LOW Voltage Wiring Topping OFF System Charge Safety PracticesHigh & LOW Pressure Switch Important Installer NoteThree Phase Scroll Compressor Start UP Information Phase MonitorDefrost Cycle Pressure Service PortsSequence of Operation Defrost Control Board Troubleshooting Solid State Heat Pump Control TroubleshootingprocedureTemperature F VS. Resistance R of Temperature Sensor Checking Temperature Sensor Outside Unit CircuitRefrigerant Charge FAN Blade Setting DimensionsRemoval of FAN Shroud Cooling Pressure Table Heating Pressures ALL Temperatures FElectrical Specifications W**H Series Indoor Blower Performance RecommendedairflowElectric Heat Tables Maximum ESP of Operation Electric Heat onlyHeater Kits Circuit Breaker Wmcb & Pull Disconnect Wmpd Optional AccessoriesW18, W24 W30, W36 W42, W48, W60 Vent & Control Options
Related manuals
Manual 27 pages 26.73 Kb

W60H1, W18H1, W48H1, W30H1, W42H1 specifications

The Bard W24H1D, W24H1, W30H1D, W36H1, and W48H1D are advanced wall-mounted heating and cooling units that exemplify efficiency, performance, and adaptability. These models are particularly suited for residential and light commercial applications, providing excellent temperature control in a variety of settings.

One of the distinguishing features of these Bard units is their robust heat pump technology, which offers both heating and cooling capabilities. This dual-functionality enables users to regulate indoor climates effectively throughout different seasons. Bard's heat pumps are designed for high efficiency, helping to reduce energy consumption and lower utility bills while maintaining comfort.

The W24H1D and W24H1 models are suited for spaces requiring moderate heating and cooling, with their compact design allowing for easy installation in tight spaces. They provide a heating capacity of 24,000 BTU and are capable of delivering exceptional performance even in colder climates. The W30H1D, on the other hand, elevates this performance with a slightly higher output of 30,000 BTU, making it ideal for larger areas or environments with intensified temperature control needs.

For larger applications, the W36H1 and W48H1D models stand out with their impressive heating capacities of 36,000 BTU and 48,000 BTU, respectively. These units are engineered to tackle larger installations with ease, ensuring warmth during harsh winters and refreshing cool air in sweltering summers. The robust construction of these models also contributes to their durability and longevity, making them a cost-effective investment over time.

In addition to their heating and cooling capabilities, these Bard models come equipped with user-friendly interfaces, allowing for easy temperature adjustments. Many units include programmable thermostats that can be customized for different times of the day, enhancing convenience and energy management.

A standout characteristic of the Bard line is their quiet operation. Utilizing sound-dampening technology, these units are designed to minimize noise levels, making them suitable for residential settings where peace and tranquility are essential.

Moreover, Bard’s commitment to efficiency is evident in the design of these units. They adhere to strict energy efficiency guidelines, including the Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER) ratings. This attention to energy efficiency not only benefits the environment but also assures users of lower operational costs.

In summary, the Bard W24H1D, W24H1, W30H1D, W36H1, and W48H1D models provide versatile, efficient heating and cooling solutions suitable for various applications. With their advanced technologies and user-friendly features, these units stand out in the HVAC market, offering reliability and comfort year-round.