10-11. Selecting Extension Cord (Use Shortest Cord Possible)

Cord Lengths for 120 Volt Loads

YIf unit does not have GFCI receptacles, use GFCI-protected extension cord.

 

 

 

Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)*

 

Current

 

 

 

 

 

 

 

 

 

 

 

Load (Watts)

4

 

 

6

 

8

10

12

 

14

(Amperes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

 

 

 

 

350

(106)

225 (68)

137 (42)

 

100 (30)

 

 

 

 

 

 

 

 

 

 

 

7

840

 

 

400

(122)

250 (76)

150 (46)

100 (30)

 

62 (19)

 

 

 

 

 

 

 

 

 

 

10

1200

400 (122)

 

275 (84)

175 (53)

112 (34)

62 (19)

 

50 (15)

 

 

 

 

 

 

 

 

 

 

15

1800

300 (91)

 

175 (53)

112 (34)

75 (23)

37 (11)

 

30 (9)

 

 

 

 

 

 

 

 

 

 

 

20

2400

225 (68)

 

137 (42)

87

(26)

50 (15)

30 (9)

 

 

 

 

 

 

 

 

 

 

 

 

 

25

3000

175 (53)

 

112 (34)

62

(19)

37 (11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

3600

150 (46)

 

87

(26)

50

(15)

37 (11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

4200

125 (38)

 

75

(23)

50

(15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

4800

112 (34)

 

62

(19)

37 (11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

5400

100 (30)

 

62

(19)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

6000

87 (26)

 

50

(15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Conductor size is based on maximum 2% voltage drop

Cord Lengths for 240 Volt Loads

YIf unit does not have GFCI receptacles, use GFCI-protected extension cord.

 

 

 

Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)*

 

Current

 

 

 

 

 

 

 

 

 

 

Load (Watts)

4

 

6

 

8

10

12

 

14

(Amperes)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

1200

 

 

 

700

(213)

450 (137)

225 (84)

 

200 (61)

 

 

 

 

 

 

 

 

 

 

 

7

1680

 

 

800 (244)

500

(152)

300 (91)

200 (61)

 

125 (38)

 

 

 

 

 

 

 

 

 

 

 

10

2400

800 (244)

 

550 (168)

350

(107)

225 (69)

125 (38)

 

100 (31)

 

 

 

 

 

 

 

 

 

 

15

3600

600 (183)

 

350 (107)

225 (69)

150 (46)

75 (23)

 

60 (18)

 

 

 

 

 

 

 

 

 

 

20

4800

450 (137)

 

275 (84)

175 (53)

100 (31)

60 (18)

 

 

 

 

 

 

 

 

 

 

 

 

25

6000

350 (107)

 

225 (69)

125 (38)

75 (23)

 

 

 

 

 

 

 

 

 

 

 

 

 

30

7000

300 (91)

 

175 (53)

100 (31)

75 (23)

 

 

 

 

 

 

 

 

 

 

 

 

 

35

8400

250 (76)

 

150 (46)

100 (31)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

9600

225 (69)

 

125 (38)

75

(23)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

10,800

200 (61)

 

125 (38)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

12,000

175 (53)

 

100 (31)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Conductor size is based on maximum 2% voltage drop

OM-498 Page 40

Image 44
Contents Description OM-498Processes From Hobart to You Table of Contents Page Symbol Usage Arc Welding HazardsElectric Shock can kill ARC Rays can burn eyes and skinEngine Hazards Battery Explosion can Blind Moving Parts can cause injuryEngine Exhaust Gases can kill Engine Heat can cause firePrincipal Safety Standards EMF InformationRadiation can cause interference ARC Welding can cause interferenceSignification des symboles Consignes DE SÉ Curité Lire Avant UtilisationUN Choc É Lectrique peut tuer LES Fumé ES ET LES GAZ peuvent ê tre dangereuxLE Soudage peut provoquer un in- cendie ou une explosion DES Particules Volantes peuvent blesser les yeuxDES PIÈ CES Chaudes peuvent provoquer des brû lures graves LE Bruit peut affecter l’ouïeDES Organes Mobiles peuvent provoquer des blessures ’EXPLOSION DE LA Batterie peutLA Chaleur DU Moteur peut pro- voquer un incendie LA Chute DE L’APPAREIL peut blesserPrincipales normes de sé curité Information sur les champs é lectromagné tiquesLE Soudage À L’ARC risque de provoquer des interfé rences Consignes relatives aux stimulateurs cardiaquesSpecifications Symbol DefinitionsWeld, Power, And Engine Specifications DefinitionsDimensions, Weights, And Operating Angles Fuel Consumption Kohler-Powered UnitsDimensions Weight Kohler-Powered UnitsFuel Consumption Honda-Powered Units Exceeding duty cycle can damage unit and void warrantyDuty Cycle 100% Duty Cycle at 80 Amperes CC/DCAuxiliary Power Curve Volt-Ampere CurvesGrounding Generator To Truck Or Trailer Frame InstallationInstalling Welding Generator Grounding Generator When Supplying Building Systems Use ground device as stated in electrical codesEngine Prestart Checks Honda-Powered Units Connecting The Battery Honda Electric-Start Models OnlyOil Connect negative cable lastConnecting To Weld Output Terminals Selecting Weld Cable Sizes45 m 60 m 70 m 90 m 105 m 120 m Stop engine beforeControls Kohler-Powered Units Operating the Welding Generator60 Hz Choke Control LeverControls Honda-Powered Units See Section Recoil-Start 2Electric-StartDescription Of Controls Honda-Powered Units See Section Auxiliary Power Panel 495 218 USA Operating Auxiliary EquipmentCircuit Breaker CB1 120 V x 10 a + 240 V x 9 a = 3.5 kVA/ KW OM-498Optional Auxiliary Power Panels Auxiliary Power Panel 495Canada South Africa South America Australia Europe AsiaAuxiliary Power Panel Ratings It exceeds 3500WPlug Wired For 120/240 Wire LoadPlex receptacle shares a load with One half of the 240 V receptacleMaintenance Maintenance Label Overload Protection Honda-Powered Units OnlyAdjusting Engine Speed Kohler-Powered Units Weld/Power Speed AdjustmentTop View Idle Speed Adjustment Stop engine. Close fuel valve Top ViewAdjusting Engine Speed Honda-Powered Units Throttle Control Lever Adjustment ScrewStop engine. Close fuel valve Tools Needed 3/8Troubleshooting TroubleshootingAuxiliary Power WeldingCheck battery voltage Honda electric-start models only Viscosity oil for operating temperatureEngine Make starting difficultElectrical Diagrams Circuit Diagram For Welding GeneratorWiring Diagram For Welding Generator Wiring Diagram For Auxiliary Power Panels 1 Wiring Diagram For Auxiliary Power Panels 2 Auxiliary Power Guidelines Selecting EquipmentGrounding When Supplying Building Systems How Much Power Does Equipment Require?Earth ground if supplying Rating DataApproximate Power Requirements For Industrial Motors Approximate Power Requirements For Farm/Home EquipmentIndustrial Motors Rating Starting Watts Running Watts Farm/Home Equipment Rating Starting Watts Running WattsApproximate Power Requirements For Contractor Equipment Contractor Rating Starting Watts Running WattsPower Required To Start Motor How Much Power Can Generator Supply?Single-Phase Induction Motor Starting Requirements KVA/HP x HP xTypical Connections To Supply Standby Power Selecting Extension Cord Use Shortest Cord Possible Current Load Watts AmperesStick Welding Smaw Guidelines Stick Welding ProcedureWeld current starts when electrode touches work- piece Striking an Arc Tapping Technique Electrode and Amperage Selection ChartStriking an Arc Scratch Start Technique Poor Weld Bead Characteristics Good Weld Bead CharacteristicsPositioning Electrode Holder 9090 End View of Work AngleConditions That Affect Weld Bead Shape Electrode Movement During WeldingButt Joints Lap JointTee Joint 16 in 1.6 mm Tack WeldsTroubleshooting Porosity Troubleshooting Excessive SpatterWeld Test Possible Causes Corrective ActionsTroubleshooting Excessive Penetration Troubleshooting Incomplete FusionTroubleshooting Lack Of Penetration Troubleshooting Distortion Troubleshooting Burn-ThroughTroubleshooting Waviness Of Bead OM-498 Parts List 31-FigDia Part Auxiliary Power Panel 495 Auxiliary Power Panel 495 315 USA Auxiliary Power Panel 495 South Africa AustraliaCanada Europe AmericaAuxiliary Power Panel 495 Canada Auxiliary Power Panel 495 253 South AfricaAuxiliary Power Panel 495 Australia Auxiliary Power Panel 495 290 EuropeOM-498 Service SupportCall Contact your Distributor forHobart Welding Products