Carrier 50RTG Unit Start-Up Cooling Mode, Unit Start-Up Heating Mode, AIR Limits Cooling Heating

Page 17

NOTE: Three factors determine the operating limits of a unit:

(1)entering air temperature, (2) water temperature and (3) ambient temperature. Whenever any of these factors are at a minimum or maximum level, the other two factors must be at a normal level to ensure proper unit operation. See Table 15.

Table 15 — Operating Limits — 50RTG Units

AIR LIMITS

COOLING

HEATING

Rated Ambient Air

80° F

70° F

Min. Entering Air

50° F

40° F

Rated Entering Air db/wb

80/67° F

70° F

Max. Entering Air db/wb

110/83° F

80° F

WATER LIMITS

 

 

Min. Entering Water

25° F

25° F

Normal Entering Water

85° F

70° F

Max. Entering Water

115° F

115° F

LEGEND

 

 

db — Dry Bulb wb — Wet Bulb

NOTE: Value in heating column is dry bulb only. Any wet bulb read- ing is acceptable.

Scroll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure does not rise to normal levels:

1.Turn off power to the unit. Install disconnect tag.

2.Reverse any two of the unit power leads.

3.Reapply power to the unit and verify pressures are correct.

The suction and discharge pressure levels should now move to their normal start-up levels.

When the compressor is rotating in the wrong direction, the unit makes an elevated level of noise and does not provide cooling.

After a few minutes of reverse operation, the scroll com- pressor internal overload protection will open, thus activating the unit lockout. This requires a manual reset. To reset, turn the thermostat on and then off.

NOTE: There is a 5-minute time delay before the compressor will start.

Unit Start-Up Cooling Mode

1.Adjust the unit thermostat to the warmest position. Slowly reduce the thermostat position until the compres- sor activates.

2.Check for cool air delivery at unit grille a few minutes after the unit has begun to operate.

3.Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using P/T plugs. Check the elevation and cleanliness of the condensate lines; any dripping could be a sign of a blocked line. Be sure the condensate trap in- cludes a water seal.

4.Check the temperature of both supply and discharge water. If temperature is within range, proceed. If tempera- ture is outside the range, check the cooling refrigerant pressures.

5.Air temperature drop across the coil should be checked when compressor is operating. Air temperature drop should be between 15 and 25 F.

Unit Start-Up Heating Mode

NOTE: Operate the unit in heating cycle after checking the cooling cycle. Allow five minutes between tests for the pres- sure or reversing valve to equalize.

1.Turn thermostat to lowest setting and set thermostat switch to HEAT position.

2.Slowly turn the thermostat to a higher temperature until the compressor activates.

3.Check for warm air delivery at the unit grille within a few minutes after the unit has begun to operate.

4.Check the temperature of both supply and discharge water. If temperature is within range, proceed. If tempera- ture is outside the range, check the heating refrigerant pressures.

5.Once the unit has begun to run, check for warm air deliv- ery at the unit grille.

6.Air temperature rise across the coil should be checked when compressor is operating. Air temperature rise should be between 20 and 30 F after 15 minutes at load.

7.Check for vibration, noise and water leaks.

Flow Regulation — Flow regulation can be accom- plished by two methods. Most water control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger, the flow rate can be deter- mined. See Table 16. Adjust the water control valve until the flow of 1.5 to 2 gpm is achieved. Since the pressure con- stantly varies, two pressure gages may be needed in some applications.

An alternative method is to install a flow control device. These devices are typically an orifice of plastic material de- signed to allow a specified flow rate that are mounted on the outlet of the water control valve. Occasionally these valves produce a velocity noise that can be reduced by applying some back pressure. To accomplish this, slightly close the leaving isolation valve of the well water setup.

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position before flushing system.

Flushing — Once the piping is complete, final purging and loop charging is needed. A flush cart pump of at least 1.5 hp is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop. Flush the loop in both direc- tions with a high volume of water at a high velocity. Follow the steps below to properly flush the loop:

1.Verify power is off.

2.Fill loop with water from hose through flush cart before using flush cart pump to ensure an even fill. Do not allow the water level in the flush cart tank to drop below the pump inlet line to prevent air from filling the line.

3.Maintain a fluid level in the tank above the return tee to avoid air entering back into the fluid.

4.Shutting off the return valve that connects into the flush cart reservoir will allow 50 psi surges to help purge air pockets. This maintains the pump at 50 psi.

5.To purge, keep the pump at 50 psi until maximum pump- ing pressure is reached.

17

Image 17
Contents Safety Considerations ContentsGeneral InstallationUnit 50RTG Physical Data Aquazone 50RTG03-20 UnitsRefrigerant to AIR Heat Exchanger Number of Circuits Blower Data50RTG Dimensional Data Return Air Supply Condensate Drain 50RTG Curb InstallationWater Quality Guidelines Electrical Wiring50RTG03-07 with Economizer and Complete C Controller 50RTG03 Blower Performance 50RTG Electrical Data50RTG05 Blower Performance 50RTG04 Blower Performance50RTG08 Blower Performance 50RTG07 Blower Performance50RTG12 Blower Performance 50RTG10 Blower Performance50RTG20 Blower Performance 50RTG15 Blower PerformancePRE-START-UP Low Voltage WiringField Selectable Inputs Control Jumper Settings See FigControl Jumper Settings DIP Switch Block S2 Accessory 1 Relay Options Control Accessory Relay ConfigurationsDIP Switch Block S2 Accessory 2 Relay Options START-UPUnit Start-Up Heating Mode Unit Start-Up Cooling ModeOperating Limits 50RTG Units AIR Limits Cooling Heating50RTG Coaxial Water Pressure Drop Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C Control OperationUnits with Aquazone Deluxe D Control System TestControl LED Code Fault Descriptions ServiceControl Current LED Status Alarm Relay Operations ESD Alarm RelayDescription Status LED Test LED Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging FP1 and FP2 Thermistor Location Fault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Copyright 2002 Carrier Corporation II. START-UP 50RTG START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis

50RTG specifications

The Carrier 50RTG represents a significant advancement in the field of rooftop air conditioning systems, combining performance, efficiency, and reliability for commercial applications. Designed to meet the rigorous demands of today’s buildings, the 50RTG series is ideally suited for a variety of environments, including retail, office spaces, and industrial facilities.

One of the standout features of the Carrier 50RTG is its energy efficiency. Utilizing the latest in compressor technology, these units achieve high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), which translates to lower energy costs for users. This efficiency is further enhanced by the incorporation of environmentally friendly refrigerants that comply with current regulations, reducing the overall carbon footprint of the unit.

Another notable characteristic of the 50RTG series is its modular design. The unit can be tailored to specific requirements, making it versatile for different installation scenarios. This modularity not only simplifies maintenance and repair operations but also allows for easy upgrades as technologies evolve or as space demands change.

The advanced control system in the 50RTG is another key technology that sets it apart from competing products. Intuitive user interfaces and smart controls enable precise temperature regulation and improved energy management. These controls often include features such as variable speed fans and integrated economizers, which optimize the system's performance in real-time based on current load requirements.

Durability is also a hallmark of the Carrier 50RTG. Constructed with robust materials and designed to withstand harsh weather conditions, these units provide dependable operation year-round. The corrosion-resistant finish and weather-tight construction ensure that the systems maintain their performance levels and aesthetic appeal over time.

Additionally, the 50RTG series is designed with a focus on low noise operation. With quieter components and advanced noise control technology, these units are ideal for noise-sensitive environments, ensuring that occupants can work, live, or shop in comfort without disruptive background noise.

In summary, the Carrier 50RTG series exemplifies the perfect combination of energy efficiency, advanced technology, customization potential, durability, and low noise operation, making it a top choice for commercial heating and cooling needs. Its innovative features and reliable performance solidify its status as a leader in rooftop HVAC solutions, catering to the evolving requirements of modern buildings.