Table 22 — Troubleshooting (cont)

FAULT

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Only Compressor Runs

X

X

Thermostat wiring

Check G wiring at heat pump. Jumper G and R for fan operation.

 

X

X

Fan motor relay

Jumper G and R for fan operation. Check for line voltage across BR

 

 

 

 

contacts.

 

 

 

 

Check fan power enable relay operation (if present).

 

X

X

Fan motor

Check for line voltage at motor. Check capacitor.

 

X

X

Thermostat wiring

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

operation in test mode.

Unit Does Not Operate in

 

X

Reversing valve

Set for cooling demand and check 24 VAC on RV coil and at control.

Cooling

 

 

 

 

 

 

 

If RV is stuck, run high pressure up by reducing water flow and while

 

 

 

 

 

 

 

 

operating engage and disengage RV coil voltage to push valve.

 

 

X

Thermostat setup

Check for 'O' RV setup not 'B'.

 

 

X

Thermostat wiring

Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.

Insufficient capacity/

X

X

Dirty filter

Replace or clean.

Not cooling or heating

 

 

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

properly

 

 

 

heating

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

 

 

 

External static too high. Check blower Tables 4-12.

 

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

cooling

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

External static too high. Check blower Tables 4-12.

 

X

X

Leaky ductwork

Check supply and return air temperatures at the unit and at distant duct

 

 

 

 

registers if significantly different, duct leaks are present.

 

X

X

Low refrigerant charge

Check superheat and subcooling .

 

X

X

Restricted metering device

Check superheat and subcooling. Replace metering device.

 

 

X

Defective reversing valve

Perform RV touch test.

 

X

X

Thermostat improperly

Check location and for air drafts behind thermostat.

 

 

 

located

 

 

X

X

Unit undersized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

capacity.

 

X

X

Scaling in water heat

Perform Scaling check and clean if necessary.

 

 

 

exchanger

 

 

X

X

Inlet water too hot or cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

heating

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

External static too high. Check blower Tables 4-12.

 

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

 

 

 

cooling

Check water flow and adjust to proper flow rate.

 

 

 

 

 

 

X

Inlet water too hot

Check load, loop sizing, loop backfill, ground moisture.

 

X

 

Air temperature out of range

Bring return air temperature within design parameters.

 

 

 

in heating

 

 

 

X

Scaling in water heat

Perform Scaling check and clean if necessary.

 

 

 

exchanger

 

 

X

X

Unit overcharged

Check superheat and subcooling. Reweigh in charge.

 

X

X

Non-condensables in

Vacuum system and reweigh in charge.

 

 

 

system

 

 

X

X

Restricted metering device

Check superheat and subcooling. Replace metering device.

Low Suction Pressure

X

 

Reduced water flow in

Check pump operation or water valve operation/setting.

 

 

 

heating

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

range

 

 

 

X

Reduced airflow in cooling

Check for dirty air filter and clean or replace.

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

External static too high. Check blower Tables 4-12.

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering air temperature within design

 

 

 

 

parameters.

 

X

X

Insufficient charge

Check for refrigerant leaks.

Low discharge air

X

 

Airflow too high

Check blower Tables 4-12.

temperature in heating

X

 

Poor performance

See 'Insufficient Capacity'.

High humidity

 

X

Airflow too high

Check blower Tables 4-12.

 

 

X

Unit oversized

Recheck loads and sizing check sensible cooling load and heat pump

 

 

 

 

capacity.

LEGEND

 

 

 

 

RV — Reversing Valve

 

 

 

 

25

Image 25
Contents Safety Considerations ContentsGeneral InstallationUnit 50RTG Physical Data Aquazone 50RTG03-20 UnitsRefrigerant to AIR Heat Exchanger Number of Circuits Blower Data50RTG Dimensional Data Return Air Supply Condensate Drain 50RTG Curb InstallationWater Quality Guidelines Electrical Wiring50RTG03-07 with Economizer and Complete C Controller 50RTG03 Blower Performance 50RTG Electrical Data50RTG05 Blower Performance 50RTG04 Blower Performance50RTG08 Blower Performance 50RTG07 Blower Performance50RTG12 Blower Performance 50RTG10 Blower Performance50RTG20 Blower Performance 50RTG15 Blower PerformancePRE-START-UP Low Voltage WiringControl Jumper Settings Control Jumper Settings See FigField Selectable Inputs DIP Switch Block S2 Accessory 1 Relay Options Control Accessory Relay ConfigurationsDIP Switch Block S2 Accessory 2 Relay Options START-UPUnit Start-Up Heating Mode Unit Start-Up Cooling ModeOperating Limits 50RTG Units AIR Limits Cooling HeatingAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of Pipe50RTG Coaxial Water Pressure Drop Units with Aquazone Complete C Control OperationUnits with Aquazone Deluxe D Control System TestControl Current LED Status Alarm Relay Operations ServiceControl LED Code Fault Descriptions Description Status LED Test LED Alarm RelayESD Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location Fault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Copyright 2002 Carrier Corporation II. START-UP 50RTG START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis

50RTG specifications

The Carrier 50RTG represents a significant advancement in the field of rooftop air conditioning systems, combining performance, efficiency, and reliability for commercial applications. Designed to meet the rigorous demands of today’s buildings, the 50RTG series is ideally suited for a variety of environments, including retail, office spaces, and industrial facilities.

One of the standout features of the Carrier 50RTG is its energy efficiency. Utilizing the latest in compressor technology, these units achieve high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), which translates to lower energy costs for users. This efficiency is further enhanced by the incorporation of environmentally friendly refrigerants that comply with current regulations, reducing the overall carbon footprint of the unit.

Another notable characteristic of the 50RTG series is its modular design. The unit can be tailored to specific requirements, making it versatile for different installation scenarios. This modularity not only simplifies maintenance and repair operations but also allows for easy upgrades as technologies evolve or as space demands change.

The advanced control system in the 50RTG is another key technology that sets it apart from competing products. Intuitive user interfaces and smart controls enable precise temperature regulation and improved energy management. These controls often include features such as variable speed fans and integrated economizers, which optimize the system's performance in real-time based on current load requirements.

Durability is also a hallmark of the Carrier 50RTG. Constructed with robust materials and designed to withstand harsh weather conditions, these units provide dependable operation year-round. The corrosion-resistant finish and weather-tight construction ensure that the systems maintain their performance levels and aesthetic appeal over time.

Additionally, the 50RTG series is designed with a focus on low noise operation. With quieter components and advanced noise control technology, these units are ideal for noise-sensitive environments, ensuring that occupants can work, live, or shop in comfort without disruptive background noise.

In summary, the Carrier 50RTG series exemplifies the perfect combination of energy efficiency, advanced technology, customization potential, durability, and low noise operation, making it a top choice for commercial heating and cooling needs. Its innovative features and reliable performance solidify its status as a leader in rooftop HVAC solutions, catering to the evolving requirements of modern buildings.