Carrier 50RTG Coaxial Water Pressure Drop, Approximate Fluid Volume gal Per 100 Ft of Pipe

Page 18

6.Open the return valve to send a pressure surge through the loop to purge any air pockets in the piping system.

7.A noticeable drop in fluid level will be seen in the flush cart tank. This is the only indication of air in the loop.

NOTE: If air is purged from the system while using a 10 in. PVC flush tank, only a 1 to 2 in. level drop will be noticed since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being com- pressed in the loop. If level is less than 1 to 2 in., reverse the flow.

8.Repeat this procedure until all air is purged.

9.Restore power.

Antifreeze may be added before, during or after the flushing process. However, depending on when it is added in the process, it can be wasted. Refer to the Antifreeze section for more detail.

Loop static pressure will fluctuate with the seasons. Pres- sures will be higher in the winter months than during the warm- er months. This fluctuation is normal and should be considered when charging the system initially. Run the unit in either heat- ing or cooling for several minutes to condition the loop to a homogenous temperature.

When complete, perform a final flush and pressurize the loop to a static pressure of 40 to 50 psi for winter months or 15 to 20 psi for summer months.

After pressurization, be sure to remove the plug from the end of the loop pump motor(s) to allow trapped air to be discharged and to ensure the motor housing has been flooded. Be sure the loop flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger. Compare the results to the data in Table 16.

Table 16 — 50RTG Coaxial Water Pressure Drop

UNIT

 

WATER TEMPERATURE (F)

GPM

30

 

50

70

 

90

50RTG

 

 

 

 

Pressure Drop (ft. H2O)

 

 

 

 

 

 

4.0

3.1

 

2.8

2.8

 

2.8

03

6.0

6.1

 

5.3

5.3

 

5.3

 

8.0

9.9

 

8.9

8.9

 

8.9

 

10.0

14.3

 

12.9

12.9

 

12.9

 

5.5

4.2

 

3.4

3.4

 

3.4

04

8.5

8.9

 

7.8

7.8

 

7.8

 

11.5

14.8

 

13.2

13.2

 

13.2

 

14.0

20.5

 

18.6

18.6

 

18.6

 

7.0

8.1

 

5.3

5.3

 

5.3

05

11.0

16.9

 

11.2

11.2

 

11.2

 

15.0

28.5

 

18.9

18.9

 

18.9

 

18.0

38.8

 

25.6

25.6

 

25.6

 

10.0

3.4

 

2.3

2.3

 

2.3

07

15.0

10.1

 

6.7

6.7

 

6.7

 

20.0

16.0

 

10.7

10.7

 

10.7

 

24.0

22.3

 

14.9

14.9

 

14.9

 

11.0

4.5

 

3.5

3.5

 

3.5

08

17.0

9.4

 

8.1

8.1

 

8.1

 

22.0

14.2

 

12.7

12.7

 

12.7

 

27.0

20.0

 

18.2

18.2

 

18.2

 

14.0

8.3

 

5.5

5.5

 

5.5

10

22.0

17.6

 

11.7

11.7

 

11.7

 

30.0

29.4

 

19.7

19.7

 

19.7

 

36.0

39.9

 

26.7

26.7

 

26.7

 

17.0

4.8

 

3.2

3.2

 

3.2

12

25.0

9.4

 

6.0

6.0

 

6.0

 

34.0

13.1

 

10.3

10.3

 

10.3

 

40.0

22.0

 

13.5

13.5

 

13.5

 

21.0

5.2

 

2.9

2.9

 

2.9

15

32.0

10.7

 

7.4

7.4

 

7.4

 

42.0

17.4

 

11.6

11.6

 

11.6

 

51.0

24.3

 

16.5

16.5

 

16.5

 

31.0

10.6

 

6.4

6.4

 

6.4

20

47.0

21.2

 

13.1

13.1

 

13.1

 

62.0

34.2

 

20.8

20.8

 

20.8

 

74.0

46.2

 

28.0

28.0

 

28.0

Antifreeze — In areas where entering loop temperatures drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leav- ing loop temperature would be 22 to 25 F. Therefore, the freeze protection should be at 15 F (30 F – 15 F = 15 F).

IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or introduced under water level to prevent fumes.

Calculate the total volume of fluid in the piping system. See Table 17. Use the percentage by volume in Table 18 to deter- mine the amount of antifreeze to use. Antifreeze concentration should be checked from a well mixed sample using a hydrome- ter to measure specific gravity.

FREEZE PROTECTION SELECTION — The 30 F FP1 fac- tory setting (water) should be used to avoid freeze damage to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (anti- freeze 13 F) set point to avoid nuisance faults.

Table 17 — Approximate Fluid Volume (gal.)

per 100 Ft of Pipe

PIPE

DIAMETER (in.)

VOLUME (gal.)

Copper

1

 

 

4.1

 

1.25

 

6.4

 

1.5

 

9.2

Rubber Hose

1

 

 

3.9

Polyethylene

3/

IPS SDR11

2.8

 

4

 

 

4.5

 

1 IPS SDR11

 

11/

4

IPS SDR11

8.0

 

1/

IPS SDR11

10.9

 

2

 

 

18.0

 

2 IPS SDR11

 

11/

4

IPS SCH40

8.3

 

11/

IPS SCH40

10.9

 

2

 

2 IPS SCH40

17.0

LEGEND

IPS — Internal Pipe Size

SCH — Schedule

SDR — Standard Dimensional Ratio

NOTE: Volume of heat exchanger is approximately 1.0 gallon.

Table 18 — Antifreeze Percentages by Volume

 

MINIMUM TEMPERATURE FOR

ANTIFREEZE

 

FREEZE PROTECTION (F)

 

 

10

 

15

20

 

25

Methanol (%)

25

 

21

16

 

10

100% USP Food Grade

38

 

30

22

 

15

Propylene Glycol (%)

 

 

 

 

 

 

 

 

Cooling Tower/Boiler Systems — These systems typically use a common loop maintained at 60 to 90 F. The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recom- mended. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary.

Ground Coupled, Closed Loop and Plateframe Heat Exchanger Well Systems — These systems al- low water temperatures from 30 to 110 F. The external loop field is divided up into 2 in. polyethylene supply and return lines. Each line has valves connected in such a way that upon system start-up, each line can be isolated for flushing using only the system pumps. Air separation should be located in the piping system prior to the fluid re-entering the loop field.

18

Image 18
Contents Contents Safety ConsiderationsInstallation GeneralRefrigerant to AIR Heat Exchanger Physical Data Aquazone 50RTG03-20 UnitsUnit 50RTG Number of Circuits Blower Data50RTG Dimensional Data Return Air Supply 50RTG Curb Installation Condensate DrainElectrical Wiring Water Quality Guidelines50RTG03-07 with Economizer and Complete C Controller 50RTG Electrical Data 50RTG03 Blower Performance50RTG04 Blower Performance 50RTG05 Blower Performance50RTG07 Blower Performance 50RTG08 Blower Performance50RTG10 Blower Performance 50RTG12 Blower Performance50RTG15 Blower Performance 50RTG20 Blower PerformanceLow Voltage Wiring PRE-START-UPControl Jumper Settings See Fig Control Jumper SettingsField Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options Control Accessory Relay ConfigurationsDIP Switch Block S2 Accessory 1 Relay Options START-UPOperating Limits 50RTG Units Unit Start-Up Cooling ModeUnit Start-Up Heating Mode AIR Limits Cooling HeatingApproximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by Volume50RTG Coaxial Water Pressure Drop Units with Aquazone Deluxe D Control OperationUnits with Aquazone Complete C Control System TestService Control Current LED Status Alarm Relay OperationsControl LED Code Fault Descriptions Alarm Relay Description Status LED Test LEDESD Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location Troubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate Copyright 2002 Carrier Corporation 50RTG START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis

50RTG specifications

The Carrier 50RTG represents a significant advancement in the field of rooftop air conditioning systems, combining performance, efficiency, and reliability for commercial applications. Designed to meet the rigorous demands of today’s buildings, the 50RTG series is ideally suited for a variety of environments, including retail, office spaces, and industrial facilities.

One of the standout features of the Carrier 50RTG is its energy efficiency. Utilizing the latest in compressor technology, these units achieve high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), which translates to lower energy costs for users. This efficiency is further enhanced by the incorporation of environmentally friendly refrigerants that comply with current regulations, reducing the overall carbon footprint of the unit.

Another notable characteristic of the 50RTG series is its modular design. The unit can be tailored to specific requirements, making it versatile for different installation scenarios. This modularity not only simplifies maintenance and repair operations but also allows for easy upgrades as technologies evolve or as space demands change.

The advanced control system in the 50RTG is another key technology that sets it apart from competing products. Intuitive user interfaces and smart controls enable precise temperature regulation and improved energy management. These controls often include features such as variable speed fans and integrated economizers, which optimize the system's performance in real-time based on current load requirements.

Durability is also a hallmark of the Carrier 50RTG. Constructed with robust materials and designed to withstand harsh weather conditions, these units provide dependable operation year-round. The corrosion-resistant finish and weather-tight construction ensure that the systems maintain their performance levels and aesthetic appeal over time.

Additionally, the 50RTG series is designed with a focus on low noise operation. With quieter components and advanced noise control technology, these units are ideal for noise-sensitive environments, ensuring that occupants can work, live, or shop in comfort without disruptive background noise.

In summary, the Carrier 50RTG series exemplifies the perfect combination of energy efficiency, advanced technology, customization potential, durability, and low noise operation, making it a top choice for commercial heating and cooling needs. Its innovative features and reliable performance solidify its status as a leader in rooftop HVAC solutions, catering to the evolving requirements of modern buildings.