Carrier 50RTG specifications Electrical Wiring, Water Quality Guidelines

Page 7

Step 7 — Electrical Wiring

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors.

All field installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the

AB = 452 volts

BC = 464 volts

AC = 455 volts

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v. Determine percent voltage imbalance.

NEC.

% Voltage Imbalance = 100 x

7

Refer to unit wiring diagram Fig. 4 for a schematic of the field connections which must be made by the installing (or electrical) contractor.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.

Operating voltage must be the same voltage and phase as shown in Electrical Data shown in Table 3.

Make all final electrical connections with a length of flexi- ble conduit to minimize vibration and sound transmission to the building.

SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter- mine the percentage voltage imbalance:

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.

NOTE: If more than 2% voltage imbalance is present, contact local electric utility.

208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation (as illustrated on the wiring diagram) by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.

BLOWER SELECTION — All water source heat pumps are factory set with the appropriate motor and sheave combination to achieve the desired airflow performance. Performance is selected by matching the desired performance with the appro- priate region in Tables 4-12. Per the table notes, regions desig- nated by A, B, C and D represent motor drive options.

NOTE: Factory-installed sheaves are field adjustable. Refer to Tables 4-12 for adjustment points.

 

Table 2 — Water Quality Guidelines

 

 

 

 

 

CONDITION

ACCEPTABLE LEVEL

 

pH

7 to 9 range for copper. Cupro-nickel may be used in the 5 to 9 range.

 

Total Hardness

Calcium and magnesium carbonate should not exceed 20 grains per gallon (350 ppm).

Iron Oxides

Less than 1 ppm.

 

 

Iron Bacteria

No level allowable.

 

 

Corrosion*

 

Max Allowable Level

Coaxial Metal

 

Ammonia, Ammonium Hydroxide

0.5 ppm

Cu

 

Ammonium Chloride, Ammonium Nitrate

0.5 ppm

Cu

 

Ammonium Sulfate

0.5 ppm

Cu

 

Chlorine/Chlorides

0.5 ppm

CuNi

 

Hydrogen Sulfide†

None Allowable

Brackish

Use Cupro-nickel heat exchanger when concentrations of calcium or sodium chloride are greater

 

than 125 ppm are present. (Seawater is approximately 25,000 ppm.)

 

*If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists.

†Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause sys- tem problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0.

NOTE: To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.

7

Image 7
Contents Safety Considerations ContentsGeneral InstallationNumber of Circuits Blower Data Physical Data Aquazone 50RTG03-20 UnitsUnit 50RTG Refrigerant to AIR Heat Exchanger50RTG Dimensional Data Return Air Supply Condensate Drain 50RTG Curb InstallationWater Quality Guidelines Electrical Wiring50RTG03-07 with Economizer and Complete C Controller 50RTG03 Blower Performance 50RTG Electrical Data50RTG05 Blower Performance 50RTG04 Blower Performance50RTG08 Blower Performance 50RTG07 Blower Performance50RTG12 Blower Performance 50RTG10 Blower Performance50RTG20 Blower Performance 50RTG15 Blower PerformancePRE-START-UP Low Voltage WiringControl Jumper Settings Control Jumper Settings See FigField Selectable Inputs START-UP Control Accessory Relay ConfigurationsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsAIR Limits Cooling Heating Unit Start-Up Cooling ModeUnit Start-Up Heating Mode Operating Limits 50RTG UnitsAntifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of Pipe50RTG Coaxial Water Pressure Drop System Test OperationUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlControl Current LED Status Alarm Relay Operations ServiceControl LED Code Fault Descriptions Description Status LED Test LED Alarm RelayESD Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location Fault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate Copyright 2002 Carrier Corporation II. START-UP 50RTG START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis

50RTG specifications

The Carrier 50RTG represents a significant advancement in the field of rooftop air conditioning systems, combining performance, efficiency, and reliability for commercial applications. Designed to meet the rigorous demands of today’s buildings, the 50RTG series is ideally suited for a variety of environments, including retail, office spaces, and industrial facilities.

One of the standout features of the Carrier 50RTG is its energy efficiency. Utilizing the latest in compressor technology, these units achieve high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), which translates to lower energy costs for users. This efficiency is further enhanced by the incorporation of environmentally friendly refrigerants that comply with current regulations, reducing the overall carbon footprint of the unit.

Another notable characteristic of the 50RTG series is its modular design. The unit can be tailored to specific requirements, making it versatile for different installation scenarios. This modularity not only simplifies maintenance and repair operations but also allows for easy upgrades as technologies evolve or as space demands change.

The advanced control system in the 50RTG is another key technology that sets it apart from competing products. Intuitive user interfaces and smart controls enable precise temperature regulation and improved energy management. These controls often include features such as variable speed fans and integrated economizers, which optimize the system's performance in real-time based on current load requirements.

Durability is also a hallmark of the Carrier 50RTG. Constructed with robust materials and designed to withstand harsh weather conditions, these units provide dependable operation year-round. The corrosion-resistant finish and weather-tight construction ensure that the systems maintain their performance levels and aesthetic appeal over time.

Additionally, the 50RTG series is designed with a focus on low noise operation. With quieter components and advanced noise control technology, these units are ideal for noise-sensitive environments, ensuring that occupants can work, live, or shop in comfort without disruptive background noise.

In summary, the Carrier 50RTG series exemplifies the perfect combination of energy efficiency, advanced technology, customization potential, durability, and low noise operation, making it a top choice for commercial heating and cooling needs. Its innovative features and reliable performance solidify its status as a leader in rooftop HVAC solutions, catering to the evolving requirements of modern buildings.