Carrier specifications Condensate Drain, 50RTG Curb Installation

Page 6

Step 4 — Mounting the Unit — For proper opera- tion, units must be mounted on a roof curb as shown in Fig. 3. Follow these guidelines when installing the roof curb:

1.Set unit on curb.

2.Align unit so that its return and supply air direction match the return and supply air opening in the roof curb frame.

3.Run both the return and supply loop piping, as well as the electrical supply line, through the pipe chase provided in the curb.

Step 5 — Condensate Drain

1.Install a condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection.

2.Design the length of the trap (water seal) based on the amount of positive or negative pressure on the drain pan. As a rule, 1 in. of trap is required for each inch of nega- tive pressure on the unit.

Note that condensate is allowed to drain onto the roof.

Step 6 — Piping Connections — Depending on the application, there are 3 types of WSHP piping systems to choose from: water loop, ground-water and ground loop. Refer to Piping Section of Carrier System Design Manual for addi- tional information.

All WSHP units use low temperature soldered female pipe thread fittings for water connections to prevent annealing and out-of-round leak problems which are typically associated with high temperature brazed connections. Refer to Table 1 for con- nection sizes. When making piping connections, consider the following:

Use a backup wrench when making screw connections to unit to prevent internal damage to piping.

Insulation may be required on piping to avoid condensa- tion in the case where fluid in loop piping operates at temperatures below dew point of adjacent air.

Piping systems that contain steel pipes or fittings may be subject to galvanic corrosion. Dielectric fittings may be used to isolate the steel parts of the system to avoid galvanic corrosion.

50 RTG UNIT

FLASHING

GASKET

ROOF

CURB

Fig. 3 — 50RTG Curb Installation

WATER LOOP APPLICATIONS — Water loop applications usually include a number of units plumbed to a common pip- ing system. Maintenance to any of these units can introduce air into the piping system. Therefore, air elimination equipment comprises a major portion of the mechanical room plumbing.

The flow rate is usually set between 2.25 and 3 gpm per ton of cooling capacity. For proper maintenance and servicing, pressure-temperature (P/T) ports are necessary for temperature and flow verification.

In addition to complying with any applicable codes, consid- er the following for system piping:

Piping systems utilizing water temperatures below

50 F require 1/2-in. closed cell insulation on all piping surfaces to eliminate condensation.

All plastic to metal threaded fittings should be avoided due to the potential to leak. Use a flange fitted substitute.

Teflon tape thread sealant is recommended to minimize internal fouling of the heat exchanger.

Use backup wrench. Do not overtighten connections.

Route piping to avoid service access areas to unit.

The piping system should be flushed prior to operation to remove dirt and foreign materials from the system.

GROUND-WATER APPLICATIONS — In addition to com- plying with any applicable codes, consider the following for system piping:

Install shut-off valves for servicing.

Install pressure-temperature plugs to measure flow and temperature.

Boiler drains and other valves should be connected using a “T” connector to allow acid flushing for the heat exchanger.

Do not overtighten connections.

Route piping to avoid service access areas to unit.

Use PVC SCH80 or copper piping material.

NOTE: PVC SCH40 should not be used due to system high pressure and temperature extremes.

Water Supply and Quantity — Check water supply. Water supply should be plentiful and of good quality. See Table 2 for water quality guidelines.

IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed- system application design requirements may cause damage to the tube-in-tube heat exchanger that is not the responsi- bility of the manufacturer.

In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treat- ment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits.

GROUND-LOOP APPLICATIONS — Temperatures between 25 to 110 F and a cooling capacity of 2.25 to 3 gpm of flow per ton is recommended. In addition to complying with any appli- cable codes, consider the following for system piping:

Piping materials should be limited to only polyethylene fusion in the buried sections of the loop.

Galvanized or steel fittings should not be used at any time due to corrosion.

All plastic to metal threaded fittings should be avoided due to the potential to leak. Use a flange fitted substitute.

Do not overtighten connections.

Route piping to avoid service access areas to unit.

Pressure-temperature (P/T) plugs should be used to mea- sure flow of pressure drop.

6

Image 6
Contents Contents Safety ConsiderationsInstallation GeneralRefrigerant to AIR Heat Exchanger Physical Data Aquazone 50RTG03-20 UnitsUnit 50RTG Number of Circuits Blower Data50RTG Dimensional Data Return Air Supply 50RTG Curb Installation Condensate DrainElectrical Wiring Water Quality Guidelines50RTG03-07 with Economizer and Complete C Controller 50RTG Electrical Data 50RTG03 Blower Performance50RTG04 Blower Performance 50RTG05 Blower Performance50RTG07 Blower Performance 50RTG08 Blower Performance50RTG10 Blower Performance 50RTG12 Blower Performance50RTG15 Blower Performance 50RTG20 Blower PerformanceLow Voltage Wiring PRE-START-UPControl Jumper Settings See Fig Control Jumper SettingsField Selectable Inputs DIP Switch Block S2 Accessory 2 Relay Options Control Accessory Relay ConfigurationsDIP Switch Block S2 Accessory 1 Relay Options START-UPOperating Limits 50RTG Units Unit Start-Up Cooling ModeUnit Start-Up Heating Mode AIR Limits Cooling HeatingApproximate Fluid Volume gal Per 100 Ft of Pipe Antifreeze Percentages by Volume50RTG Coaxial Water Pressure Drop Units with Aquazone Deluxe D Control OperationUnits with Aquazone Complete C Control System TestService Control Current LED Status Alarm Relay OperationsControl LED Code Fault Descriptions Alarm Relay Description Status LED Test LEDESD Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal FP1 and FP2 Thermistor Location Troubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate Copyright 2002 Carrier Corporation 50RTG START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis

50RTG specifications

The Carrier 50RTG represents a significant advancement in the field of rooftop air conditioning systems, combining performance, efficiency, and reliability for commercial applications. Designed to meet the rigorous demands of today’s buildings, the 50RTG series is ideally suited for a variety of environments, including retail, office spaces, and industrial facilities.

One of the standout features of the Carrier 50RTG is its energy efficiency. Utilizing the latest in compressor technology, these units achieve high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), which translates to lower energy costs for users. This efficiency is further enhanced by the incorporation of environmentally friendly refrigerants that comply with current regulations, reducing the overall carbon footprint of the unit.

Another notable characteristic of the 50RTG series is its modular design. The unit can be tailored to specific requirements, making it versatile for different installation scenarios. This modularity not only simplifies maintenance and repair operations but also allows for easy upgrades as technologies evolve or as space demands change.

The advanced control system in the 50RTG is another key technology that sets it apart from competing products. Intuitive user interfaces and smart controls enable precise temperature regulation and improved energy management. These controls often include features such as variable speed fans and integrated economizers, which optimize the system's performance in real-time based on current load requirements.

Durability is also a hallmark of the Carrier 50RTG. Constructed with robust materials and designed to withstand harsh weather conditions, these units provide dependable operation year-round. The corrosion-resistant finish and weather-tight construction ensure that the systems maintain their performance levels and aesthetic appeal over time.

Additionally, the 50RTG series is designed with a focus on low noise operation. With quieter components and advanced noise control technology, these units are ideal for noise-sensitive environments, ensuring that occupants can work, live, or shop in comfort without disruptive background noise.

In summary, the Carrier 50RTG series exemplifies the perfect combination of energy efficiency, advanced technology, customization potential, durability, and low noise operation, making it a top choice for commercial heating and cooling needs. Its innovative features and reliable performance solidify its status as a leader in rooftop HVAC solutions, catering to the evolving requirements of modern buildings.