Carrier 50RTG specifications Low Voltage Wiring, Pre-Start-Up

Page 14

Step 8 — Low Voltage Wiring

THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the Aquazone™ control board. See Fig. 4 and 5.

WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at 30 F. In earth loop applications, jumper JW3 should be clipped to change the setting to 13 F when using antifreeze in colder earth loop applications. See Fig. 6.

AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for 30 F and should not need adjusting, unless using anti-freeze.

ACCESSORY CONNECTIONS — Terminal labeled A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This sig- nal operates with the compressor terminal. See Fig. 7. Refer to the specific unit wiring schematic for details.

NOTE: The A terminal should only be used with 24 volt signals — not line voltage signals.

WATER SOLENOID VALVES — Water solenoid valves may be used on primary secondary pump and ground water installa- tions. A typical well water control valve wiring which can limit waste water in a lockout condition is shown in Fig. 7. A slow closing valve may be required to prevent water hammer. When using a slow closing valve, special wiring conditions need to be considered. The valve takes approximately 60 sec- onds to open (very little water will flow before 45 seconds) and it activates the compressor only after the valve is completely opened by closing its end switch. When wired as shown, the valve will have the following operating characteristics:

1.Remain open during a lockout.

2.Draw approximately 25 to 35 VA through the “Y” signal of the thermostat.

IMPORTANT: This can overheat the anticipators of electromechanical thermostats. Only use relay based electronic thermostats.

 

Capacitor

 

Circ Brkr

 

Grnd

Contactor-CC

 

L2

L1

 

BR

Transformer

 

 

Aquazone “C”

CB

See Note

THERMOSTAT

Low Voltage

Connector

WIRED DIRECTLY

 

TO CONTROL

 

BOARD

 

NOTE: Low voltage connector may be removed for easy installation.

Fig. 5 — Low Voltage Field Wiring

AQUAZONE CONTROL (C Control Shown)

Fig. 6 — Typical Aquazone Control Board

Jumper Locations

Terminal Strip P2

C

Typical

24 VAC Water

Valve

A

Fig. 7 — Typical D Control Accessory Wiring

PRE-START-UP

System Checkout — When the installation is complete and the system is cleaned and flushed, follow the System Checkout procedure outlined below.

1.Voltage: Ensure that the voltage is within the utilization range specifications of the unit compressor and fan motor.

2.System Water Temperature: Ensure that the system water temperature is within an acceptable range to facili- tate start-up. (When conducting this check, also verify proper heating and cooling set points.)

3.System Water pH: Verify system water acidity (pH = 7.5 or 8.5). Proper pH promotes the longevity of hoses and heat exchangers.

4.System Flushing: Properly clean and flush the system periodically. Ensure that all supply and return hoses are connected end-to-end to facilitate system flushing and prevent fouling of the heat exchanger by system water. Water used in the system must be potable and should not contain dirt, piping slag, and chemical cleaning agents.

5.Closed-Type Cooling Tower or Open Tower with Heat Exchanger: Check equipment for proper temperature set points and operation.

6.Verify Balanced Water Flow Rate to Heat Pump.

7.Standby Pump: Verify that the standby pump is properly installed and in operating condition.

8.Access Panels: Assure that all access panels in the filter and fan section are securely closed.

9.Air Dampers: Assure that all air dampers are properly set.

14

Image 14
Contents Contents Safety ConsiderationsInstallation GeneralRefrigerant to AIR Heat Exchanger Physical Data Aquazone 50RTG03-20 UnitsUnit 50RTG Number of Circuits Blower Data50RTG Dimensional Data Return Air Supply 50RTG Curb Installation Condensate DrainElectrical Wiring Water Quality Guidelines50RTG03-07 with Economizer and Complete C Controller 50RTG Electrical Data 50RTG03 Blower Performance50RTG04 Blower Performance 50RTG05 Blower Performance50RTG07 Blower Performance 50RTG08 Blower Performance50RTG10 Blower Performance 50RTG12 Blower Performance50RTG15 Blower Performance 50RTG20 Blower PerformanceLow Voltage Wiring PRE-START-UPField Selectable Inputs Control Jumper Settings See FigControl Jumper Settings DIP Switch Block S2 Accessory 2 Relay Options Control Accessory Relay ConfigurationsDIP Switch Block S2 Accessory 1 Relay Options START-UPOperating Limits 50RTG Units Unit Start-Up Cooling ModeUnit Start-Up Heating Mode AIR Limits Cooling Heating50RTG Coaxial Water Pressure Drop Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Deluxe D Control OperationUnits with Aquazone Complete C Control System TestControl LED Code Fault Descriptions ServiceControl Current LED Status Alarm Relay Operations ESD Alarm RelayDescription Status LED Test LED Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging FP1 and FP2 Thermistor Location Troubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate Copyright 2002 Carrier Corporation 50RTG START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis

50RTG specifications

The Carrier 50RTG represents a significant advancement in the field of rooftop air conditioning systems, combining performance, efficiency, and reliability for commercial applications. Designed to meet the rigorous demands of today’s buildings, the 50RTG series is ideally suited for a variety of environments, including retail, office spaces, and industrial facilities.

One of the standout features of the Carrier 50RTG is its energy efficiency. Utilizing the latest in compressor technology, these units achieve high Seasonal Energy Efficiency Ratios (SEER) and Energy Efficiency Ratios (EER), which translates to lower energy costs for users. This efficiency is further enhanced by the incorporation of environmentally friendly refrigerants that comply with current regulations, reducing the overall carbon footprint of the unit.

Another notable characteristic of the 50RTG series is its modular design. The unit can be tailored to specific requirements, making it versatile for different installation scenarios. This modularity not only simplifies maintenance and repair operations but also allows for easy upgrades as technologies evolve or as space demands change.

The advanced control system in the 50RTG is another key technology that sets it apart from competing products. Intuitive user interfaces and smart controls enable precise temperature regulation and improved energy management. These controls often include features such as variable speed fans and integrated economizers, which optimize the system's performance in real-time based on current load requirements.

Durability is also a hallmark of the Carrier 50RTG. Constructed with robust materials and designed to withstand harsh weather conditions, these units provide dependable operation year-round. The corrosion-resistant finish and weather-tight construction ensure that the systems maintain their performance levels and aesthetic appeal over time.

Additionally, the 50RTG series is designed with a focus on low noise operation. With quieter components and advanced noise control technology, these units are ideal for noise-sensitive environments, ensuring that occupants can work, live, or shop in comfort without disruptive background noise.

In summary, the Carrier 50RTG series exemplifies the perfect combination of energy efficiency, advanced technology, customization potential, durability, and low noise operation, making it a top choice for commercial heating and cooling needs. Its innovative features and reliable performance solidify its status as a leader in rooftop HVAC solutions, catering to the evolving requirements of modern buildings.