has reached acceptable levels, the unit microprocessor will power on automatically and resume previous operation.

LEAVING WATER TEMPERATURE SENSOR FAIL- URE (LWT) — If the leaving water temperature thermistor fails, it will not affect the operation of the unit. This sensor is for monitoring purposes only.

DISCHARGE AIR TEMPERATURE SENSOR FAILURE (DAT) — If the discharge temperature thermistor fails, it will not affect the operation of the unit. This sensor is for monitor- ing purposes only.

FREEZE PROTECTION 1 TEMPERATURE SENSOR FAILURE (FP1) — If the freeze protection 1 thermistor fails for 30 continuous seconds an FP1 lockout will occur. The

compressor will then be deenergized and the blower will deen- ergize 15 seconds after the compressor is deenergized. The sen- sor must be replaced if this lockout occurs.

FREEZE PROTECTION 2 TEMPERATURE SENSOR FAILURE (FP2) — If the freeze protection 2 thermistor fails for 30 continuous seconds an FP2 lockout will occur. The compressor will then be deenergized and the blower will deen- ergize 15 seconds after the compressor is deenergized. The sen- sor must be replaced if this lockout occurs.

If unit performance during any mode appears abnormal, re- fer to Table 13.

Table 13 — Troubleshooting

 

ERROR CODE

SYSTEM WARNING (FLASH)

SYSTEM LOCKOUT (STEADY

 

FAULT DESCRIPTION

 

ON)

 

POSSIBLE FAULT CAUSE

(COMMTSTAT)

 

 

 

 

 

 

 

LED1

LED2

LED3

LED4

LED1

LED2

LED3

LED4

 

High Pressure Lockout

Er 1

OFF

OFF

OFF

FLASH

OFF

OFF

OFF

ON

Low Airflow (Heating), Low

< 600 psi

Water Flow (Cooling)

 

 

 

 

 

 

 

 

 

Low Pressure Lockout

Er 2

OFF

OFF

FLASH

OFF

OFF

OFF

ON

OFF

Low Refrigerant Charge

< 40 psi

 

 

 

 

 

 

 

 

 

 

Freeze Protection, Air

Er 4

OFF

OFF

FLASH

FLASH

OFF

OFF

ON

ON

Water Temperature < 35 F

Side

or < 15 F (Heating)

 

 

 

 

 

 

 

 

 

Freeze Protection, Air

Er 5

OFF

FLASH

OFF

OFF

OFF

ON

OFF

OFF

Blower Failure (Cooling)

Side < 35 F

 

 

 

 

 

 

 

 

 

 

Condensate Overflow

Er 9, Er 10

OFF

FLASH

OFF

FLASH

OFF

ON

OFF

ON

Clogged Drain Line

Over/Under Low Voltage

 

 

 

 

 

 

 

 

 

 

Protection, 18-vac >

Er 11

OFF

FLASH

FLASH

OFF

OFF

ON

ON

OFF

Loss of Power, Brown Out

voltage, 30-vac

 

 

 

 

 

 

 

 

 

 

LWT Sensor Failure (Low

Er 13

FLASH

OFF

OFF

OFF

N/A

N/A

N/A

N/A

Sensor Resistance Above

Water Temperature)

or Below Specification

 

 

 

 

 

 

 

 

 

DAT Sensor Failure

 

 

 

 

 

 

 

 

 

Sensor Resistance Above

(Discharge Air

Er 14

FLASH

OFF

OFF

FLASH

N/A

N/A

N/A

N/A

or Below Specification

Temperature)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1 Sensor Failure

Er 15

FLASH

OFF

FLASH

OFF

ON

OFF

ON

OFF

Sensor Resistance Above

(Freeze Protection)

or Below Specification

 

 

 

 

 

 

 

 

 

FP2 Sensor Failure

Er 16

FLASH

OFF

FLASH

FLASH

ON

OFF

ON

ON

Sensor Resistance Above

(Freeze Protection)

or Below Specification

 

 

 

 

 

 

 

 

 

LEGEND

LED — Light-Emitting Diode

NOTE: Warning LEDs and error codes are found on the system con- trol board.

Copyright 2008 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53500046-01

Printed in U.S.A.

Form 50VS-1SI

Pg 22

311 11-08

Replaces: New

Image 22
Contents Safety Considerations ContentsGeneral Installation Physical Data 50VS Unit50VSE,F 50VSG,H Dimension a Water Coil Unit ConnectionDRAINa50-8295 50VSM,NA50-8291 Dimensional Data10 x 16 x A50-8296Cabinet 14 xA50-8300 A50-8298A50-8297 A50-8299 A50-8301Install Cabinet and Riser A50-8331.eps Framing Rough-In DetailA50-8332 System Expansion LoopsType Temperature Protection Antifreeze Percentages by VolumeMinimum Temperature for LOW 10 F 15 F 20 F 25 FCondition Closed Open Loop and Recirculating Well Water Quality GuidelinesRECIRCULATING† Wire Field Power Supply Connections Chassis Electrical Data 50VS UnitTypical 50VS Unit Control Wiring A50-8352Recommended Wire Gage Low Voltage Thermostat Wire Field Control ConnectionsInstall Hose Kit Maximum RUN Unit toA50-8293 Install Chassis into the CabinetInstall Return Panel Hose Diameter Bend AllowanceA50-8302.eps Install Supply GrillePRE-START-UP Supply Grille Sizes and ArrangementsSystem Checkout DIP Switch Settings and OperationField Selectable Inputs Standard 24-vac Sequence of Operation START-UPWater Flow GPM Rise Drop Cooling F Heating F Temperature Change Through Heat ExchangerOperating Limits 20-26 10-17 Systems at 1.5 gpm per tonWater Coil Maintenance ServiceTroubleshooting Troubleshooting LED1 LED2 LED3 LED4START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis