Carrier 50VS specifications Service, Water Coil Maintenance, Troubleshooting

Page 21

SERVICE

WARNING

Electrical shock can cause personal injury or death. When installing or servicing system, always turn off main power to system. There may be more than one disconnect switch.

WARNING

The installation and servicing of air-conditioning equip- ment can be hazardous due to system pressure and electri- cal components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Water Coil Maintenance

CLOSED LOOP SYSTEM (All Other Water Loop Applica- tions) — Generally water coil maintenance is not needed for closed loop systems. However, if the piping is known to have high dirt or debris content, it is best to establish a periodic maintenance schedule with the owner so the water coil can be checked regularly. Dirty installations are typically the result of deterioration of iron or galvanized piping or components in the system. Open cooling towers requiring heavy chemical treat- ment and mineral build-up through water use can also contrib- ute to higher maintenance. Should periodic coil cleaning be necessary, use standard coil cleaning procedures, which are compatible with both the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. However, flow rates over 3 gpm per ton can produce water (or debris) velocities that can erode the heat exchanger wall and ultimately produce leaks.

OPEN LOOP SYSTEM (Direct Ground Water) — If the system is installed in an area with a known high mineral con- tent (125 ppm or greater) in the water, it is best to establish a periodic maintenance schedule with the owner so the coil can be checked regularly. Should periodic coil cleaning be neces- sary, use standard coil cleaning procedures, which are compati- ble with the heat exchanger material and copper water lines. Generally, the more water flowing through the unit, the less chance for scaling. Therefore, 1.5 gpm per ton is recommended as a minimum flow. Minimum flow rate for entering water temperatures below 50 F is 2.0 gpm per ton.

Filters — A clean filter must be used to obtain maximum performance. Filters should be inspected every month under normal operating conditions. It is especially important to pro- vide consistent washing of these filters (in the opposite direc- tion of the normal airflow) once per month. Never operate a unit without a filter, severe system damage can occur.

Condensate Drain — In areas where airborne bacteria may produce an algae build-up in the drain pan, it may be nec- essary to remove and treat the drain pan chemically with an al- gaecide approximately every three months to minimize the problem. The condensate pan may also need to be cleaned peri- odically to ensure indoor air quality. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect the drain twice a year to avoid the possibility of plugging.

Compressor — Conduct annual amperage checks to in- sure that amp draw is no more than 10% greater than indicated on the serial data plate.

Fan Motors — All units have lubricated fan motors. Peri- odic maintenance oiling is not recommended, as it will result in dirt accumulating in the excess oil and cause eventual motor failure. Conduct annual dry operation check and amperage

check to ensure amp draw is no more than 10% greater than in- dicated on serial data plate.

Evaporator Coil — The air coil must be cleaned to ob- tain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fins while cleaning.

CAUTION

Use caution when cleaning the coil fins as the fin edges are extremely sharp. Failure to heed this warning could result in personal injury.

Cabinet — The cabinet can be cleaned using a mild detergent. Do not allow water to stay in contact with the cabi- net for long periods of time to prevent corrosion of the cabinet sheet metal.

Refrigerant System — To maintain sealed circuit integ- rity, do not install service gages unless unit operation appears abnormal. Verify that air and water flow rates are at proper lev- els before servicing the refrigerant circuit.

TROUBLESHOOTING

Lockout Modes — If the microprocessor board is flash- ing a system warning and the unit is locked out and not run- ning, the lockout can be cleared from the microprocessor by a momentary shutdown of incoming line voltage (208-vac or 230-vac). A lockout that still occurs after line voltage shudown means that the fault still exists and needs to be repaired.

HIGH-PRESSURE LOCKOUT (HP) — The high-pressure lockout will occur if the discharge pressure of the compressor exceeds 600 psi. The lockout is immediate and has no delay from the time the high-pressure switch opens to the lockout. Upon lockout the compressor will be deenergized immediately. The blower will be deenergized 15 seconds after the compres- sor is deenergized.

LOW-PRESSURE LOCKOUT (LP) — The low-pressure lockout will occur if the suction pressure falls below 40 psi for 30 continuous seconds. The compressor will then be deener- gized and the blower will deenergize 15 seconds after the com- pressor is deenergized.

FREEZE PROTECTION 1 LOCKOUT — The freeze pro- tection 1 lockout will occur if the liquid line temperature falls below the set point (15 F or 30 F) for 30 continuous seconds. See DIP switch 2 description in the DIP Switch Settings and Operation section. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized.

FREEZE PROTECTION 2 LOCKOUT — The freeze pro- tection 2 lockout will occur if the air coil temperature falls be- low the set point (32 F) for 30 continuous seconds. See DIP switch 2 description in the DIP Switch Settings and Operation section. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized.

CONDENSATE OVERFLOW 1 LOCKOUT (CO1) — The unit contains one condensate overflow sensor located in the chassis drain pan below the air coil. A condensate lockout will occur if the sensor senses condensate for 30 continuous seconds. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized.

OVER/UNDER VOLTAGE PROTECTION — If the unit control voltage is less than 18-vac or greater than 30-vac the unit will shut down all inputs immediately. Once the voltage

21

Image 21
Contents Contents Safety ConsiderationsGeneral Physical Data 50VS Unit InstallationDRAINa50-8295 Dimension a Water Coil Unit Connection50VSE,F 50VSG,H 50VSM,NDimensional Data A50-829110 x Cabinet A50-829616 x 14 xA50-8298 A50-8300A50-8297 A50-8301 A50-8299Install Cabinet and Riser Framing Rough-In Detail A50-8331.epsSystem Expansion Loops A50-8332Minimum Temperature for LOW Antifreeze Percentages by VolumeType Temperature Protection 10 F 15 F 20 F 25 FWater Quality Guidelines Condition Closed Open Loop and Recirculating WellRECIRCULATING† Chassis Electrical Data 50VS Unit Wire Field Power Supply ConnectionsA50-8352 Typical 50VS Unit Control WiringInstall Hose Kit Wire Field Control ConnectionsRecommended Wire Gage Low Voltage Thermostat Maximum RUN Unit toInstall Return Panel Install Chassis into the CabinetA50-8293 Hose Diameter Bend AllowancePRE-START-UP Install Supply GrilleA50-8302.eps Supply Grille Sizes and ArrangementsDIP Switch Settings and Operation System CheckoutField Selectable Inputs START-UP Standard 24-vac Sequence of OperationOperating Limits Temperature Change Through Heat ExchangerWater Flow GPM Rise Drop Cooling F Heating F 20-26 10-17 Systems at 1.5 gpm per tonService Water Coil MaintenanceTroubleshooting LED1 LED2 LED3 LED4 TroubleshootingII. START-UP START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis