f.Turn thermostat to “OFF” position. A hissing noise indicates proper functioning of the reversing valve.
g.Allow 5 minutes between tests for pressure to equalize before beginning heating test.
h.Adjust the thermostat to the lowest setting. Place the thermostat mode switch in the “HEAT” position.
i.Slowly raise the thermostat to a higher temperature until the compressor activates.
j.Check for warm air delivery within a few minutes after the unit has begun to operate.
k.Refer to Table 9. Check the temperature of both entering and leaving water. If temperature is within range, proceed with the test. If temperature is out- side of the operating range, check refrigerant pressures.
l.Check air temperature rise across the air coil when compressor is operating. Air temperature rise should be between 20 and 30 F.
m.Check for vibration, noise, and water leaks.
6.If unit fails to operate, perform troubleshooting analysis (see troubleshooting section). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to ensure proper diag- nosis and repair of the equipment.
7.When testing is complete, set system to maintain desired comfort level.
NOTE: If performance during any mode appears abnormal refer to the troubleshooting section of this manual. To obtain maximum performance, the air coil should be cleaned before
Table 12 — Temperature Change Through Heat
Exchanger
WATER FLOW GPM | RISE IN | DROP IN | |
COOLING (°F) | HEATING (°F) | ||
| |||
For Closed Loop: Ground |
|
| |
Source or Closed Loop | |||
Systems at 3 gpm per ton |
|
| |
For Open Loop: Ground Water |
|
| |
Systems at 1.5 gpm per ton | |||
|
|
Operating Limits
ENVIRONMENT — Units are designed for indoor installa- tion only. Never install units in areas subject to freezing or where humidity levels could cause cabinet condensation (such as unconditioned spaces subject to 100% outside air).
POWER SUPPLY — A voltage variation of ± 10% of name- plate utilization voltage is acceptable.
STARTING CONDITIONS — Starting conditions vary de- pending upon model number and are based upon the following:
•Conditions in Table 9 are not normal or continuous operat- ing conditions. Minimum/maximum limits are
•Voltage utilization range complies with ARI Standard 110.
•Determination of operating limits is dependent primarily upon three factors:
a.Ambient temperature
b.Return air temperature
c.Water temperature
•When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels to ensure proper unit operation.
Extreme variations in temperature and humidity and/or cor- rosive water or air will adversely affect unit performance, reli- ability, and service life.
Lockout Mode — If the microprocessor board is flashing a system warning and the unit is locked out and not running, the lockout can be cleared from the microprocessor by a mo- mentary shutdown of incoming line voltage
FREEZE PROTECTION 1 LOCKOUT — The freeze pro- tection 1 lockout will occur if the liquid line temperature falls below the set point (15 F or 30 F) for 30 continuous seconds. See DIP switch 2 description in the DIP Switch Settings and Operation section. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized.
FREEZE PROTECTION 2 LOCKOUT — The freeze pro- tection 1 lockout will occur if the air coil temperature falls be- low the set point 32 F for 30 continuous seconds. See DIP switch 2. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized.
CONDENSATE OVERFLOW 1 LOCKOUT (CO1) — The unit contains one condensate overflow sensor located in the chassis drain pan below the air coil. A condensate lockout will occur if the sensor senses condensate for 30 continuous seconds. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized.
OVER/UNDER VOLTAGE PROTECTION — If the unit control voltage is less than
LEAVING WATER TEMPERATURE SENSOR FAIL- URE (LWT) — If the leaving water temperature thermistor fails it will not affect the operation of the unit. This sensor is for monitoring purposes only.
DISCHARGE AIR TEMPERATURE SENSOR FAILURE (DAT) — If the discharge temperature thermistor fails it will not affect the operation of the unit. This sensor is for monitor- ing purposes only.
FREEZE PROTECTION 1 TEMPERATURE SENSOR FAILURE (FP1) — If the freeze protection 1 thermistor fails for 30 continuous seconds an FP1 lockout will occur. The compressor will then be deenergized and the blower will deen- ergize 15 seconds after the compressor is deenergized. The sen- sor must be replaced if this lockout occurs.
FREEZE PROTECTION 2 TEMPERATURE SENSOR FAILURE (FP2) — If the freeze protection 2 thermistor fails for 30 continuous seconds an FP2 lockout will occur. The compressor will then be deenergized and the blower will deenergize 15 seconds after the compressor is deenergized. The sensor must be replaced if this lockout occurs.