Carrier Air Conditioner specifications Example of Temperature Reset Return Fluid Configuration

Page 38

Table 16 — Configuration Mode and Sub-Mode Directory (cont)

SUB-MODE

KEYPAD

ITEM

MARQUEE

NAVIGATOR

ITEM EXPANSION

 

COMMENT

ENTRY

DISPLAY RANGE

DISPLAY RANGE

 

 

 

 

 

 

SLCT

ENTER

CLSP

0 - 5

DUAL SWITCH

COOLING SETPOINT

Default: 0

 

 

 

 

 

DUAL 7 DAY

SELECT

0

= Single

 

 

 

 

DUAL CCN OCC

 

1

= Dual Switch

 

 

 

 

4-20 INPUT

 

2

= Dual 7 Day

 

 

 

 

EXTERNAL POT

 

3

= Dual CCN Occupancy

 

 

 

 

 

 

4

= 4-20 Input

 

 

 

 

 

 

5

= Set Point Potentiometer

 

 

HTSP

0 - 4

0 - 4

HEATING SETPOINT SELECT

Not Supported

 

 

RL.S

ENBL-DSBL

ENBL-DSBL

RAMP LOAD SELECT

Default: DSBL

 

 

CRMP

0.2 - 2.0° F

0.2 - 2.0° F

COOLING RAMP LOADING

Default: 1.0

 

 

(0.1 - 1.1° C)

(0.1 - 1.1° C)

 

 

 

 

 

 

 

 

HRMP

0.2 - 2.0° F

0.2 - 2.0° F

HEATING RAMP LOADING

Not Supported

 

 

(0.1 - 1.1° C)

(0.1 - 1.1° C)

 

 

 

 

 

 

 

 

HCSW

COOL-HEAT

COOL-HEAT

HEAT COOL SELECT

Not Supported

 

 

Z.GN

1.0 - 4.0

1.0 - 4.0

DEADBAND MULTIPLIER

Default: 1.0

Table 17 — Example of Temperature Reset (Return Fluid) Configuration

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM EXPANSION

COMMENT

ENTRY

 

 

 

 

 

RSET

ENTER

CRST

0

COOLING RESET TYPE

0 = No reset

 

 

 

 

1 = 4 to 20 mA input

 

 

 

 

 

 

 

 

 

 

2 = Outdoor Air Temp

 

 

 

 

 

3 = Return Fluid

 

 

 

 

 

4 = Space Temperature

 

ENTER

 

0

 

Scrolling stops

 

 

 

 

 

ENTER

 

0

 

Value flashes

 

 

 

 

 

 

 

3

 

Select 3

 

ENTER

 

3

 

Change accepted

 

 

 

 

 

ENTER

CRST

3

 

Item/Value/Units scrolls again

 

 

 

 

 

CRT1

125

NO COOL RESET TEMP

Range: 0° to 125 F

 

ENTER

 

125

 

Scrolling stops

 

 

 

 

 

ENTER

 

125

 

Value flashes

 

 

 

 

 

 

 

10

 

Select 10

 

ENTER

 

10

 

Change accepted

 

 

 

 

 

ESCAPE

CRT1

10

 

Item/Value/Units scrolls again

 

 

 

 

 

CRT2

0

FULL COOL RESET TEMP

Range: 0° to 125 F

 

ENTER

 

0

 

Scrolling stops

 

 

 

 

 

ENTER

 

0

 

Value flashes

 

 

 

 

 

 

 

2

 

Select 2

 

ENTER

 

2

 

Change accepted

 

 

 

 

 

ESCAPE

CRT2

2

 

Item/Value/Units scrolls again

 

 

 

 

 

DGRC

0

DEGREES COOL RESET

Range: –30 to 30 F

 

ENTER

 

0

 

Scrolling stops

 

 

 

 

 

ENTER

 

0

 

Value flashes

 

 

 

 

 

 

 

8

 

Select 8

 

ENTER

 

8

 

Change accepted

 

 

 

 

 

ESCAPE

DGRC

8

 

Item/Value/Units scrolls again

NOTE: The example above shows how to configure the chiller for temperature reset based on chiller return fluid. The chiller will be configured for no reset at a cooler T (EWT-LWT) of 10 F (5.6 C) and a full reset of 8 F (4.4 C) at a cooler T of 2 F (1.1 C).

38

Image 38
Contents Safety Considerations ContentsIntroduction ContentsGeneral Unit Sizes and Modular Combinations 30GUN,R Major System ComponentsUnit Sizes and Modular Combinations 30GTN,R Unit Nominal Section a Section B 30GTN,R Tons Unit 30GTN,RThermistor Designations Control Module CommunicationCarrier Comfort Network CCN Interface Status Switches Output RelayPage 24 V Control Schematic, Unit Sizes 24 V Control Schematic, Unit Sizes 080-110, 230B-315B CCN LEN Data Communication Port Main Base Board Operating Data 040-110 130-210Thermistor T3 and T4 Locations Compressor Thermistor Locations T7 and T8 Belden 8205 Regular Wiring Plenum Wiring Alpha 1895 AmericanManufacturer Columbia D6451 Manhattan M13402 M64430 Quabik 6130Compressor Protection Control System Module Sizes Stepper Motor 12 VDC CEPL130351 30GUN,R Part Load Data Percent Displacement, Standard UnitsDisplacement Compressors Approx110, 290B 255A 60 Hz390B 60 Hz 330A/B360B 50 Hz 390B 50 HzB1† A1,B1 A1†,A2,B1 A1*,B1†,B2 Unloaded compressor Two unloaders, both unloaded 170, 270A 190, 290A, 360A/BA1*,B1*,B2 Required Hardware for Additional Unloaders 150-210Head Pressure Control PumpoutPower FAN Arrangement FAN Relay Normal ControlService Test See Both main power Scrolling Marquee DisplayModes GEN.O TestStrt Run Status Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry View VersOuts Service Test Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry Test Set Point Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectoryPressure Mode and Sub-Mode Directory SUB-MODE Keypad Range Item Expansion Comment Entry GEN.I Inputs Mode and Sub-Mode DirectoryReading and Changing Chilled Fluid Set Point Crct SUB-MODE Keypad Range Item Expansion Comment Entry GEN.O Outputs Mode and Sub-Mode Directory Configuration Mode and Sub-Mode Directory CCN OPT1OPT2 EMM240 RsetExample of Temperature Reset Return Fluid Configuration SUB-MODE Keypad Display Item Expansion Comment Entry RsetSUB-MODE Keypad Entry Display Item Expansion Comment Rset Example of Configuring Dual Chiller Control Master ChillerExample of Configuring Dual Chiller Control Slave Chiller SUB-MODE Keypad Display Item Expansion Comment Entry OPT2 Example of Compressor Lead/Lag ConfigurationTime Clock Mode and Sub-Mode Directory SUB-MODE Keypad Entry Item Expansion Comment Range TimeSetting an Occupied Time Schedule Operating Mode and Sub-Mode DirectoryMode no Item Expansion Description Operating ModesAlarms Mode and Sub-Mode Directory Example of Reading and Clearing AlarmsConfiguration Configuring Temperature ResetMode Keypad SUB-MODE Entry ExpansionRED LED Entry Expansion Configuration Configuring Demand Limit DLS2Troubleshooting To 20 mA Demand LimitingPage Alarm and Alert Codes T051FSM By Control Method Cause Code Alert GENERATED?EWT LCWT170 T153T155 T173T205 T203T204 T206Oil Charge ServiceElectronic Components Compressor OIL RequiredCooler Thermistor Locations Plugs Components for Part Number PluggingCondenser Coils Cooler Head Bolt Tightening Sequence Typical Tube SheetCondenser Fan Adjustment Hz Low Noise Fan Option Units Dimension FAN TypePrinted Circuit Board Connector Refrigerant Feed Components Each circuit hasThermistors Temperature Sensors Drop a 5K Thermistor Temperature F vs Resistance/VoltageDrop B 5K Thermistor Temperature C vs Resistance/Voltage Temp Voltage Resistance Drop 200,510 30GTN,R Units Pressure Switch Settings Psig kPaSwitch Cutout CUT-IN 30GUN,R UnitsPRE-START-UP System CheckMaximum Ambient Temperature 125 Temperature Limits for Standard UnitsTemperature START-UP and OperationNominal and Minimum Cooler Fluid Flow Rates Field WiringRefrigerant Circuit Hgbps ALMCWP Energy Management Module EMM Wiring Compressor Expansion Board CXB Accessory Wiring Description Status Default Units Point Unit Configuration SettingsOPTIONS1 Options Configuration Description Status Default PointAppendix a CCN Tables OPTIONS2 Options ConfigurationAlarmdef Alarm Definition Table Resetcon Temperature Reset and Demand Limit Brodefs Broadcast POC Definition TableCircadio Circuit a Discrete Parameters Aunit General Unit ParametersCircaan Circuit a Analog Parameters Description Status Units Point ForceableCircban Circuit B Analog Parameters Circbdio Circuit B Discrete ParametersOptions Unit Parameters Strthour Description Status Units PointDescription Status Units Point Defaults CurrmodsDescription Status Point CSM/FSM Equipment Table Type 621H, BlockLine Description Point Appendix B Fluid Drop Pressure Curves Cooler Fluid Pressure Drop Curves 30GUN,GUR040-110Cooler Pressure Drop KEY Appendix B Fluid Drop Pressure CurvesCooler Fluid Pressure Drop Curves 30GUN,GUR130-210 Appendix B Fluid Drop Pressure Curves Cooler Fluid Pressure Drop Curves 30GUN,GUR230B-315B Cooler Fluid Pressure Drop Curves 30GTN,GTR040-110 Cooler Fluid Pressure Drop Curves 30GTN,GTR130-210 Appendix B Fluid Drop Pressure Curves Module B 30GTN,GTR230,245 Module B 30GTN,GTR255,290,315 Service Training Call for Free CatalogEquipment Chiller Model no START-UP Checklist for Comfortlink Chiller SystemsRemove and use for job file Preliminary Information Preliminary Equipment Check Check box if complete System Fluid Volume in Loop Type System UnitStart-UpUnit Start-Up Ccnb Description Status Units Value CtrlCcna BaudSlct Heating Cooling Setpoint Select CND.P RMT.A All Units