Carrier Air Conditioner specifications Thermistors Temperature Sensors

Page 59

Thermistors — Electronic control uses 4 to 10 ther- mistors to sense temperatures used to control the operation of chiller.

Thermistors T1-T9 vary in their temperature vs resistance and voltage drop performance. Thermistor T10 is a 10 kin- put channel and has a different set of temperature vs resistance and voltage drop performance. Resistances at various tempera- tures are listed in Tables 32A-33B.

LOCATION — General locations of thermistor sensors are shown in Fig. 7-10. See Table 2 for pin connection points.

Sensor T2 is installed directly in the fluid circuit. Relieve all pressure or drain fluid before removing.

REPLACING THERMISTOR T2

1. Remove and discard original sensor and coupling. Do

not disassemble new coupling. Install assembly as

received. See Fig. 32.

Tables 32A-33B. To check thermistor accuracy, mea- sure temperature at probe location with an accurate thermocouple-type temperature measuring instru- ment. Insulate thermocouple to avoid ambient temper- atures from influencing reading. Temperature measured by thermocouple and temperature deter- mined from thermistor voltage reading should be close, ± 5° F (3° C) if care was taken in applying ther- mocouple and taking readings.

2.If a more accurate check is required, unit must be shut down and thermistor removed and checked at a known temperature (freezing point or boiling point of water) us- ing either voltage drop measured across thermistor at the J8 or J5 terminals, by determining the resistance with chiller shut down and thermistor disconnected from J8 or J5. Compare the values determined with the value read by the control in the Temperatures mode using the Marquee display.

2. Apply pipe sealant to 1/4-in. NPT threads on replacement

coupling, and install in place of original. Do not use the

packing nut to tighten coupling. Damage to ferrules will

result.

3. Thermistor T2 (entering fluid temperature) should not be

touching an internal refrigerant tube, but should be close

enough to sense a freeze condition. Recommended dis-

tance is 1/8 in. (3.2 mm) from cooler tube. Tighten pack-

ing nut finger tight to position ferrules, then tighten 11/4

turns more using a back-up wrench. Ferrules are now at-

tached to the sensor, which can be withdrawn from cou-

pling for service.

REPLACING THERMISTORS T1, T5, T6, T7, AND T8 — Add a small amount of thermal conductive grease to thermistor well. Thermistors are friction-fit thermistors, which must be slipped into wells located in the cooler leaving fluid nozzle for T1, in the cooler head for T5 and T6 (EXV units only), and in the compressor pump end for T7 and T8 (EXV units only).

THERMISTORS T3 AND T4 — These thermistors are located on header end of condenser coil. They are clamped on a return bend.

THERMISTOR/TEMPERATURE SENSOR CHECK — A high quality digital volt-ohmmeter is required to perform this check.

1.Connect the digital voltmeter across the appropriate thermistor terminals at the J8 terminal strip on the Main Base Board for thermistors T1-T6, T9, T10; or the J5 terminal strip on the EXV Board for thermistors T7 and T8 (see Fig. 33). Using the voltage reading

obtained, read the sensor temperature from

MAIN BASE BOARD

 

1

1

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

4

4

 

 

 

 

 

 

 

 

 

5

5

BLU TB5

5

 

6

6

BLU TB5

6

 

7

7

PNK TB5 7

 

8

8

PNK

TB5

8

 

 

 

 

9

9

 

 

 

 

 

 

 

 

 

10

10

 

 

 

 

 

 

T2

 

 

11

1

2

 

 

 

 

 

 

 

12

2

 

 

 

 

 

 

 

 

J8

13

3

1

T1

 

 

 

 

 

 

14

4

 

 

 

 

 

 

 

 

 

15

1

4

T4

 

 

 

 

 

 

 

16

2

 

 

 

 

 

 

 

 

 

17

3

 

 

 

 

 

 

T6

 

 

18

4

6

 

 

 

 

 

 

 

19

5

 

 

 

 

 

 

 

 

 

20

6

 

 

 

 

 

 

T3

 

 

21

1

3

 

 

 

 

 

 

222

233

24

4

5

T5

 

 

 

25

5

 

26

6

 

REMOTE SPACE TEMP

(ACCESSORY)

T10

T9

OUTDOOR-AIR TEMP

(ACCESSORY) OR DUAL CHILLER LWT

COOLER ENTERING FLUID TEMP

COOLER LEAVING FLUID TEMP

SATURATED CONDENSING TEMP- CIRCUIT B

SATURATED

SUCTION TEMP-

CIRCUIT B*

SATURATED CONDENSING TEMP- CIRCUIT A

SATURATED

SUCTION TEMP-

CIRCUIT A*

X = T1,T5,T6 = 3(76)

T7,T8 = 4(102)

FLUID-SIDE TEMPERATURE SENSOR (T1) AND

REFRIGERANT TEMPERATURE SENSOR (T5, T6, T7, T8)

FLUID-SIDE TEMPERATURE SENSOR (T2) NOTE: Dimensions in ( ) are in millimeters.

Fig. 32 — Thermistors (Temperature Sensors)

T1-T6, T9, T10 THERMISTORS

EXV BOARD

J5

12

11

10

9

8

7

6

5

4

3

2

1

12 11 10 9

T7

7

8

T8

CKTA* CKTB*

COMPRESSOR RETURN GAS TEMP

T7, T8 THERMISTORS

LEGEND

LWT — Leaving Fluid Temperature

*Not used on units with TXV (Thermostatic Expansion Valve) FIOP (Factory-Installed Option).

Fig. 33 — Thermistor Connections to J5 and J8

Processor Boards

59

Image 59
Contents Contents Safety ConsiderationsIntroduction ContentsGeneral Unit Nominal Section a Section B 30GTN,R Tons Unit 30GTN,R Major System ComponentsUnit Sizes and Modular Combinations 30GTN,R Unit Sizes and Modular Combinations 30GUN,RThermistor Designations Control Module CommunicationCarrier Comfort Network CCN Interface Output Relay Status SwitchesPage 24 V Control Schematic, Unit Sizes 24 V Control Schematic, Unit Sizes 080-110, 230B-315B CCN LEN Data Communication Port Main Base Board 040-110 130-210 Operating DataThermistor T3 and T4 Locations Compressor Thermistor Locations T7 and T8 Columbia D6451 Manhattan M13402 M64430 Quabik 6130 Regular Wiring Plenum Wiring Alpha 1895 AmericanManufacturer Belden 8205Compressor Protection Control System Module Sizes Stepper Motor 12 VDC CEPL130351 Approx Part Load Data Percent Displacement, Standard UnitsDisplacement Compressors 30GUN,R255A 60 Hz 110, 290B390B 50 Hz 330A/B360B 50 Hz 390B 60 HzB1† A1,B1 A1†,A2,B1 A1*,B1†,B2 Unloaded compressor Two unloaders, both unloaded 190, 290A, 360A/B 170, 270AA1*,B1*,B2 150-210 Required Hardware for Additional UnloadersPumpout Head Pressure ControlFAN Arrangement FAN Relay Normal Control PowerScrolling Marquee Display Service Test See Both main powerGEN.O Test ModesVers Run Status Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry View StrtOuts Service Test Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry Test Set Point Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectoryPressure Mode and Sub-Mode Directory Crct Inputs Mode and Sub-Mode DirectoryReading and Changing Chilled Fluid Set Point SUB-MODE Keypad Range Item Expansion Comment Entry GEN.ISUB-MODE Keypad Range Item Expansion Comment Entry GEN.O Outputs Mode and Sub-Mode DirectoryConfiguration Mode and Sub-Mode Directory EMM OPT1OPT2 CCNRset 240SUB-MODE Keypad Display Item Expansion Comment Entry Rset Example of Temperature Reset Return Fluid ConfigurationSUB-MODE Keypad Entry Display Item Expansion Comment Rset Example of Configuring Dual Chiller Control Master ChillerExample of Configuring Dual Chiller Control Slave Chiller SUB-MODE Keypad Entry Item Expansion Comment Range Time Example of Compressor Lead/Lag ConfigurationTime Clock Mode and Sub-Mode Directory SUB-MODE Keypad Display Item Expansion Comment Entry OPT2Operating Mode and Sub-Mode Directory Setting an Occupied Time ScheduleOperating Modes Mode no Item Expansion DescriptionExample of Reading and Clearing Alarms Alarms Mode and Sub-Mode DirectoryEntry Expansion Configuring Temperature ResetMode Keypad SUB-MODE ConfigurationRED LED Entry Expansion Configuration DLS2 Configuring Demand LimitTo 20 mA Demand Limiting TroubleshootingPage T051 Alarm and Alert CodesLCW By Control Method Cause Code Alert GENERATED?EWT FSMT173 T153T155 T170T206 T203T204 T205Compressor OIL Required ServiceElectronic Components Oil ChargeCooler Thermistor Locations Components for Part Number Plugging PlugsCooler Head Bolt Tightening Sequence Typical Tube Sheet Condenser CoilsDimension FAN Type Condenser Fan Adjustment Hz Low Noise Fan Option UnitsRefrigerant Feed Components Each circuit has Printed Circuit Board ConnectorThermistors Temperature Sensors Drop a 5K Thermistor Temperature F vs Resistance/VoltageDrop B 5K Thermistor Temperature C vs Resistance/Voltage Temp Voltage Resistance Drop 200,510 30GUN,R Units Pressure Switch Settings Psig kPaSwitch Cutout CUT-IN 30GTN,R UnitsSystem Check PRE-START-UPSTART-UP and Operation Temperature Limits for Standard UnitsTemperature Maximum Ambient Temperature 125Nominal and Minimum Cooler Fluid Flow Rates Field WiringRefrigerant Circuit Hgbps ALMCWP Energy Management Module EMM Wiring Compressor Expansion Board CXB Accessory Wiring Description Status Default Point Unit Configuration SettingsOPTIONS1 Options Configuration Description Status Default Units PointAppendix a CCN Tables OPTIONS2 Options ConfigurationAlarmdef Alarm Definition Table Brodefs Broadcast POC Definition Table Resetcon Temperature Reset and Demand LimitDescription Status Units Point Forceable Aunit General Unit ParametersCircaan Circuit a Analog Parameters Circadio Circuit a Discrete ParametersCircbdio Circuit B Discrete Parameters Circban Circuit B Analog ParametersOptions Unit Parameters Description Status Units Point StrthourCurrmods Description Status Units Point DefaultsDescription Status Point CSM/FSM Equipment Table Type 621H, BlockLine Description Point Cooler Fluid Pressure Drop Curves 30GUN,GUR040-110 Appendix B Fluid Drop Pressure CurvesCooler Pressure Drop KEY Appendix B Fluid Drop Pressure CurvesCooler Fluid Pressure Drop Curves 30GUN,GUR130-210 Appendix B Fluid Drop Pressure Curves Cooler Fluid Pressure Drop Curves 30GUN,GUR230B-315B Cooler Fluid Pressure Drop Curves 30GTN,GTR040-110 Cooler Fluid Pressure Drop Curves 30GTN,GTR130-210 Appendix B Fluid Drop Pressure Curves Module B 30GTN,GTR230,245 Module B 30GTN,GTR255,290,315 Call for Free Catalog Service TrainingEquipment Chiller Model no START-UP Checklist for Comfortlink Chiller SystemsRemove and use for job file Preliminary Information Preliminary Equipment Check Check box if complete UnitStart-Up System Fluid Volume in Loop Type SystemUnit Start-Up Baud Description Status Units Value CtrlCcna CcnbSlct Heating Cooling Setpoint Select CND.P RMT.A All Units

Air Conditioner specifications

Carrier Air Conditioners have long been synonymous with reliability and innovation in climate control. Founded by Willis Carrier, the inventor of modern air conditioning, the brand has continuously set industry standards through state-of-the-art technologies and features designed to enhance indoor comfort.

One of the standout features of Carrier air conditioners is their energy efficiency. Many models are equipped with advanced inverter technology, allowing the compressor to adjust its speed based on the cooling demand. This results in decreased energy consumption, which not only reduces utility bills but also lessens the environmental impact. Recognizing the importance of sustainable practices, Carrier has integrated eco-friendly refrigerants into their systems, further promoting energy-efficient operations.

Carrier also emphasizes user comfort through its variable speed systems. These systems maintain consistent temperatures while minimizing temperature fluctuations, ensuring an even distribution of cool air throughout the home. Additionally, many Carrier models come with advanced air filtration systems, designed to capture allergens, dust, and other particulates, thereby improving indoor air quality.

The smart technology featured in Carrier air conditioners plays a key role in modern convenience. Many units are compatible with smart home systems, allowing users to control settings remotely via smartphones or voice-activated devices. With features like programmable thermostats, users can easily set cooling schedules to match their lifestyle, ensuring comfort while maximizing energy savings.

Durability and noise reduction are also central to the Carrier brand. Many models are designed with sound-dampening features, making them some of the quietest units on the market. This is particularly advantageous for residential use, where noise can disrupt daily activities and sleep.

In terms of design, Carrier air conditioners come in various styles and capacities to suit a wide range of spaces, from compact apartment units to large central systems for sprawling homes. Their extensive warranty and service offerings further reinforce Carrier’s commitment to customer satisfaction.

In conclusion, Carrier air conditioners represent a perfect blend of cutting-edge technology, energy efficiency, and user comfort. Their emphasis on sustainability and smart features positions them as a leading choice for homeowners seeking reliable and innovative climate control solutions. Whether for cooling a small room or an entire house, Carrier remains a trusted name in air conditioning.