| ALARM/ | ALARM | | WHY WAS THIS | ACTION TAKEN | RESET | PROBABLE |
| ALERT | OR | DESCRIPTION | ALARM |
| BY CONTROL | METHOD | CAUSE |
| CODE | ALERT | | GENERATED? |
| | | | |
| | | | | | | |
| T051 | Alert | Circuit A, Compressor 1 | Compressor feedback signal | Circuit A shut down. | Manual | High-pressure or loss-of- |
| | | Failure | does not match relay state | | | charge switch open, faulty |
| | | | | | | control relay or CPCS board, |
| | | | | | | loss of condenser air, liquid |
| | | | | | | valve closed, operation |
| | | | | | | beyond capability. |
| T052 | Alert | Circuit A, Compressor 2 | Compressor feedback signal | Circuit A shut down. Circuit | Manual | High-pressure switch open, |
| | | Failure | does not match relay state | restarted in 1 minute. Com- | | faulty control relay or CPCS |
| | | | | pressor A2 not used until | | board, loss of condenser air, |
| | | | | alarm is reset. | | liquid valve closed, opera- |
| | | | | | | tion beyond capability. |
| T053 | Alert | Circuit A, Compressor 3 | Compressor feedback signal | Circuit A shut down. Circuit | Manual | High-pressure switch open, |
| | | Failure | does not match relay state | restarted in 1 minute. Com- | | faulty control relay or CPCS |
| | | | | pressor A3 not used until | | board, loss of condenser air, |
| | | | | alarm is reset. | | liquid valve closed, opera- |
| | | | | | | tion beyond capability. |
| T054 | Alert | Circuit A, Compressor 4 | Compressor feedback signal | Circuit A shut down. Circuit | Manual | High-pressure switch open, |
| | | Failure | does not match relay state | restarted in 1 minute. Com- | | faulty control relay or CPCS |
| | | | | pressor A4 not used until | | board, loss of condenser air, |
| | | | | alarm is reset. | | liquid valve closed, opera- |
| | | | | | | tion beyond capability. |
| T055 | Alert | Circuit B, Compressor 1 | Compressor feedback signal | Circuit B shut down. | Manual | High-pressure or loss-of- |
| | | Failure | does not match relay state | | | charge switch open, faulty |
| | | | | | | control relay or CPCS board, |
| | | | | | | loss of condenser air, liquid |
| | | | | | | valve closed, operation |
| | | | | | | beyond capability. |
| T056 | Alert | Circuit B, Compressor 2 | Compressor feedback signal | Circuit B shut down. Circuit | Manual | High-pressure switch open, |
| | | Failure | does not match relay state | restarted in 1 minute. Com- | | faulty control relay or CPCS |
| | | | | pressor B2 not used until | | board, loss of condenser air, |
| | | | | alarm is reset. | | liquid valve closed, opera- |
| | | | | | | tion beyond capability. |
| T057 | Alert | Circuit B, Compressor 3 | Compressor feedback signal | Circuit B shut down. Circuit | Manual | High-pressure switch open, |
| | | Failure | does not match relay state | restarted in 1 minute. Com- | | faulty control relay or CPCS |
| | | | | pressor B3 not used until | | board, loss of condenser air, |
| | | | | alarm is reset. | | liquid valve closed, opera- |
| | | | | | | tion beyond capability. |
| A060 | Alarm | Cooler Leaving Fluid | Thermistor outside range of | Chiller shutdown after | Automatic | Thermistor failure, damaged |
| | | Thermistor Failure (T1) | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| A061 | Alarm | Cooler Entering Fluid | Thermistor outside range of | Chiller shutdown after | Automatic | Thermistor failure, damaged |
| | | Thermistor Failure (T2) | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| T064 | Alert | Circuit A Saturated Con- | Thermistor outside range of | Circuit A shutdown after | Automatic | Thermistor failure, damaged |
| | | densing Thermistor Failure | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| | | (T3) | | | | |
| T065 | Alert | Circuit B Saturated Con- | Thermistor outside range of | Circuit B shutdown after | Automatic | Thermistor failure, damaged |
| | | densing Thermistor Failure | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| | | (T4) | | | | |
| T066 | Alert | Circuit A Saturated Suction | Thermistor outside range of | Circuit A shutdown after | Automatic | Thermistor failure, damaged |
| | | Thermistor Failure (T5) | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| | | | | (EXV only) | | |
| T067 | Alert | Circuit B Saturated Suction | Thermistor outside range of | Circuit B shutdown after | Automatic | Thermistor failure, damaged |
| | | Thermistor Failure (T6) | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| | | | | (EXV only). | | |
| T068 | Alert | Compressor A1 Suction | Thermistor outside range of | Circuit A shutdown after | Automatic | Thermistor failure, damaged |
| | | Gas Thermistor Failure (T7) | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| | | | | (EXV only). | | |
| T069 | Alert | Compressor B1 Suction | Thermistor outside range of | Circuit B shutdown after | Automatic | Thermistor failure, damaged |
| | | Gas Thermistor Failure (T8) | –40 to 245 F (–40 to 118 C) | pumpdown complete. | | cable/wire or wiring error. |
| | | | | (EXV only). | | |
| | | | | | | |
| T073 | Alert | Outside Air Thermistor | Thermistor outside range of | Temperature reset disabled. | Automatic | Thermistor failure, damaged |
| | | Failure (T9) | –40 to 245 F (–40 to 118 C) | Chiller runs under normal | | cable/wire or wiring error. |
| | | | | control/set points. | | |
| T074 | Alert | Space Temperature | Thermistor outside range of | Temperature reset disabled. | Automatic | Thermistor failure, damaged |
| | | Thermistor Failure (T10) | –40 to 245 F (–40 to 118 C) | Chiller runs under normal | | cable/wire or wiring error. |
| | | | | control/set points. | | |
| | | | | | | |
| T077 | Alert | Circuit A Saturated | Saturated suction is | Circuit A shutdown after | Automatic | Faulty expansion valve or |
| | | Suction Temperature | greater than leaving fluid | pumpdown complete. | | EXV board, faulty cooler suc- |
| | | exceeds Cooler Leaving | temperature for more than | | | tion thermistor (T5) or leav- |
| | | Fluid Temperature | 5 minutes | | | ing fluid thermistor (T1). |
| T078 | Alert | Circuit B Saturated | Saturated suction is | Circuit B shutdown after | Automatic | Faulty expansion valve or |
| | | Suction Temperature | greater than leaving fluid | pumpdown complete | | EXV board, faulty cooler suc- |
| | | exceeds Cooler Leaving | temperature for more than | | | tion thermistor (T6) or leav- |
| | | Fluid Temperature | 5 minutes | | | ing fluid thermistor (T1). |
| T079 | Alert | Lead/Lag Thermistor Failure | Thermistor outside range of | Lead/lag algorithm runs | Automatic | Dual chiller LWT thermistor |
| | | | –40 to 245 F (–40 to 118 C) | using Master LWT sensor | | failure, damaged cable/wire |
| | | | | Master is lead chiller. | | or wiring error. |