Demand Limit — Demand Limit is a feature that allows the unit capacity to be limited during periods of peak energy usage. There are 3 types of demand limiting that can be config- ured. The first type is through 2-stage switch control, which will reduce the maximum capacity to 2 user-configurable per- centages. The second type is by 4 to 20 mA signal input which will reduce the maximum capacity linearly between 100% at a 4 mA input signal (no reduction) down to the user-configurable level at a 20 mA input signal. The third type uses the CNN Loadshed module and has the ability to limit the current operat- ing capacity to maximum and further reduce the capacity if required.

NOTE: The 2-stage switch control and 4 to 20 mA input signal types of demand limiting require the Energy Management Module (EMM).

To use Demand Limit, select the type of demand limiting to use. Then configure the Demand Limit set points based on the type selected.

DEMAND LIMIT (2-Stage Switch Controlled) — To con- figure Demand Limit for 2-stage switch control set the Demand Limit Select (DMDC) to 1. Then configure the 2 De- mand Limit Switch points (DLS1 and DLS2) to the desired ca- pacity limit. See Table 28. Capacity steps are controlled by 2 relay switch inputs field wired to TB6 as shown in Fig. 2-4.

For Demand Limit by 2-stage switch control, closing the first stage demand limit contact will put the unit on the first de- mand limit level. The unit will not exceed the percentage of ca- pacity entered as Demand Limit Switch 1 set point. Closing contacts on the second demand limit switch prevents the unit from exceeding the capacity entered as Demand Limit Switch

2 set point. The demand limit stage that is set to the lowest de- mand takes priority if both demand limit inputs are closed. If the demand limit percentage does not match unit staging, the unit will limit capacity to the closest capacity stage.

To disable demand limit configure the DMDC to 0. See Table 28.

EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA Controlled) — To configure Demand Limit for 4 to 20 mA control set the Demand Limit Select (DMDC) to 2. Then configure the Demand Limit at 20 mA (DM20) to the maximum loadshed value desired. The control will reduce al- lowable capacity to this level for the 20 mA signal. See Table 28 and Fig. 23.

DEMAND LIMIT (CCN Loadshed Controlled) — To con- figure Demand Limit for CCN Loadshed control set the De- mand Limit Select (DMDC) to 3. Then configure the Loadshed Group Number (SHNM), Loadshed Demand Delta (SHDL), and Maximum Loadshed Time (SHTM). See Table 28.

The Loadshed Group number is established by the CCN system designer. The MBB will respond to a Redline com- mand from the Loadshed control. When the Redline command is received, the current stage of capacity is set to the maximum stages available. Should the loadshed control send a Loadshed command, the MBB will reduce the current stages by the value entered for Loadshed Demand delta. The Maximum Loadshed Time defines the maximum length of time that a loadshed con- dition is allowed to exist. The control will disable the Redline/ Loadshed command if no Cancel command has been received within the configured maximum loadshed time limit.

Table 28 — Configuring Demand Limit

MODE

KEYPAD

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM EXPANSION

COMMENT

ENTRY

ENTRY

 

 

 

 

 

 

CONFIGURATION

ENTER

DISP

ENTER

TEST

ON/OFF

Test Display LEDs

 

 

 

 

 

 

 

UNIT

ENTER

TYPE

X

Unit Type

 

 

 

 

 

 

 

OPT1

ENTER

FLUD

X

Cooler Fluid

 

 

 

 

 

 

 

OPT2

ENTER

CTRL

X

Control Method

 

 

 

 

 

 

 

RSET

ENTER

CRST

X

Cooling Reset Type

 

 

 

 

 

 

 

 

 

CRT1

XXX.X °F

No Cool Reset Temperature

 

 

 

 

 

CRT2

XXX.X °F

Full Cool Reset Temperature

 

 

 

 

 

DGRC

XX.X F

Degrees Cool Reset

 

 

 

 

 

 

 

 

Default: 0

 

 

 

 

 

 

 

0 = None

 

 

 

 

DMDC

X

Demand Limit Select

1 = Switch

 

 

 

 

 

 

 

2 = 4 to 20 mA Input

 

 

 

 

 

 

 

3 = CCN Loadshed

 

 

 

 

DM20

XXX %

Demand Limit at 20 mA

Default: 100%

 

 

 

 

Range: 0 to 100

 

 

 

 

 

 

 

 

 

 

 

 

 

Loadshed Group

Default: 0

 

 

 

 

SHNM

XXX

Range: 0 to 99

 

 

 

 

Number

 

 

 

 

 

 

 

 

 

 

 

 

 

Loadshed Demand

Default: 0%

 

 

 

 

SHDL

XXX%

Range: 0 to 60%

 

 

 

 

Delta

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Loadshed

Default: 60 min.

 

 

 

 

SHTM

XXX MIN

Range: 0 to 120 min.

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

 

Demand Limit

Default: 80%

 

 

 

 

DLS1

XXX %

Range: 0 to 100%

 

 

 

 

Switch 1

 

 

 

 

 

 

 

 

 

 

 

 

 

Demand Limit

Default: 50%

 

 

 

 

DLS2

XXX%

Range: 0 to 100%

 

 

 

 

Switch 2

 

 

 

 

 

 

 

NOTE: Heating reset values skipped in this example.

46

Image 46
Contents Safety Considerations ContentsGeneral ContentsIntroduction Unit Sizes and Modular Combinations 30GUN,R Major System ComponentsUnit Sizes and Modular Combinations 30GTN,R Unit Nominal Section a Section B 30GTN,R Tons Unit 30GTN,RCarrier Comfort Network CCN Interface Control Module CommunicationThermistor Designations Status Switches Output RelayPage 24 V Control Schematic, Unit Sizes 24 V Control Schematic, Unit Sizes 080-110, 230B-315B CCN LEN Data Communication Port Main Base Board Operating Data 040-110 130-210Thermistor T3 and T4 Locations Compressor Thermistor Locations T7 and T8 Belden 8205 Regular Wiring Plenum Wiring Alpha 1895 AmericanManufacturer Columbia D6451 Manhattan M13402 M64430 Quabik 6130Compressor Protection Control System Module Sizes Stepper Motor 12 VDC CEPL130351 30GUN,R Part Load Data Percent Displacement, Standard UnitsDisplacement Compressors Approx110, 290B 255A 60 Hz390B 60 Hz 330A/B360B 50 Hz 390B 50 HzB1† A1,B1 A1†,A2,B1 A1*,B1†,B2 Unloaded compressor Two unloaders, both unloaded 170, 270A 190, 290A, 360A/BA1*,B1*,B2 Required Hardware for Additional Unloaders 150-210Head Pressure Control PumpoutPower FAN Arrangement FAN Relay Normal ControlService Test See Both main power Scrolling Marquee DisplayModes GEN.O TestStrt Run Status Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry View VersSUB-MODE Keypad Range Item Expansion Comment Entry Test Service Test Mode and Sub-Mode DirectoryOuts Pressure Mode and Sub-Mode Directory Temperature Mode and Sub-Mode DirectorySet Point Mode and Sub-Mode Directory SUB-MODE Keypad Range Item Expansion Comment Entry GEN.I Inputs Mode and Sub-Mode DirectoryReading and Changing Chilled Fluid Set Point CrctConfiguration Mode and Sub-Mode Directory Outputs Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry GEN.O CCN OPT1OPT2 EMM240 RsetExample of Temperature Reset Return Fluid Configuration SUB-MODE Keypad Display Item Expansion Comment Entry RsetExample of Configuring Dual Chiller Control Slave Chiller Example of Configuring Dual Chiller Control Master ChillerSUB-MODE Keypad Entry Display Item Expansion Comment Rset SUB-MODE Keypad Display Item Expansion Comment Entry OPT2 Example of Compressor Lead/Lag ConfigurationTime Clock Mode and Sub-Mode Directory SUB-MODE Keypad Entry Item Expansion Comment Range TimeSetting an Occupied Time Schedule Operating Mode and Sub-Mode DirectoryMode no Item Expansion Description Operating ModesAlarms Mode and Sub-Mode Directory Example of Reading and Clearing AlarmsConfiguration Configuring Temperature ResetMode Keypad SUB-MODE Entry ExpansionRED LED Entry Expansion Configuration Configuring Demand Limit DLS2Troubleshooting To 20 mA Demand LimitingPage Alarm and Alert Codes T051FSM By Control Method Cause Code Alert GENERATED?EWT LCWT170 T153T155 T173T205 T203T204 T206Oil Charge ServiceElectronic Components Compressor OIL RequiredCooler Thermistor Locations Plugs Components for Part Number PluggingCondenser Coils Cooler Head Bolt Tightening Sequence Typical Tube SheetCondenser Fan Adjustment Hz Low Noise Fan Option Units Dimension FAN TypePrinted Circuit Board Connector Refrigerant Feed Components Each circuit hasThermistors Temperature Sensors Drop B 5K Thermistor Temperature F vs Resistance/VoltageDrop a 5K Thermistor Temperature C vs Resistance/Voltage Temp Voltage Resistance Drop 200,510 30GTN,R Units Pressure Switch Settings Psig kPaSwitch Cutout CUT-IN 30GUN,R UnitsPRE-START-UP System CheckMaximum Ambient Temperature 125 Temperature Limits for Standard UnitsTemperature START-UP and OperationRefrigerant Circuit Field WiringNominal and Minimum Cooler Fluid Flow Rates CWP ALMHgbps Energy Management Module EMM Wiring Compressor Expansion Board CXB Accessory Wiring Description Status Default Units Point Unit Configuration SettingsOPTIONS1 Options Configuration Description Status Default PointAlarmdef Alarm Definition Table OPTIONS2 Options ConfigurationAppendix a CCN Tables Resetcon Temperature Reset and Demand Limit Brodefs Broadcast POC Definition TableCircadio Circuit a Discrete Parameters Aunit General Unit ParametersCircaan Circuit a Analog Parameters Description Status Units Point ForceableCircban Circuit B Analog Parameters Circbdio Circuit B Discrete ParametersOptions Unit Parameters Strthour Description Status Units PointDescription Status Units Point Defaults CurrmodsLine Description Point CSM/FSM Equipment Table Type 621H, BlockDescription Status Point Appendix B Fluid Drop Pressure Curves Cooler Fluid Pressure Drop Curves 30GUN,GUR040-110Cooler Fluid Pressure Drop Curves 30GUN,GUR130-210 Appendix B Fluid Drop Pressure CurvesCooler Pressure Drop KEY Appendix B Fluid Drop Pressure Curves Cooler Fluid Pressure Drop Curves 30GUN,GUR230B-315B Cooler Fluid Pressure Drop Curves 30GTN,GTR040-110 Cooler Fluid Pressure Drop Curves 30GTN,GTR130-210 Appendix B Fluid Drop Pressure Curves Module B 30GTN,GTR230,245 Module B 30GTN,GTR255,290,315 Service Training Call for Free CatalogRemove and use for job file Preliminary Information START-UP Checklist for Comfortlink Chiller SystemsEquipment Chiller Model no Preliminary Equipment Check Check box if complete System Fluid Volume in Loop Type System UnitStart-UpUnit Start-Up Ccnb Description Status Units Value CtrlCcna BaudSlct Heating Cooling Setpoint Select CND.P RMT.A All Units

Air Conditioner specifications

Carrier Air Conditioners have long been synonymous with reliability and innovation in climate control. Founded by Willis Carrier, the inventor of modern air conditioning, the brand has continuously set industry standards through state-of-the-art technologies and features designed to enhance indoor comfort.

One of the standout features of Carrier air conditioners is their energy efficiency. Many models are equipped with advanced inverter technology, allowing the compressor to adjust its speed based on the cooling demand. This results in decreased energy consumption, which not only reduces utility bills but also lessens the environmental impact. Recognizing the importance of sustainable practices, Carrier has integrated eco-friendly refrigerants into their systems, further promoting energy-efficient operations.

Carrier also emphasizes user comfort through its variable speed systems. These systems maintain consistent temperatures while minimizing temperature fluctuations, ensuring an even distribution of cool air throughout the home. Additionally, many Carrier models come with advanced air filtration systems, designed to capture allergens, dust, and other particulates, thereby improving indoor air quality.

The smart technology featured in Carrier air conditioners plays a key role in modern convenience. Many units are compatible with smart home systems, allowing users to control settings remotely via smartphones or voice-activated devices. With features like programmable thermostats, users can easily set cooling schedules to match their lifestyle, ensuring comfort while maximizing energy savings.

Durability and noise reduction are also central to the Carrier brand. Many models are designed with sound-dampening features, making them some of the quietest units on the market. This is particularly advantageous for residential use, where noise can disrupt daily activities and sleep.

In terms of design, Carrier air conditioners come in various styles and capacities to suit a wide range of spaces, from compact apartment units to large central systems for sprawling homes. Their extensive warranty and service offerings further reinforce Carrier’s commitment to customer satisfaction.

In conclusion, Carrier air conditioners represent a perfect blend of cutting-edge technology, energy efficiency, and user comfort. Their emphasis on sustainability and smart features positions them as a leading choice for homeowners seeking reliable and innovative climate control solutions. Whether for cooling a small room or an entire house, Carrier remains a trusted name in air conditioning.