Carrier Air Conditioner specifications Compressor Protection Control System Module Sizes

Page 15

Thermostatic Expansion Valves (TXV) — Model 30GTN,R and 30GUN,R 040-110 units are available from the factory with conventional TXVs with liquid line solenoids. The liquid line solenoid valves are not intended to be a mechanical shut-off. When service is required, use the liquid line service valve to pump down the system.

NOTE: This option is not available for modular units.

The TXV is set at the factory to maintain approximately 8 to 12° F (4.4 to 6.7° C) suction superheat leaving the cooler by metering the proper amount of refrigerant into the cooler. All TXVs are adjustable, but should not be adjusted unless abso- lutely necessary. When TXV is used, thermistors T5, T6, T7, and T8 are not required.

The TXV is designed to limit the cooler saturated suction temperature to 55 F (12.8 C). This makes it possible for unit to start at high cooler fluid temperatures without overloading the compressor.

Compressor Protection Control System (CPCS [CPCS — Standard on Sizes 080-110 and Optional on Sizes 040-070]) or Control Relay (CR) — 30GTN,R and 30GUN,R 040-110Each compressor has its own CPCS module or CR. See Fig. 13 for CPCS module. The CPCS or CR is used to control and protect the compressors and crankcase heaters. The CPCS and CR pro- vide the following functions:

compressor contactor control/crankcase heater

crankcase heater control

compressor ground current protection (CPCS only)

status communication to processor board

high-pressure protection

One large relay is located on the CPCS board. This relay controls the crankcase heater and compressor contactor, and also provides a set of signal contacts that the microprocessor monitors to determine the operating status of the compressor. If the processor board determines that the compressor is not oper- ating properly through the signal contacts, it will lock the com- pressor off by deenergizing the proper 24-v control relay on the relay board. The CPCS board contains logic that can detect if the current-to-ground of any compressor winding exceeds

2.5amps. If this condition occurs, the CPCS shuts down the compressor.

A high-pressure switch is wired in series between the MBB and the CR or CPCS. On compressor A1 and B1 a loss-of- charge switch is also wired in series with the high-pressure switch. If the high-pressure switch opens during operation of a compressor, the compressor will be stopped, the failure will be detected through the signal contacts, and the compressor will be locked off. If the lead compressor in either circuit is shut down by the high-pressure switch, loss-of-charge switch, ground current protector, or oil safety switch, all compressors in that circuit are shut down.

NOTE: The CR operates the same as the CPCS, except the ground current circuit protection is not provided.

Compressor Ground Current Protection Board (CGF) and Control Relay (CR) — The 30GTN,R and 30GUN,R 130-210, and associated modular units (see Table 1) contain one compressor ground current pro- tection board (CGF) (see Fig. 14) for each refrigeration circuit. The CGF contains logic that can detect if the current-to-ground

of any compressor winding exceeds 2.5 amps. If this occurs, the lead compressor in that circuit is shut down along with oth- er compressors in that circuit.

A high-pressure switch is wired in series between the MBB and the CR. On compressor A1 and B1 a loss-of-charge switch is also wired in series with the high-pressure switch. The lead compressor in each circuit also has the CGF contacts described above. If any of these switches open during operation of a com- pressor, the CR relay is deenergized, stopping the compressor and signaling the processor at the MBB-J9 inputs to lock out the compressor. If the lead compressor in either circuit is shut down by high-pressure switch, compressor ground fault, oil pressure switch, or the loss-of-charge switch, all compressors in that circuit are also shut down.

Fig. 13 — Compressor Protection Control

System Module — Sizes 040-110

Fig. 14 — Compressor Ground Fault Module

Sizes 130-210

15

Image 15
Contents Contents Safety ConsiderationsContents GeneralIntroduction Unit Nominal Section a Section B 30GTN,R Tons Unit 30GTN,R Major System ComponentsUnit Sizes and Modular Combinations 30GTN,R Unit Sizes and Modular Combinations 30GUN,RControl Module Communication Carrier Comfort Network CCN InterfaceThermistor Designations Output Relay Status SwitchesPage 24 V Control Schematic, Unit Sizes 24 V Control Schematic, Unit Sizes 080-110, 230B-315B CCN LEN Data Communication Port Main Base Board 040-110 130-210 Operating Data Thermistor T3 and T4 Locations Compressor Thermistor Locations T7 and T8 Columbia D6451 Manhattan M13402 M64430 Quabik 6130 Regular Wiring Plenum Wiring Alpha 1895 AmericanManufacturer Belden 8205Compressor Protection Control System Module Sizes Stepper Motor 12 VDC CEPL130351 Approx Part Load Data Percent Displacement, Standard UnitsDisplacement Compressors 30GUN,R255A 60 Hz 110, 290B390B 50 Hz 330A/B360B 50 Hz 390B 60 HzB1† A1,B1 A1†,A2,B1 A1*,B1†,B2 Unloaded compressor Two unloaders, both unloaded 190, 290A, 360A/B 170, 270AA1*,B1*,B2 150-210 Required Hardware for Additional UnloadersPumpout Head Pressure ControlFAN Arrangement FAN Relay Normal Control PowerScrolling Marquee Display Service Test See Both main powerGEN.O Test ModesVers Run Status Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry View StrtService Test Mode and Sub-Mode Directory SUB-MODE Keypad Range Item Expansion Comment Entry TestOuts Temperature Mode and Sub-Mode Directory Pressure Mode and Sub-Mode DirectorySet Point Mode and Sub-Mode Directory Crct Inputs Mode and Sub-Mode DirectoryReading and Changing Chilled Fluid Set Point SUB-MODE Keypad Range Item Expansion Comment Entry GEN.IOutputs Mode and Sub-Mode Directory Configuration Mode and Sub-Mode DirectorySUB-MODE Keypad Range Item Expansion Comment Entry GEN.O EMM OPT1OPT2 CCNRset 240SUB-MODE Keypad Display Item Expansion Comment Entry Rset Example of Temperature Reset Return Fluid ConfigurationExample of Configuring Dual Chiller Control Master Chiller Example of Configuring Dual Chiller Control Slave ChillerSUB-MODE Keypad Entry Display Item Expansion Comment Rset SUB-MODE Keypad Entry Item Expansion Comment Range Time Example of Compressor Lead/Lag ConfigurationTime Clock Mode and Sub-Mode Directory SUB-MODE Keypad Display Item Expansion Comment Entry OPT2Operating Mode and Sub-Mode Directory Setting an Occupied Time ScheduleOperating Modes Mode no Item Expansion DescriptionExample of Reading and Clearing Alarms Alarms Mode and Sub-Mode DirectoryEntry Expansion Configuring Temperature ResetMode Keypad SUB-MODE ConfigurationRED LED Entry Expansion Configuration DLS2 Configuring Demand LimitTo 20 mA Demand Limiting TroubleshootingPage T051 Alarm and Alert CodesLCW By Control Method Cause Code Alert GENERATED?EWT FSMT173 T153T155 T170T206 T203T204 T205Compressor OIL Required ServiceElectronic Components Oil ChargeCooler Thermistor Locations Components for Part Number Plugging PlugsCooler Head Bolt Tightening Sequence Typical Tube Sheet Condenser CoilsDimension FAN Type Condenser Fan Adjustment Hz Low Noise Fan Option UnitsRefrigerant Feed Components Each circuit has Printed Circuit Board ConnectorThermistors Temperature Sensors 5K Thermistor Temperature F vs Resistance/Voltage Drop BDrop a 5K Thermistor Temperature C vs Resistance/Voltage Temp Voltage Resistance Drop 200,510 30GUN,R Units Pressure Switch Settings Psig kPaSwitch Cutout CUT-IN 30GTN,R UnitsSystem Check PRE-START-UPSTART-UP and Operation Temperature Limits for Standard UnitsTemperature Maximum Ambient Temperature 125Field Wiring Refrigerant CircuitNominal and Minimum Cooler Fluid Flow Rates ALM CWPHgbps Energy Management Module EMM Wiring Compressor Expansion Board CXB Accessory Wiring Description Status Default Point Unit Configuration SettingsOPTIONS1 Options Configuration Description Status Default Units PointOPTIONS2 Options Configuration Alarmdef Alarm Definition TableAppendix a CCN Tables Brodefs Broadcast POC Definition Table Resetcon Temperature Reset and Demand LimitDescription Status Units Point Forceable Aunit General Unit ParametersCircaan Circuit a Analog Parameters Circadio Circuit a Discrete ParametersCircbdio Circuit B Discrete Parameters Circban Circuit B Analog ParametersOptions Unit Parameters Description Status Units Point StrthourCurrmods Description Status Units Point DefaultsCSM/FSM Equipment Table Type 621H, Block Line Description PointDescription Status Point Cooler Fluid Pressure Drop Curves 30GUN,GUR040-110 Appendix B Fluid Drop Pressure CurvesAppendix B Fluid Drop Pressure Curves Cooler Fluid Pressure Drop Curves 30GUN,GUR130-210Cooler Pressure Drop KEY Appendix B Fluid Drop Pressure Curves Cooler Fluid Pressure Drop Curves 30GUN,GUR230B-315B Cooler Fluid Pressure Drop Curves 30GTN,GTR040-110 Cooler Fluid Pressure Drop Curves 30GTN,GTR130-210 Appendix B Fluid Drop Pressure Curves Module B 30GTN,GTR230,245 Module B 30GTN,GTR255,290,315 Call for Free Catalog Service TrainingSTART-UP Checklist for Comfortlink Chiller Systems Remove and use for job file Preliminary InformationEquipment Chiller Model no Preliminary Equipment Check Check box if complete UnitStart-Up System Fluid Volume in Loop Type SystemUnit Start-Up Baud Description Status Units Value CtrlCcna CcnbSlct Heating Cooling Setpoint Select CND.P RMT.A All Units