RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*
(120 or 240 VOLT)
NAMEPLATE |
| EXTENSION CORD LENGTH |
| ||||
AMPERES |
|
| |||||
|
|
|
|
| |||
(at full load) |
|
|
|
|
| ||
25 Feet | 50 Feet | 75 Feet | 100 Feet | 150 Feet | |||
|
| ||||||
|
|
|
|
|
| ||
0 – 2.0 | 18 | 18 | 18 | 18 | 16 | ||
2.1 | – 3.4 | 18 | 18 | 18 | 16 | 14 | |
3.5 | – 5.0 | 18 | 18 | 16 | 14 | 12 | |
5.1 | – 7.0 | 18 | 16 | 14 | 12 | 12 | |
7.1 – 12.0 | 18 | 14 | 12 | 10 | - | ||
12.1 | – 16.0 | 14 | 12 | 10 | - | - | |
16.1 | – 20.0 | 12 | 10 | - | - | - | |
FIGURE C | *Basedonlimitingthelinevoltagedroptofivevoltsat150%oftheratedamperes. |
|
|
|
| Symbology |
|
|
|
|
| ||
|
|
| Double Insulated | ||
|
|
| |||
|
|
|
| ||
|
|
|
|
|
|
|
|
| Canadian Standards Association | ||
|
|
|
| ||
|
|
| Underwriters Laboratories, Inc. | ||
|
|
|
| ||
V~ | Volts Alternating Current | ||||
| A | Amperes | |||
|
|
| |||
|
|
|
| ||
n0 xxxx/min. | No Load Revolutions per Minute | ||||
|
|
| (RPM) |