Proview 6537-22 Grounding, Extension Cords, Double Insulated Tools Tools with Two Prong Plugs

Page 4

GROUNDING

WARNING!

Improperly connecting the grounding wire can result in the risk of electric shock. Check with a qualified electrician if you are in doubt as to whether the outlet is properly grounded. Do not modify the plug provided with the tool. Never remove the grounding prong from the plug. Do not use the tool if the cord or plug is damaged. If damaged, have it repaired by a MILWAUKEE service facility before use. If the plug will not fit the outlet, have a proper outlet installed by a qualified electrician.

Grounded Tools:

Tools with Three Prong Plugs

Tools marked “Grounding Required” have a three wire cord and three prong grounding plug. The plug must be connected to a properly grounded outlet (See Figure A). If the tool should

electrically malfunction

or break

down, grounding provides a low re-

sistance path to carry electricity

away from the user, reducing the risk

of electric shock.

Fig. A

The grounding prong in the plug is connected through the green wire inside the cord to the grounding system in the tool. The green wire in the cord must be the only wire connected to the tool's grounding system and must never be attached to an electrically “live” terminal.

Your tool must be plugged into an appropriate outlet, properly installed and grounded in accordance with all codes and ordinances. The plug and outlet should look like those in Figure A.

Double Insulated Tools:

Tools with Two Prong Plugs

Tools marked “Double Insulated” do

 

 

not require grounding. They have a

 

 

special double insulation system

 

 

which satisfies OSHA requirements

 

 

and complies with the applicable

 

 

standards of Underwriters Labora-

 

 

tories, Inc., the Canadian Standard

 

 

Association and the National Electri-

 

 

cal Code. Double Insulated tools may

 

 

be used in either of the 120 volt out-

Fig. B

Fig. C

lets shown in Figures B and C.

 

 

page 4

EXTENSION CORDS

Grounded tools require a three wire extension cord. Double insulated tools can use either a two or three wire extension cord. As the distance from the supply outlet increases, you must use a heavier gauge exten- sion cord. Using extension cords with inadequately sized wire causes a serious drop in voltage, resulting in loss of power and possible tool damage. Refer to the table shown to determine the required minimum wire size.

The smaller the gauge number of the wire, the greater the capacity of the cord. For example, a 14 gauge cord can carry a higher current than a 16 gauge cord. When using more than one extension cord to make up the total length, be sure each cord contains at least the minimum wire size required. If you are using one extension cord for more than one tool, add the nameplate amperes and use the sum to determine the required mini- mum wire size.

Guidelines for Using Extension Cords

If you are using an extension cord outdoors, be sure it is marked with the suffix “W-A” (“W” in Canada) to indicate that it is acceptable for outdoor use.

Be sure your extension cord is properly wired and in good electrical condition. Always replace a damaged extension cord or have it repaired by a qualified person before using it.

Protect your extension cords from sharp objects, excessive heat and damp or wet areas.

Recommended Minimum Wire Gauge

for Extension Cords*

Nameplate

 

Extension Cord Length

 

 

 

 

 

 

Amperes

25'

50'

75'

100'

150'

200'

 

 

 

 

 

 

 

0 - 5

16

16

16

14

12

12

5.1

- 8

16

16

14

12

10

--

8.1 - 12

14

14

12

10

--

--

12.1

- 15

12

12

10

10

--

--

15.1

- 20

10

10

10

--

--

--

 

 

 

 

 

 

 

 

*Based on limiting the line voltage drop to five volts at 150% of the rated amperes.

READ AND SAVE ALL INSTRUCTIONS

FOR FUTURE USE.

Image 4
Contents Operators Manual General Safety Rules Read and Understand ALL Instructions Electrical Safety Tool USE and CarePersonal Safety ServiceSpecific Safety Rules Sawzalls FunctionaldescriptionGuidelines for Using Extension Cords Recommended Minimum Wire Gauge For Extension CordsGrounding Extension CordsTool Assembly Operation Maintenance CleaningGeneral Cutting Cutting MetalsTWO Year Tool Limited Warranty AccessoriesConservez CES Instructions Aire DE Travail Sécurité ÉlectriqueUtilisation ET Entretien DES Outils Sécurité DES Personnes RéparationRègles DE Sécurité Spécifiques Sawzalls DescriptionfonctionnelleNo de Volts Longueur Cycles CA seul De course Par minute 6537-22 120 32 mm 1-1/4Calibres minimaux recommandés pour Les cordons de rallonge Mise À LA Terre AvertissementCordons DE Rallonge Directives pour l’emploi des cordons de rallongeMontage DE Loutil Avertissement Choix d’une lameModèles de la fixation de lame Quik-LokFig Entretien de la fixation de lame Quik-LokRetrait d’une lame brisée de la fixation de lame Quik-Lok Réglage de la semelle FigManiement Avertissement Maintenance Avertissement NettoyageAccessoires Avertissement Garantie Limitée DE L’OUTIL DE Deux ANSModèles spécifiques Fixation de lame Vis de fixationGuarde Estas Instrucciones Area DE Trabajo Seguridad ElectricaUSO Y Mantenimiento DE LA Herramienta Seguridad PersonalReglas Especificas DE Seguridad Sawzalls DescripcionfuncionalCat Volts ca~ Largo de Carreras Carrera Por Minuto 6537-22 120 32 mm 1-1/4Extensiónes Eléctricas Tierra ¡ADVERTENCIAGuías para el uso de cables de extensión Seleccionando las seguetas Ensambaje DE LA Herramienta ¡ADVERTENCIAModelos de la abrazadera de la sequeta Quik-LokFig Mantenimiento de la abrazadera de la segueta Quik-Lok Ajuste de la zapata FigOperacion ¡ADVERTENCIA Mantenimiento ¡ADVERTENCIA LimpiezaGarantía Limitada DE DOS Años Accesorios ¡ADVERTENCIAModelos especificas Seguro de la segueta Tornillo del seguro de la seguetaMateriales Emplastados Seguetas Para Calar En Metal Ax Baldes Ax Baldes Hojas Ax United States