Repair
Replacing a Communication Gateway Module
NOTICE
To avoid damaging the circuit boards when servicing the control box, wear Part No. 112190 grounding strap on your wrist and ground appropriately.
To avoid electrical component damage, remove all system power before plugging any connectors.
1.Follow the steps in Before Servicing, page 34.
2.Loosen the screws (124) and remove the enclosure cover (117).
3.Remove the screws (182b) holding the communication gateway module (CGM) to the module base. Remove the CGM. You do not have to disconnect the cables.
4.Install the new CGM (182a), using the screws (182b).
5.Turn on power at the main circuit breaker.
6.Turn on the control box power switch. Check that the three status indicator lights are green.
7.Reinstall the cover (117) and tighten the screws (124).
Figure 30 Replacing a Communication Gateway Module
332709B | 45 |