Carrier 40QAC Complete Outdoor Refrigerant Piping Connec- tions, Connection at Outdoor Unit

Page 12

40QAC/38HDR -- 40QAQ/38QRR

Complete Outdoor Refrigerant Piping Connec- tions

Follow the following general guidelines:

1.Use refrigerant grade field – supplied tubing. Refer to Table 4 for the correct line sizes.

2.Do not use less than 10 ft (93.05 m) of interconnecting tubing.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

If any section of pipe is buried, there must be a 6 in. (152.4

mm)vertical rise to the valve connections on the outdoor unit. If more than the recommended length is buried, refrigerant may migrate to cooler, buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start-up.

When more than 80 ft (24.4 m) of interconnecting tubing is used, consult the Duct-Free Split System Long Line Application Guide for required accessories.

3.On cooling only units, insulate the liquid line. On heat pumps, insulate both lines. A minimum of 1/2 inch foam pipe insulation is recommended.

4.Run the refrigerant tubes as directly as possible and avoid unnecessary turns and bends.

5.Suspend refrigerant tubes to avoid damage to insulation or tubes so they do not transmit vibration to the structure.

6.When passing refrigerant tubes through the wall, seal the opening so rain and insects do not enter the structure. Leave some slack in refrigerant tubes between structure and out- door unit to absorb vibration.

NOTE: A fusible plug is located in unit suction line; do not cap this plug. If local codes require additional safety devices, install as directed.

Connection at Outdoor Unit

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

To prevent damage to unit or service valves observe the following:

SA brazing shield MUST be used.

SWrap service valves with wet cloth or use a heat sink material.

1.Braze the connector tubes (field supplied for the 38HDR units and factory supplied for the 38QRR units) to the inlet of the factory supplied filter drier. If a cooling only unit is being installed move to step 3 (see Fig. 8).

2.Remove the plastic cap from the liquid and suction service valve on the 38QRR unit and assemble the heating piston and piston cap supplied with the outdoor unit as shown in Fig. 16.

NOTE: Teflon Seal must face toward the outdoor heat pump unit.

A09538

Fig. 16 - AccuRater Metering Device at Service

Valve (Bypass Type Components),

Heat Pump Systems Only

NOTE: The Teflon seal on the piston should point towards the liquid service valve.

The size of the factory supplied piston might have to adjusted for long line applications (over 80 ft / 24.4 m). Refer to the Duct Free Long Line Application Guide for additional information.

3.On 38HDR units, remove the plastic caps on the liquid and suction service valves. Braze the completed filter drier as- sembly (from Step 1) to the liquid service valve. On the 38QRR unit, connect the completed filter drier assembly (from Step 1) to the piston cap.

4.Braze the field supplied line set to the filter drier assembly and to the suction valve.

5.Insulate any exposed areas between the filter drier and the liquid valve.

Complete Outdoor Power and Control Wiring

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation could void any applicable Carrier warranty.

12

Image 12
Contents Safety Considerations 40QAC, QAQ Unit38HDR, QRR Unit Dimensions Indoor UnitSize 38HDR Outdoor Unit Dimensions English 38HDR Outdoor Unit Dimensions SI 38QRR Outdoor Unit Dimensions English 38QRR Outdoor Unit Dimensions SI Parts List System RequirementsPower and Connecting Cables Field Supplied User Interface Finished Goods AccessoryInstallation Fan Coil Unit Hanging Dimensions Mounting on Ground Mounting on RoofMounting Unit on Wall Complete Outdoor Power and Control Wiring Complete Outdoor Refrigerant Piping Connec- tionsConnection at Outdoor Unit Power Wiring Line Power Connections38HDR Electrical Data 38QRR Electrical Data40QAC/QAQ Electrical Data 38HDR and 40QAC Cooling System Wiring Diagram 38QRR and 40QAQ Heat Pump System Wiring Diagram Complete Indoor Piping Connect Condensate Drain LineComplete Control Wiring Complete Power Connection To Indoor UnitInstall Thermostat Using Vacuum Pump START-UPReassemble Indoor Unit Preliminary ChecksTo Start the Unit Manifold Deep Vacuum MethodCleaning and Maintenance Operating SequenceService To clean the outdoor coilTo clean or replace drain pan Cleaning and Maintenance ScheduleTroubleshooting Before Calling for ServiceTroubleshooting Problem Cause Typical SolutionTroubleshooting the Heating Cycle Troubleshooting the Cooling Cycle 2SI

40QAC specifications

The Carrier 40QAC is a standout product in the realm of commercial air conditioning systems. This air-cooled chiller is designed to meet a variety of cooling needs while ensuring energy efficiency and reliability. One of the most notable features of the 40QAC is its advanced scroll compressor technology, which is engineered to provide consistent performance with reduced noise levels. This makes it an ideal choice for applications where minimizing sound pollution is crucial, such as in urban settings or near sensitive environments.

In terms of energy efficiency, the 40QAC boasts impressive ratings, with a high coefficient of performance (COP) that helps to lower operational costs and reduce environmental impact. Its design integrates various energy-saving features, including variable speed fans and a robust control system that optimizes performance based on real-time demand. This adaptability allows the chiller to maintain comfort levels while consuming less energy than traditional models.

The 40QAC is equipped with a microprocessor-based control system that simplifies operation and enhances user experience. This intelligent control interface allows operators to monitor performance metrics, adjust settings, and troubleshoot any issues remotely, increasing overall system reliability. The system is also designed to be compatible with building management systems, which facilitates seamless integration into existing infrastructure.

Another prominent characteristic of the Carrier 40QAC is its robust construction. Built with high-quality materials, it offers excellent durability and longevity, even in challenging environmental conditions. The unit also incorporates features to streamline maintenance, such as accessible component layout and easy-to-remove panels, ensuring that downtime for servicing is minimized.

Safety is another critical aspect of the Carrier 40QAC’s design. It’s engineered with numerous safety protocols to protect against overheating, overpressure, and other potential hazards, guaranteeing both system integrity and peace of mind for operators.

Overall, the Carrier 40QAC is a versatile and efficient solution for commercial cooling needs. With its technological advancements, energy-saving features, and robust design, it stands out as a reliable choice for businesses looking to balance performance with sustainability. The 40QAC not only promises efficient cooling but does so while aligning with the growing demand for eco-friendly solutions in today's marketplace.