RECOMMENDED MINIMUM WIRE GAUGE FOR EXTENSION CORDS*

(120/240 VOLT)

NAMEPLATE

AMPERES

(at full load)

0 – 2.0

2.1– 3.4

3.5– 5.0

5.1– 7.0

7.1– 12.0

12.1– 16.0

16.1– 20.0

TABLE A

EXTENSION CORD

LENGTH

25’

50’

75’

100’

150’

18

18

18

18

16

18

18

18

16

14

18

18

16

14

12

18

16

14

12

12

18

14

12

10

-

14

12

10

-

-

12

10

-

-

-

 

 

 

 

 

*Based on limiting the line voltage drop to five volts at

150% of the rated amperes.

Symbology

Double Insulated

 

Canadian Standards Association

 

 

 

Underwriters Laboratories, Inc.

 

 

V~

Volts Alternating Current

A

Amperes

 

 

 

n0 xxxx/min.

No Load Revolutions per Minute

(RPM)

SKU 99702

For technical questions, please call 1-800-444-3353.

Page 8

Image 8
Contents For technical questions or replacement parts, please call Distributed exclusively by Harbor Freight ToolsFor technical questions, please call General Power Tool SafetySave This Manual Gfci reduces the risk of electric shock Spray Machine Safety Warnings Vibration Safety Plug and Outlet GroundingGrounded Tools Tools with Three Prong Plugs Double Insulated Tools Tools With Two Prong Plugs Extension CordsPlug Outlets for 2-Prong PlugSymbology 25’ 50’ 75’ 100’ 150’Instructions for putting into use SpecificationsAssemblyUnpacking Tool Set Up Operating InstructionsWork Piece and Work Area Set Up General Operating InstructionsFill the pump with oil Purge and prime the SprayerPainting Purge and prime the HoseAttach the Spray Tip For technical questions, please call Maintenance Servicing Cleaning, Maintenance, LubricationFor technical questions, please call Troubleshooting Problem Possible Causes Likely SolutionsRecord Product’s Serial Number Here Pump Parts ListPart Description Qty Pump diagram Pump diagram Suction tube assembly Parts List & diagram Gun Parts List Diagram Limited 90 DAY Warranty