Carrier 48EZ-A Check Heating Control, Check Gas Input, Adjust Gas Input, Unit Damage Hazard

Page 16

48EZ -- A

BURNER FLAME

BURNER

MANIFOLD

C99021

Fig. 12 - Monoport Burner

Check Heating Control

Start and check the unit for proper heating control operation as follows (see furnace lighting instructions located on the inside of the control access panel):

1.Place room thermostat SYSTEM switch in the HEAT position and the fan switch is placed in AUTO position.

2.Set the heating temperature control of the thermostat above room temperature.

3.The induced-draft motor will start.

4.On a call for heating, the main burner should light within 5 sec. of the spark being energized. If the burners do not light, there is a 22-sec. delay before another 5-sec. try. If the burners still do not light, this sequence is repeated. If the burners do not light within 15 minutes from the initial call for heat, there is a lockout. To reset the control, break the 24-v power to W.

5.The evaporator fan will turn on 45 sec. after the flame has been established. The evaporator fan will turn off 45 sec. after the thermostat has been satisfied. Please note that the integrated gas unit controller (IGC) has the capability to automatically reduce the evaporator “ON” delay and in- crease the evaporator “OFF” delay in the event of high duct static and/or partially-clogged filter.

Check Gas Input

Check gas input and manifold pressure after unit start-up (See Table 3). If adjustment is required proceed as follows:

SThe rated gas inputs shown in Table 3 are for altitudes from sea level to 2000 ft (610 m) above sea level. These inputs are based on natural gas with a heating value of 1025 Btu/ft3 at 0.60 specific gravity, or propane gas with a heating value of 2500 Btu/ft3 at 1.5 specific gravity.

IN THE U.S.A.:

The input rating for altitudes above 2,000 ft (610 m) must be reduced by 4% for each 1,000 ft (305 m) above sea level.

For installations below 2,000 ft (610 m), refer to the unit rating plate.

For installations above 2,000 ft (610 m) multiply the input by on the rating plate by the derate multiplier in Table 4 for correct input rate.

Table 4 – Altitude Derate Multiplier for U.S.A.*

ALTITUDE FT (M)

PERCENT OF DERATE

DERATE MULTIPLIER

FACTOR{

 

 

 

 

 

 

0---2000

0

1.00

(0---610)

 

 

 

 

 

2001---3000*

8--- 12

0.90

(610

---914)

 

 

 

 

 

 

3001

---4000

12--- 16

0.86

(315---1219)

 

 

 

 

 

 

4001

---5000

16--- 20

0.82

(1220

---1524)

 

 

 

 

 

 

5001

---6000

20--- 24

0.78

(1524

---1829)

 

 

 

 

 

 

6001

---7000

24--- 28

0.74

(1829

---2134)

 

 

 

 

 

 

7001

---8000

28--- 32

0.70

(2134

---2438)

 

 

 

 

 

 

8001

---9000

32--- 36

0.66

(2439

---2743)

 

 

 

 

 

9001---10,000

36--- 40

0.62

(2744

---3048)

 

 

*In Canada see Canadian Altitude Adjustment.

{Derate multiplier factors are based on midpoint altitude for altitude range.

IN CANADA:

The input rating for altitudes from 2,000 to 4,500 ft (610 m to 1372 m) above sea level must be derated 10% by an authorized Gas Conversion Station or Dealer.

EXAMPLE:

90,000 Btu/hr Input Furnace Installed at 4300 ft (1311 m).

Furnace Input Rate at

X

Derate Multiplier

=

Furnace Input Rate at

Sea Level

 

Factor

 

Installation Altitude

90,000

X

0.90

=

81,000

When the gas supply being used has a different heating value or specific gravity, refer to national and local codes, or contact your distributor to determine the required orifice size.

!CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in reduced unit and/or component life.

Do Not redrill an orifice. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise and misdirection of burner flame. If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size.

Adjust Gas Input

The gas input to the unit is determined by measuring the gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natural gas units. The manifold pressure must be measured to determine the input of propane gas units.

Measure Gas Flow (Natural Gas Units)

Minor adjustment to the gas flow can be made by changing the manifold pressure. The manifold pressure must be maintained between 3.2 and 3.8 IN. W.C.

If larger adjustments are required, change main burner orifices following the recommendations of national and local codes.

NOTE: All other appliances that use the same meter must be turned off when gas flow is measured at the meter.

Proceed as follows:

1.Turn off gas supply to unit.

2.Remove pipe plug on manifold (See Fig. 11) and connect manometer. Turn on gas supply to unit.

3.Record number of seconds for gas meter test dial to make one revolution.

16

Image 16
Contents Table of Contents Safety ConsiderationsReceiving and Installation IntroductionCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Small Curb Rig and Place Unit Provide ClearancesPersonal Injury or Property Damage HazardInstall Flue Hood Install Gas PipingConnect Condensate Drain InspectionFire or Explosion Hazard Sediment TrapPhysical Data Unit 48EZ-A Unit Size 48EZMaximum Gas Flow Capacity Physical Data Unit 48EZ-A Cont’dHeating Inputs Install Duct Connections Configuring Units for Downflow Vertical DischargeAlternate Method Unit Component Damage HazardSupply Duct Panels Install Electrical Connections Special Procedures for 208-V OperationHigh-Voltage Connections Control Voltage ConnectionsBalance Point Setting-Thermidistat or Hybrid Thermostat PRE-START-UPTransformer Protection FIRE, EXPLOSION, Electrical Shock HazardStart-up Heating and Make Adjust- ments START-UPCheck for Refrigerant Leaks Unit Sequence of OperationAdjust Gas Input Check Heating ControlCheck Gas Input Unit Damage HazardAirflow and Temperature Rise Limit SwitchesRollout Switch Check Burner FlameStart-up Cooling and Make Adjust- ments Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Checking Cooling Control OperationTwo Cooling Fan Speeds Set-up Dehumidification feature used Gas Heating Fan Speed Set-upContinuous Fan Operation Color Coding for Indoor Fan Motor LeadsFilter Pressure Drop Table IN. W.C 48EZ-A Wet Coil Pressure Drop IN. W.C741 638 547 415 Heating Low Blue 1234 1168 1093 1021 961 894 825 759 687 Heating Low Blue 1736 1695 1642 1601 1553 1512 1465 1427 1381 65oF Heating 1927 1893 1858 1824 1791 1759 1720 1689 1640 65oF Heating 48EZ a 208/230-3-60 Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Maintenance Cleaning the Blower Motor and WheelAir Filter Indoor Blower and MotorLimit Switch Induced Draft combustion air Blower AssemblyBurner Ignition Main BurnersOutdoor Fan Electrical Controls and WiringRefrigerant Circuit Pressure Switches Loss of Charge SwitchGas Input Indoor AirflowCopeland Scroll Compressor Puron Refrigerant High-Pressure SwitchExplosion Hazard Refrigerant System Unit Operation and Safety HazardCompressor Oil START-UP Checklist TroubleshootingPuronr R-410A Quick Reference Guide Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyTroubleshooting Guide-Heating Troubleshooting Guide-LED Error CodesTemperatures Remove and Store in Job FilesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 48EZ---06SI
Related manuals
Manual 10 pages 39.3 Kb

48EZ-A specifications

The Carrier 48EZ-A and 48VT-A are two advanced rooftop unit air conditioners that exemplify innovation and efficiency in HVAC technology. Designed for commercial applications, these units provide optimal comfort while ensuring energy conservation and reliability.

One of the standout features of the Carrier 48EZ-A is its high-efficiency cooling system. With SEER ratings reaching up to 16, this model uses advanced compressor technology to ensure that energy consumption stays low while maximizing cooling output. The 48EZ-A incorporates a two-stage scroll compressor that enhances performance during partial load conditions, making it ideal for varying temperature demands throughout the day.

Meanwhile, the Carrier 48VT-A is designed with variable speed technology that allows for precise modulation of airflow and cooling capacity, adapting seamlessly to real-time building conditions. This technology not only improves comfort but also significantly reduces energy usage by optimizing operational efficiency.

Both units are equipped with advanced microprocessor controls that facilitate superior management of the HVAC system. The controls offer programmable options allowing for enhanced control over system operation, scheduling, and diagnostics. This promotes easy maintenance and ensures long-term reliability.

In terms of construction, the Carrier 48EZ-A and 48VT-A units are built with corrosion-resistant materials, ensuring durability and longevity even in challenging environments. The cabinet is designed with insulated panels to minimize sound levels, making them suitable for installation in noise-sensitive locations.

Moreover, both models are equipped for easy installation and serviceability. The logical wiring design and access ports streamline maintenance, reducing downtime and optimizing overall performance. Additionally, they feature an energy-efficient fan design that maximizes airflow while minimizing energy use.

In summary, the Carrier 48EZ-A and 48VT-A rooftop units stand out in the HVAC market for their energy efficiency, advanced technology, and durable construction. These features make them ideal choices for various commercial applications where comfort, efficiency, and reliability are paramount. The combination of high-performance components and user-friendly features positions these models as leaders in modern HVAC solutions.