Carrier 48EZ-A installation instructions Maintenance, Air Filter, Indoor Blower and Motor

Page 28

48EZ -- A

MAINTENANCE

To ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic maintenance must be performed on this equipment. This combination heating/cooling unit should be inspected at least once each year by a qualified service person. To troubleshoot cooling or heating of units, refer to Tables 10, 11 and 12.

NOTE: Consult your local dealer about the availability of a maintenance contract.

!WARNING

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal injury or death and unit component damage.

The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment, other than those procedures recommended in the Owner’s Manual.

!WARNING

ELECTRICAL SHOCK AND EXPLOSION HAZARD

Failure to follow these warnings could result in personal injury or death:

1.Turn off electrical power to the unit and install a lockout tag before performing any maintenance or service on this unit.

2.Use extreme caution when removing panels and parts.

3.Never place anything combustible either on or in contact with the unit.

4.Should overheating occur or the gas supply fail to shut off, turn off external main manual gas valve to the unit. Then shut off electrical supply.

!CAUTION

CUT HAZARD

Failure to follow this caution may result in personal injury.

When removing access panels (see Fig. 19) or performing maintenance functions inside your unit, be aware of sharp sheet metal parts and screws. Although special care is taken to reduce sharp edges to a minimum, be extremely careful when handling parts or reaching into the unit.

!CAUTION

UNIT OPERATION HAZARD

Failure to follow this caution may result in improper operation.

Errors made when reconnecting wires may cause improper and dangerous operation. Label all wires prior to disconnecting when servicing.

The minimum maintenance requirements for this equipment are as follows:

1.Inspect air filter(s) each month. Clean or replace when necessary. Certain geographical locations may require more frequent inspections.

2.Inspect indoor coil, outdoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean when necessary.

3.Inspect blower motor and wheel for cleanliness at the beginning of each heating and cooling season. Clean when necessary. For first heating and cooling season, inspect blower wheel bi-monthly to determine proper cleaning frequency.

4.Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary. Ensure electrical wiring is not in contact with refrigerant tubing or sharp metal edges.

5.Check and inspect heating section before each heating season. Clean and adjust when necessary.

6.Check flue hood and remove any obstructions, if necessary.

Air Filter

IMPORTANT: Never operate the unit without a suitable air filter in the return-air duct system. Always replace the filter with the same dimensional size and type as originally installed. (See Table 1 for recommended filter sizes.)

Inspect air filter(s) at least once each month and replace (throwaway-type) or clean (cleanable-type) at least twice during each heating and cooling season or whenever the filter(s) becomes clogged with dust and/or lint.

Indoor Blower and Motor

NOTE: All motors are prelubricated. Do not attempt to lubricate these motors.

For longer life, operating economy, and continuing efficiency, clean accumulated dirt and grease from the blower wheel and motor annually.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect and tag electrical power to the unit before cleaning and lubricating the blower motor and wheel.

Cleaning the Blower Motor and Wheel

1.Remove and disassemble blower assembly as follows:

a.Remove blower access panel (see Fig. 19).

b.Disconnect 5 pin plug and 4 pin plug from indoor blower motor. Remove capacitor if required.

c.On all units, remove blower assembly from unit. Remove screws securing blower to blower partition and slide assembly out. Be careful not to tear insulation in blower compartment.

d.Ensure proper reassembly by marking blower wheel and motor in relation to blower housing before disassembly.

e.Loosen setscrew(s) that secures wheel to motor shaft. Remove screws that secure motor mount brackets to housing, and slide motor and motor mount out of housing.

2.Remove and clean blower wheel as follows:

a.Ensure proper reassembly by marking wheel orientation.

b.Lift wheel from housing. When handling and/or cleaning blower wheel, be sure not to disturb balance weights (clips) on blower wheel vanes.

c.Remove caked-on dirt from wheel and housing with a brush. Remove lint and/or dirt accumulations from wheel and housing with vacuum cleaner, using soft brush attachment. Remove grease and oil with mild solvent.

d.Reassemble wheel into housing.

e.Reassemble motor into housing. Be sure setscrews are tightened on motor shaft flats and not on round part of shaft. Reinstall blower into unit. Reinstall capacitor.

28

Image 28
Contents Table of Contents Safety ConsiderationsReceiving and Installation IntroductionCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Small Curb Rig and Place Unit Provide ClearancesPersonal Injury or Property Damage HazardInstall Flue Hood Install Gas PipingConnect Condensate Drain InspectionFire or Explosion Hazard Sediment TrapPhysical Data Unit 48EZ-A Unit Size 48EZMaximum Gas Flow Capacity Physical Data Unit 48EZ-A Cont’dHeating Inputs Install Duct Connections Configuring Units for Downflow Vertical DischargeAlternate Method Unit Component Damage HazardSupply Duct Panels Install Electrical Connections Special Procedures for 208-V OperationHigh-Voltage Connections Control Voltage ConnectionsBalance Point Setting-Thermidistat or Hybrid Thermostat PRE-START-UPTransformer Protection FIRE, EXPLOSION, Electrical Shock HazardStart-up Heating and Make Adjust- ments START-UPCheck for Refrigerant Leaks Unit Sequence of OperationAdjust Gas Input Check Heating ControlCheck Gas Input Unit Damage HazardAirflow and Temperature Rise Limit SwitchesRollout Switch Check Burner FlameStart-up Cooling and Make Adjust- ments Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Checking Cooling Control OperationTwo Cooling Fan Speeds Set-up Dehumidification feature used Gas Heating Fan Speed Set-upContinuous Fan Operation Color Coding for Indoor Fan Motor LeadsFilter Pressure Drop Table IN. W.C 48EZ-A Wet Coil Pressure Drop IN. W.C741 638 547 415 Heating Low Blue 1234 1168 1093 1021 961 894 825 759 687 Heating Low Blue 1736 1695 1642 1601 1553 1512 1465 1427 1381 65oF Heating 1927 1893 1858 1824 1791 1759 1720 1689 1640 65oF Heating 48EZ a 208/230-3-60 Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Maintenance Cleaning the Blower Motor and WheelAir Filter Indoor Blower and MotorLimit Switch Induced Draft combustion air Blower AssemblyBurner Ignition Main BurnersOutdoor Fan Electrical Controls and WiringRefrigerant Circuit Pressure Switches Loss of Charge SwitchGas Input Indoor AirflowCopeland Scroll Compressor Puron Refrigerant High-Pressure SwitchExplosion Hazard Refrigerant System Unit Operation and Safety HazardCompressor Oil START-UP Checklist TroubleshootingPuronr R-410A Quick Reference Guide Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyTroubleshooting Guide-Heating Troubleshooting Guide-LED Error CodesTemperatures Remove and Store in Job FilesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 48EZ---06SI
Related manuals
Manual 10 pages 39.3 Kb

48EZ-A specifications

The Carrier 48EZ-A and 48VT-A are two advanced rooftop unit air conditioners that exemplify innovation and efficiency in HVAC technology. Designed for commercial applications, these units provide optimal comfort while ensuring energy conservation and reliability.

One of the standout features of the Carrier 48EZ-A is its high-efficiency cooling system. With SEER ratings reaching up to 16, this model uses advanced compressor technology to ensure that energy consumption stays low while maximizing cooling output. The 48EZ-A incorporates a two-stage scroll compressor that enhances performance during partial load conditions, making it ideal for varying temperature demands throughout the day.

Meanwhile, the Carrier 48VT-A is designed with variable speed technology that allows for precise modulation of airflow and cooling capacity, adapting seamlessly to real-time building conditions. This technology not only improves comfort but also significantly reduces energy usage by optimizing operational efficiency.

Both units are equipped with advanced microprocessor controls that facilitate superior management of the HVAC system. The controls offer programmable options allowing for enhanced control over system operation, scheduling, and diagnostics. This promotes easy maintenance and ensures long-term reliability.

In terms of construction, the Carrier 48EZ-A and 48VT-A units are built with corrosion-resistant materials, ensuring durability and longevity even in challenging environments. The cabinet is designed with insulated panels to minimize sound levels, making them suitable for installation in noise-sensitive locations.

Moreover, both models are equipped for easy installation and serviceability. The logical wiring design and access ports streamline maintenance, reducing downtime and optimizing overall performance. Additionally, they feature an energy-efficient fan design that maximizes airflow while minimizing energy use.

In summary, the Carrier 48EZ-A and 48VT-A rooftop units stand out in the HVAC market for their energy efficiency, advanced technology, and durable construction. These features make them ideal choices for various commercial applications where comfort, efficiency, and reliability are paramount. The combination of high-performance components and user-friendly features positions these models as leaders in modern HVAC solutions.