Carrier 48EZ-A installation instructions Install Electrical Connections, High-Voltage Connections

Page 13

Step 10 — Install Electrical Connections

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted, unbroken electrical ground. This ground may consist of an electrical wire connected to the unit ground screw in the control compartment, or conduit approved for electrical ground when installed in accordance with NEC, NFPA 70 National Fire Protection Association (latest edition) (in Canada, Canadian Electrical Code CSA C22.1) and local electrical codes.

!CAUTION

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the unit being installed.

1.Make all electrical connections in accordance with NEC NFPA 70 (latest edition) and local electrical codes governing such wiring. In Canada, all electrical connections must be in accordance with CSA standard C22.1 Canadian Electrical Code Part 1 and applicable local codes. Refer to unit wiring diagram.

2.Use only copper conductor for connections between field-supplied electrical disconnect switch and unit. DO NOT USE ALUMINUM WIRE.

3.Be sure that high-voltage power to unit is within operating voltage range indicated on unit rating plate. On 3-phase units, ensure phases are balanced within 2 percent. Consult local power company for correction of improper voltage and/or phase imbalance.

4.Insulate low-voltage wires for highest voltage contained within conduit when low-voltage control wires are in same conduit as high-voltage wires.

5.Do not damage internal components when drilling through any panel to mount electrical hardware, conduit, etc.

High-Voltage Connections

When routing power leads into unit, use only copper wire between disconnect and unit. The high voltage leads should be in a conduit until they enter the duct panel; conduit termination at the duct panel must be watertight.

The unit must have a separate electrical service with a field-supplied, waterproof disconnect switch mounted at, or within sight from, the unit. Refer to the unit rating plate, NEC and local codes for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.

The field-supplied disconnect switch box may be mounted on the unit over the high-voltage inlet hole when the standard power and low-voltage entry points are used (See Fig. 2 and 3 for acceptable location).

See unit wiring label (Fig. 15 and 16) and Fig. 10 for reference when making high voltage connections. Proceed as follows to complete the high-voltage connections to the unit.

Single phase units:

1.Run the high-voltage (L1, L2) and ground lead into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the line side of the contactor.

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

5.Connect field wire L2 to yellow wire on connection 23 of the compressor contactor.

Three-phase units:

1.Run the high-voltage (L1, L2, L3) and ground lead into the control box.

2.Connect ground lead to chassis ground connection.

3.Locate the black and yellow wires connected to the line side of the contactor.

4.Connect field L1 to black wire on connection 11 of the compressor contactor.

5.Connect field wire L3 to yellow wire on connection 13 of the compressor contactor.

6.Connect field wire L2 to blue wire from compressor.

Special Procedures for 208-V Operation

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Make sure the power supply to the unit is switched OFF before making any wiring changes. Tag the disconnect switch with a suitable warning label. With disconnect switch open, move black wire from transformer (3/16 in.) terminal marked 230 to terminal marked 200. This retaps transformer to primary voltage of 208 vac.

!WARNING

ELECTRICAL SHOCK AND EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death.

Before making any wiring changes, make sure the gas supply is switched off first. Then switch off the power supply to the unit and install lockout tag.

Control Voltage Connections

Do not use any type of power-stealing thermostat. Unit control problems may result.

Use no. 18 American Wire Gage (AWG) color-coded, insulated (35_C minimum) wires to make the control voltage connections between the thermostat and the unit. If the thermostat is located more than 100 ft (30.5 m) from the unit (as measured along the control voltage wires), use no. 16 AWG color-coded, insulated (35_C minimum) wires.

Locate the seven (eight on 3-phase) low voltage thermostat leads in 24 volt splice box. See Fig. 10 for connection diagram. Run the low-voltage leads from the thermostat, through the control wiring inlet hole grommet (Fig. 2 and 3), and into the low-voltage splice box. Provide a drip loop before running wires through panel. Secure and strain relief all wires so that they do not interfere with operation of unit. A gray wire is standard on 3-phase unit for connection to an economizer.

48EZ -- A

13

Image 13
Contents Safety Considerations Table of ContentsIntroduction Receiving and InstallationCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Small Curb Provide Clearances Rig and Place UnitPersonal Injury or Property Damage HazardInstall Gas Piping Install Flue HoodConnect Condensate Drain InspectionSediment Trap Fire or Explosion HazardUnit Size 48EZ Physical Data Unit 48EZ-AMaximum Gas Flow Capacity Physical Data Unit 48EZ-A Cont’dHeating Inputs Configuring Units for Downflow Vertical Discharge Install Duct ConnectionsAlternate Method Unit Component Damage HazardSupply Duct Panels Special Procedures for 208-V Operation Install Electrical ConnectionsHigh-Voltage Connections Control Voltage ConnectionsPRE-START-UP Balance Point Setting-Thermidistat or Hybrid ThermostatTransformer Protection FIRE, EXPLOSION, Electrical Shock HazardSTART-UP Start-up Heating and Make Adjust- mentsCheck for Refrigerant Leaks Unit Sequence of OperationCheck Heating Control Adjust Gas InputCheck Gas Input Unit Damage HazardLimit Switches Airflow and Temperature RiseRollout Switch Check Burner FlameChecking and Adjusting Refrigerant Charge Start-up Cooling and Make Adjust- mentsIndoor Airflow and Airflow Adjustments Checking Cooling Control OperationGas Heating Fan Speed Set-up Two Cooling Fan Speeds Set-up Dehumidification feature usedContinuous Fan Operation Color Coding for Indoor Fan Motor Leads48EZ-A Wet Coil Pressure Drop IN. W.C Filter Pressure Drop Table IN. W.C741 638 547 415 Heating Low Blue 1234 1168 1093 1021 961 894 825 759 687 Heating Low Blue 1736 1695 1642 1601 1553 1512 1465 1427 1381 65oF Heating 1927 1893 1858 1824 1791 1759 1720 1689 1640 65oF Heating 48EZ a 208/230-3-60 Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Cleaning the Blower Motor and Wheel MaintenanceAir Filter Indoor Blower and MotorInduced Draft combustion air Blower Assembly Limit SwitchBurner Ignition Main BurnersOutdoor Fan Electrical Controls and WiringRefrigerant Circuit Loss of Charge Switch Pressure SwitchesGas Input Indoor AirflowCopeland Scroll Compressor Puron Refrigerant High-Pressure SwitchExplosion Hazard Refrigerant System Unit Operation and Safety HazardCompressor Oil START-UP Checklist TroubleshootingPuronr R-410A Quick Reference Guide Symptom Cause Remedy Troubleshooting Guide Cooling or Heat Pump Heating ModeTroubleshooting Guide-LED Error Codes Troubleshooting Guide-HeatingRemove and Store in Job Files TemperaturesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 48EZ---06SI
Related manuals
Manual 10 pages 39.3 Kb

48EZ-A specifications

The Carrier 48EZ-A and 48VT-A are two advanced rooftop unit air conditioners that exemplify innovation and efficiency in HVAC technology. Designed for commercial applications, these units provide optimal comfort while ensuring energy conservation and reliability.

One of the standout features of the Carrier 48EZ-A is its high-efficiency cooling system. With SEER ratings reaching up to 16, this model uses advanced compressor technology to ensure that energy consumption stays low while maximizing cooling output. The 48EZ-A incorporates a two-stage scroll compressor that enhances performance during partial load conditions, making it ideal for varying temperature demands throughout the day.

Meanwhile, the Carrier 48VT-A is designed with variable speed technology that allows for precise modulation of airflow and cooling capacity, adapting seamlessly to real-time building conditions. This technology not only improves comfort but also significantly reduces energy usage by optimizing operational efficiency.

Both units are equipped with advanced microprocessor controls that facilitate superior management of the HVAC system. The controls offer programmable options allowing for enhanced control over system operation, scheduling, and diagnostics. This promotes easy maintenance and ensures long-term reliability.

In terms of construction, the Carrier 48EZ-A and 48VT-A units are built with corrosion-resistant materials, ensuring durability and longevity even in challenging environments. The cabinet is designed with insulated panels to minimize sound levels, making them suitable for installation in noise-sensitive locations.

Moreover, both models are equipped for easy installation and serviceability. The logical wiring design and access ports streamline maintenance, reducing downtime and optimizing overall performance. Additionally, they feature an energy-efficient fan design that maximizes airflow while minimizing energy use.

In summary, the Carrier 48EZ-A and 48VT-A rooftop units stand out in the HVAC market for their energy efficiency, advanced technology, and durable construction. These features make them ideal choices for various commercial applications where comfort, efficiency, and reliability are paramount. The combination of high-performance components and user-friendly features positions these models as leaders in modern HVAC solutions.