Carrier 48EZ-A High-Pressure Switch, Copeland Scroll Compressor Puron Refrigerant

Page 32

48EZ -- A

C99097

Fig. 25 - Refrigerant Circuit

2.Disconnect leads on switch.

3.Apply ohm meter leads across switch. You should have continuity on a good switch.

NOTE: Because these switches are attached to refrigeration system under pressure, it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exists. If switch must be removed, remove and recover all system charge so that pressure gauges read 0 psi. Never open system without breaking vacuum with dry nitrogen.

High-Pressure Switch

The high-pressure switch is located in the discharge line and protects against excessive condenser coil pressure. It opens at 650 psig.

High pressure may be caused by a dirty outdoor coil, failed fan motor, or outdoor air recirculation. To check switch:

1.Turn off all power to unit.

2.Disconnect leads on switch.

3.Apply ohm meter leads across switch. You should have continuity on a good switch.

Copeland Scroll Compressor (Puron Refrigerant)

The compressor used in this product is specifically designed to operate with Puron (R-410A) refrigerant and cannot be interchanged.

The compressor is an electrical (as well as mechanical) device. Exercise extreme caution when working near compressors. Power should be shut off, if possible, for most troubleshooting techniques. Refrigerants present additional safety hazards.

!WARNING

EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death and/or property damage.

Wear safety glasses and gloves when handling refrigerants. Keep torches and other ignition sources away from refrigerants and oils.

The scroll compressor pumps refrigerant throughout the system by the interaction of a stationary and an orbiting scroll. The scroll compressor has no dynamic suction or discharge valves, and it is more tolerant of stresses caused by debris, liquid slugging, and flooded starts. The compressor is equipped with an internal pressure relief port. The pressure relief port is a safety device, designed to protect against extreme high pressure. The relief port has an operating range between 550 and 625 psig differential pressure.

32

Image 32
Contents Table of Contents Safety ConsiderationsReceiving and Installation IntroductionCheck Equipment Provide Unit Support48EZ-A24-36 Unit Dimensions 48EZ-A42-60 Unit Dimensions Small Curb Rig and Place Unit Provide ClearancesPersonal Injury or Property Damage HazardInstall Flue Hood Install Gas PipingConnect Condensate Drain InspectionFire or Explosion Hazard Sediment TrapPhysical Data Unit 48EZ-A Unit Size 48EZHeating Inputs Physical Data Unit 48EZ-A Cont’dMaximum Gas Flow Capacity Install Duct Connections Configuring Units for Downflow Vertical DischargeAlternate Method Unit Component Damage HazardSupply Duct Panels Install Electrical Connections Special Procedures for 208-V OperationHigh-Voltage Connections Control Voltage ConnectionsBalance Point Setting-Thermidistat or Hybrid Thermostat PRE-START-UPTransformer Protection FIRE, EXPLOSION, Electrical Shock HazardStart-up Heating and Make Adjust- ments START-UPCheck for Refrigerant Leaks Unit Sequence of OperationAdjust Gas Input Check Heating ControlCheck Gas Input Unit Damage HazardAirflow and Temperature Rise Limit SwitchesRollout Switch Check Burner FlameStart-up Cooling and Make Adjust- ments Checking and Adjusting Refrigerant ChargeIndoor Airflow and Airflow Adjustments Checking Cooling Control OperationTwo Cooling Fan Speeds Set-up Dehumidification feature used Gas Heating Fan Speed Set-upContinuous Fan Operation Color Coding for Indoor Fan Motor LeadsFilter Pressure Drop Table IN. W.C 48EZ-A Wet Coil Pressure Drop IN. W.C741 638 547 415 Heating Low Blue 1234 1168 1093 1021 961 894 825 759 687 Heating Low Blue 1736 1695 1642 1601 1553 1512 1465 1427 1381 65oF Heating 1927 1893 1858 1824 1791 1759 1720 1689 1640 65oF Heating 48EZ a 208/230-3-60 Wiring Diagram, Unit 48EZ-A Cooling Charging Table-Subcooling Maintenance Cleaning the Blower Motor and WheelAir Filter Indoor Blower and MotorLimit Switch Induced Draft combustion air Blower AssemblyBurner Ignition Main BurnersRefrigerant Circuit Electrical Controls and WiringOutdoor Fan Pressure Switches Loss of Charge SwitchGas Input Indoor AirflowExplosion Hazard High-Pressure SwitchCopeland Scroll Compressor Puron Refrigerant Compressor Oil Unit Operation and Safety HazardRefrigerant System Puronr R-410A Quick Reference Guide TroubleshootingSTART-UP Checklist Troubleshooting Guide Cooling or Heat Pump Heating Mode Symptom Cause RemedyTroubleshooting Guide-Heating Troubleshooting Guide-LED Error CodesTemperatures Remove and Store in Job FilesPreliminary Information Model no III. START-UP Electrical Supply Voltage Compressor AmpsCatalog No 48EZ---06SI
Related manuals
Manual 10 pages 39.3 Kb

48EZ-A specifications

The Carrier 48EZ-A and 48VT-A are two advanced rooftop unit air conditioners that exemplify innovation and efficiency in HVAC technology. Designed for commercial applications, these units provide optimal comfort while ensuring energy conservation and reliability.

One of the standout features of the Carrier 48EZ-A is its high-efficiency cooling system. With SEER ratings reaching up to 16, this model uses advanced compressor technology to ensure that energy consumption stays low while maximizing cooling output. The 48EZ-A incorporates a two-stage scroll compressor that enhances performance during partial load conditions, making it ideal for varying temperature demands throughout the day.

Meanwhile, the Carrier 48VT-A is designed with variable speed technology that allows for precise modulation of airflow and cooling capacity, adapting seamlessly to real-time building conditions. This technology not only improves comfort but also significantly reduces energy usage by optimizing operational efficiency.

Both units are equipped with advanced microprocessor controls that facilitate superior management of the HVAC system. The controls offer programmable options allowing for enhanced control over system operation, scheduling, and diagnostics. This promotes easy maintenance and ensures long-term reliability.

In terms of construction, the Carrier 48EZ-A and 48VT-A units are built with corrosion-resistant materials, ensuring durability and longevity even in challenging environments. The cabinet is designed with insulated panels to minimize sound levels, making them suitable for installation in noise-sensitive locations.

Moreover, both models are equipped for easy installation and serviceability. The logical wiring design and access ports streamline maintenance, reducing downtime and optimizing overall performance. Additionally, they feature an energy-efficient fan design that maximizes airflow while minimizing energy use.

In summary, the Carrier 48EZ-A and 48VT-A rooftop units stand out in the HVAC market for their energy efficiency, advanced technology, and durable construction. These features make them ideal choices for various commercial applications where comfort, efficiency, and reliability are paramount. The combination of high-performance components and user-friendly features positions these models as leaders in modern HVAC solutions.